Carrier manual Typical 52S Unit Operating Controls

Page 24

52S

SERIES

OPERATING CONTROLS

The controls and components used in the 52S cooling only or heat/cool units are as follows: the selector switch, the indoor thermostat, the dual capacitor, the temperature limiter, the vent lever, and the fan cycle switch (Figure 45).

The selector switch is used to determine the mode of op- eration: heat, cool, fan, or off. The indoor thermostat controls the room ambient temperature and cycles the heater or the compressor based on the selector switch setting. The dual capacitor aids in the start-up of the compressor and the fan motor. The temperature limiter is mounted on the thermostat under the escutcheon.

It is a mechanical device that restricts the amount of ro- tation of the thermostat. The temperature limiter de- vice may be adjusted by moving the plastic temperature selector tabs to another temperature location on the device. The vent lever is located in the upper right cor- ner of the control box. It is a slide mechanism that opens and closes the vent door. The control may be ac- cessed by removing the front panel of the unit. The fan cycle switch is used to provide 2 options of fan control. The ®rst option, CON, causes the fan to run continuously. The second option, CYC, causes the fan to cycle on when venting, heating, or cooling is requested and off when the thermostat is satis®ed.

The 52S heat pump unit contains all the components of the heat/cool and cooling only unit, and the follow- ing additional ones: the outdoor frost thermostat and the reversing valve. The outdoor frost thermostat prevents operation of the unit in the heat pump mode when the outdoor coil temperature drops below 15 F, or at about

30 to 35 F outdoor ambient temperature (about 40 to

45 F outdoor ambient temperature for 1999 models). The unit automatically engages the electric heat strip un- der these conditions.

The outdoor frost thermostat has a manual override to place the unit in electric heat mode operation only.

The override switch is located behind the front panel on the right side of the unit control box. Placing the over- ride switch into electric heat mode operation will dis- able the compressor for ALL heating or cooling operations.

The reversing valve allows for operation in reverse cycle heat pump mode. The valve is located in the piping sys- tem and is controlled by the reversing valve solenoid coil. The coil is energized only during the heating mode.

For 52S remote control (RC) units, all controls are located on the wall mounted thermostat except the vent lever and outdoor thermostat. Remote control is a factory-installed option only. There are 2 styles of ther- mostats quali®ed for use with 52S series Remote Con- trol units. See Figures 46 and 47. For all other 52S units, room controls are located on the unit or unit control panel. Remote control units do not have a fan cycle switch.

See Figure 48 for sample control panels and Figure 49 for controls locations.

FIGURE 45 Ð TYPICAL 52S UNIT

OPERATING CONTROLS

FIGURE 46 Ð MANUAL THERMOSTAT

RCD P/N TSTATCCPAC01-A or TSTATCCPHP01-A

FIGURE 47 Ð PROGRAMMABLE THERMOSTAT

24

Image 24
Contents Service Technician Guide ContentsIntroduction Summary of DANGERS, WARNINGS, and CautionsModel Number Nomenclature General Disassembly To Disconnect Power for CORD- Connected UnitTo Open the Control BOX To Remove the Unit from the Wall SleeveDuct Extension Screws To Access INDOOR-AIR Section Components Removing the AIR BaffleTo Remove the AIR Discharge Grille To Remove the TOP Cover Ð Remove the screwTo Access OUTDOOR-AIR Section Components To Remove the Discharge DeckTo Remove the Gusset Removing Stator General Cleaning Cleaning and SafetyComponent Cleaning Schedule Consider the following safety issues before beginningMonthly Cleaning Cleaning the Indoor AIR Filter Ð RemoveReplacing the Indoor AIR Filter Ð Access Tools NeededCleaning the Vent AIR Filter Replacing the Vent AIR FilterChassis Seasonal Cleaning Accessing the Indoor and OutdoorDisconnect ALL Power to Unit Cleaning the Indoor and Outdoor Coils Accessing the Indoor FAN and IndoorCoils section Section Components onCleaning the Indoor FAN and FAN Disconnect ALL Power to the UnitCleaning the Heater Assembly Ð Once Compressor Rotary Compressor ComponentsCompressor Troubleshooting Basic Hermetic Compressor Electrical MeasurementsBasic Compressor Troubleshooting Guide Compressor Replacement SHORTED/OPEN Windings TestDisconnect all power to unit Removing the Compressor Ð Follow the stepsInstalled Filter Drier Refrigerant Charging Ð Every mechanicalHeaters Common Causes Heater FailureHeater Removal Removing Heater Screws Operating Controls Typical 52S Unit Operating ControlsDescription of Switch Settings NON-USER Adjustable SwitchesHigh Heat or High Cool Ð Push button Outside or Vent AIR Ð Push the FAN onlySequence of Operation HEAT/COOL Units FigureCooling only Units Figure Heat Pump Units FigureComponent Operation and Troubleshooting Tools NeededIndoor Thermostat Heat Pump Units Indoor Thermostat IT CONTACTS, ALL 52SQ AA and CP Models Outdoor Frost Thermostat Heat Pump UnitsLocked OUT Capacitor TestElectrical Components Removal and Replacement Outdoor Frost Thermostat ScrewsComponent Locations Open Control BOX FAN Motor Troubleshooting FAN MotorBasic FAN Motor Electrical Tests FAN Motor Troubleshooting Chart Typical 208/230 Volt Motors Typical 265 Volt MotorsFAN Motor Replacement RemovalField Temperature Charts 52S Series Page 52S Series Page 52S Series Page 52S Series Page 52S Series Page 52S Series Page 52S Series Page 52S Series Wiring Schematics Wiring Schematic 52SC Ð 208/230 V and 265 V AA and CP UnitsWiring Schematic 52SE Ð 208/230 V and 265 V AA and CP Units Wiring Schematic 52SE Ð 208/230 V and 265 V RC Units Wiring Schematic 52SQ Ð 208/230 V and 265 V AA and CP Units Wiring Schematic 52SQ Ð 208/230 V and 265 V RC Units Most Frequent Ptac Service Questions