Page 18

4.4.4 Selecting the correct Profile algorithm.

Screen display:

ProF

 

Factory default value:

Linear

This selection is offered only if the user has chosen a duty of Flow or Contents, or is shown when manually navigating the main menu - ignore if duty chosen is Level or Distance.

The MSP400 is pre-programmed with a selection of popular profiles which are mathematical formulae to convert a linear level reading to a flow or volumetric PV.

Once converted, the 4-20mA and the display of the unit will operate according to the flow or volumetric PV.

The options available are described in the following sections:

4.4.4.1 Flow measurement

3/2

Flume 3/2 flow law

5/2

V-Notch 5/2 flow law

mann

Manning formula

PAr 1

1 ft Parshall flume

PAr 2

2 ft Parshall flume

PAr 3

3 ft Parshall flume

PAr 4

4 ft Parshall flume

PAr 5

5 ft Parshall flume

PAr 6

6 ft Parshall flume

PAr 7

7 ft Parshall flume

PAr 8

8 ft Parshall flume

FF01

Flume Flat 1

:

 

:

 

:

 

FP07

Flume Parabolic 7

The last 30 options for flow FF01 - FP07 comprise a selection of pre-defined standard flow structures which may be of use if none of the other profiles suit. Refer to Appendix D for details.

Note, when scrolling around the profile option loop, all flow and contents profiles are shown.

There are two other profiles which are available but which are not visible when programming the MSP400 using the push buttons.

SPEC. P

Special plotted : only used if the MSP400 has been configured by a HART master such as

 

the Mobrey MCU900 series controller or Mobrey H-Conf401 software

SPEC.C

Special calculated : used when a standard profile is not available from the MSP400 library.

 

Allows the user to enter a Power law and a K factor, for example for a small Parshall flume or

 

to modify the K factor or power to allow for imperfections in standard flow structures.

To change the flow profile:

a)Press the green button to display the “ProF” menu entry screen.

b)Press the blue button to display the current selection. If this selection is correct, press the red button to return to the main menu.

c)To change the profile to one of the other options, press the blue button to enter the “ProF” menu. The current selection will now be flashing, indicating it may be changed.

d)Press the green button to scroll through the list of available profile options, as given in the table above.

18

IP2046/IM

Nov 2006

 

Image 18
Contents Mobrey Contents Introduction Pvdf Wetside Installation IP2046/IM IP2046/IM IP2046/IM Do not USE Housing to Tighten Ptfe RL1 Spst IP2046/IM Alarm IP2046/IM IP2046/IM Selecting the units of measurement Screen display 20/4 Ullage Liquid level SPEC. P CYL.F Scale LEUEL@ max Maximum flow entry Screen display IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM Loop IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM Duty Appendix A1 Main Menu ProgrammingSEt20 Appendix A1Appendix A2 Diagnostics Menu LeuelLoop Appendix A3 Commissioning / Loop Test MenuEngineering Menu Appendix A4Appendix B Default Value Listing Main Menu Parameters ProFDefault Value Listing Engineering Parameters DEAdAppendix C Listing of NON-LINEAR Profiles in the MSP400 SPEC.CAppendix D Hart Communications with the MSP400 Table of MSP400 Parameters IP2046/IM IP2046/IM Instruction & maintenance leaflet