4.7 Engineering Set-up menu : See also Appendix A4

“Eng”

The proficient user is able to fine tune operation of the MSP400 if site or application conditions are unusual.

Users are recommended to leave all operational fine tuning parameters at the factory default settings unless they have a good understanding of the function and capability of the parameters.

The “reload factory defaults” function may be found within this menu, and should be used if the transmitter has been configured incorrectly or if the user wishes to reset all parameter values back to factory default values.

To display the Engineering set-up menu “Eng”, navigate from the normal PV display using the blue button and the red button . Note the requirement to hold the button or hold two buttons together as shown on the main menu in Appendix A.

To enter the “Eng” menu, press the green button to display the first menu item “t.HoLd”

4.7.1 Setting the Threshold

Screen display

“t.HoLd”

 

Factory default value

Auto

The threshold value is actually a limit below which false echoes are rejected.

Auto shows that the MSP400 will automatically set the threshold level for optimum performance based on echo sizes being received.

A new value may be entered up to a maximum value of 99. A large value will have the effect of eliminating false echo processing.

Note that the value shown is in the same units as echo size; if the wrong echo is being processed then raising the threshold level above that of the false echo size (see 4.5.3) will allow the MSP400 to ignore any echoes below this size, including the false echo itself.

To edit the threshold value:

a)Press the blue button to enter the threshold menu and to display the current value in use. If this is correct, press the red button return to the main menu.

If the threshold is to be edited, press the blue button again to allow editing

The leading digit of the 3 digit threshold value will now be flashing, indicating it may be changed.

b)Use the green button D to edit the value of the leading digit.

c)Once correct, use the blue button to select the next digit and then the green button to edit as before, or the blue button to move to the next digit. Continue this sequence until all 3 digits are correct.

d)Press the blue button a final time to confirm the new value. None of the digits should now be flashing.

If the new threshold is incorrect, the edit sequence can be re-started by pressing the blue button again.

If the threshold is correct, press the red button to save the new value to memory and automatically scroll on to the next main menu option: “LE”

29

IP2046/IM

Nov 2006

 

Image 29
Contents Mobrey Contents Introduction Pvdf Wetside Installation IP2046/IM IP2046/IM IP2046/IM Do not USE Housing to Tighten Ptfe RL1 Spst IP2046/IM Alarm IP2046/IM IP2046/IM Selecting the units of measurement Screen display 20/4 Ullage Liquid level SPEC. P CYL.F Scale LEUEL@ max Maximum flow entry Screen display IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM Loop IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM Appendix A1 Main Menu Programming DutyAppendix A1 SEt20Leuel Appendix A2 Diagnostics MenuAppendix A3 Commissioning / Loop Test Menu LoopAppendix A4 Engineering MenuProF Appendix B Default Value Listing Main Menu ParametersDEAd Default Value Listing Engineering ParametersSPEC.C Appendix C Listing of NON-LINEAR Profiles in the MSP400Appendix D Hart Communications with the MSP400 Table of MSP400 Parameters IP2046/IM IP2046/IM Instruction & maintenance leaflet