3.3.3 Relays

The MSP400RH transmitter has 2 integral relays which may be used for control purposes. These relays are light duty and should be used as signal relays only, with control functions being performed by external control relays.

Relay 2 is defaulted as a ‘fault’ relay, normally energised, but may be reconfigured on site as a set point relay if required.

3.4 Additional components in the two wire loop.

3.4.1 Lightning / surge protection and other loop devices

It is allowable to fit loop powered or separately powered devices in the two wire loop provided that the transmitter receives a minimum voltage of 12V dc at 21 mA loop current.

If the area is prone to lightning strikes or voltage surges, fitting of a suppressor device is desirable between the transmitter and the control unit.

3.5 Wiring to allow HART communication

If it is intended to use HART digital communications with the MSP400RH transmitter, a 250 Ohm 0.25W load resistor must be installed in the loop.

When used with the Mobrey MCU900 family of Control Units, there is no need to install an external load resistor in the loop as there is a suitable resistor built in to the Control Unit.

If the transmitter is being supplied through a safety barrier, ensure the type chosen will pass HART/ SMART information.

Once installed, a HART communicator can be connected across the load resistor, or across the loop at any point downstream of the load resistor.

12

IP2046/IM

Nov 2006

 

Image 12
Contents Mobrey Contents Introduction Pvdf Wetside Installation IP2046/IM IP2046/IM IP2046/IM Do not USE Housing to Tighten Ptfe RL1 Spst IP2046/IM Alarm IP2046/IM IP2046/IM Selecting the units of measurement Screen display 20/4 Ullage Liquid level SPEC. P CYL.F Scale LEUEL@ max Maximum flow entry Screen display IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM Loop IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM Duty Appendix A1 Main Menu ProgrammingSEt20 Appendix A1Appendix A2 Diagnostics Menu LeuelLoop Appendix A3 Commissioning / Loop Test MenuEngineering Menu Appendix A4Appendix B Default Value Listing Main Menu Parameters ProFDefault Value Listing Engineering Parameters DEAdAppendix C Listing of NON-LINEAR Profiles in the MSP400 SPEC.CAppendix D Hart Communications with the MSP400 Table of MSP400 Parameters IP2046/IM IP2046/IM Instruction & maintenance leaflet