Fig. 10 Ð Condensate Drain Connections (Typical Roof Curb or Slab Mount Shown)

Step 6 Ð Controls Options Ð The control options that the units can provide are based on the following param- eters: CV (constant volume) or VAV (variable air volume) operation; stand-alone unit with ®eld-supplied sensors in- stalled (CV or VAV); as a system via the Carrier Comfort System (TEMP or VVT); optional electronic expansion board installed (CV or VAV); linked to the Carrier Comfort Net- work; and availability of a computer and software (Comfort Works, Building Supervisor, and Service Tool) to access the base control board. See Table 3.

NOTE: Access to the base control board allows unit occu- pancy schedules, unit timeclock, and various set points to be changed from their factory-de®ned default settings.

CONSTANT VOLUME APPLICATIONS Ð The standard CV unit is capable of being operated with either a Carrier- approved thermostat or a ®eld-supplied sensor. (See Price Pages for ordering information.)

Features with Thermostat Control of Unit

·two-stage heating (if installed)

·two-stage cooling

·control of unit using Y1, Y2, W1, W2, and G thermostat inputs

·control of the indoor fan

·outdoor air temperature/supply air temperature monitoring

·control of an outdoor air condenser fan based on outdoor air temperature

·control of modulating economizer damper to provide free cooling when outdoor conditions are suitable, using sup- ply air temperature as a control point

·control of the economizer damper and indoor fan to obtain unoccupied free cooling

·provide power exhaust output to an external power ex- haust controller

·support a ®eld test for ®eld checkout

·control of 2 stages of CV power exhaust

· compressor Time Guard (power up and minimum off and on times)

Additional features are provided by accessing the stand- ard unit control board via software with a computer. These features are:

·electronic expansion board features (if installed)

·compressor lockout during low supply air temperature

·control board diagnostics

·ability to change supply air set point (economizer control)

·ability to change high outdoor air temperature lockout set point (economizer control)

·ability to change power exhaust set points

NOTE: A CV unit without a thermostat requires a ®eld- supplied sensor for operation.

Features with Sensor Control of Unit (Stand-Alone Appli- cations Ð Unit control is limited to CV unoccupied default set points, 90 F for cooling, 55 F for heating. There are

3 sensor options available:

·T-57 sensor will monitor room temperature

·T-55 sensor will monitor room temperature and provide unoccupied override capability (1 hour)

·T-56 sensor will monitor room temperature, provide un- occupied override capability (1 hour), and provide a tem- perature offset of 5° F.

Standard features are:

·support of remote occupied/unoccupied input to start and stop the unit

·cooling capacity control of 3 stages using economizer and 2 compressors to maintain space temperature to an occu- pied or unoccupied set point

·enable heating (if installed) or cooling during unoccupied periods as required to maintain space temperature within the unoccupied set points

·adjustment of space temperature set points of ± 5° F when using a T-56 sensor

Table 3 Ð Controls Options and Con®gurations (Non-Thermostat Applications)

UNIT CONFIGURATION

DEFAULT COOLING

DEFAULT HEATING

UNITS RUNNING VERSION 1.0 UNIT CONTROL SOFTWARE

 

 

 

CV or VAV Unit with SPT Sensor

Unoccupied Cooling Ð 90 F (SPT)

Unoccupied Heating Ð 55 F (SPT)

Occupied Cooling

Ð NA

Occupied Heating

Ð NA

 

CV Unit with SPT Sensor and Remote

Unoccupied Cooling Ð 90 F (SPT)

Unoccupied Heating Ð 55 F (SPT)

Start/Stop Switch

Occupied Cooling

Ð 78 F (SPT)

Occupied Heating

Ð 68 F (SPT)

VAV Unit Remote Start/Switch Only

Unoccupied Cooling Ð NA

Unoccupied Heating Ð NA

Occupied Cooling

Ð 55 F (SAT)

Occupied Heating

Ð NA

 

VAV Unit with SPT Sensor and Remote

Unoccupied Cooling Ð 90 F (SPT)

Unoccupied Heating Ð 55 F (SPT)

Start/Stop Switch

Occupied Cooling

Ð 55 F (SAT)

Occupied Heating

Ð NA

UNITS RUNNING VERSION 2.0 UNIT CONTROL SOFTWARE

 

 

 

CV or VAV Unit with SPT Sensor

Unoccupied Cooling Ð 90 F (SPT)

Unoccupied Heating Ð 55 F (SPT)

Occupied Cooling

Ð NA

Occupied Heating

Ð NA

 

CV Unit with SPT Sensor and Remote

Unoccupied Cooling Ð 90 F (SPT)

Unoccupied Heating Ð 55 F (SPT)

Start/Stop Switch

Occupied Cooling

Ð 78 F (SPT)

Occupied Heating

Ð 68 F (SPT)

VAV Unit Remote Start/Stop Switch Only

Unoccupied Cooling Ð 90 F (RAT)

Unoccupied Heating Ð 55 F (RAT)

Occupied Cooling

Ð 55 F (SAT)

Occupied Heating

Ð 68 F (RAT)*

 

VAV Unit with SPT Sensor and Remote

Unoccupied Cooling Ð 90 F (SPT)

Unoccupied Heating Ð 55 F (SPT)

Start/Stop Switch

Occupied Cooling

Ð 55 F (SAT)

Occupied Heating

Ð 68 F (RAT)*

 

 

LEGEND

 

 

 

*With DIP Switch No. 5 con®gured to OPEN (Occupied Heat Enabled).

CV

Ð

Constant Volume

SAT

Ð

Supply-Air Temperature

NOTE: Space temperature sensor and remote stop/switch are ®eld-supplied.

NA

Ð

Not Available

SPT

Ð

Space Temperature

 

RAT

Ð

Return-Air Temperature

VAV

Ð

Variable Air Volume

 

12

Image 12
Contents Installation, Start-Up Service Instructions Unit Leveling Tolerances Dimensions Roof Curb SizesRoof Curb Sizes Base Unit Dimensions, 50EJ/EK024-034 Unit Size Operating Corner Weight 50EJ/EKBase Unit Dimensions, 50EJ038-048 and 50EK044 Unit Size Operating Corner WeightBase Unit Dimensions, 50EW/EY024-034 Unit Size Operating Corner Weight 50EW/EYBase Unit Dimensions, 50EW038-048 and 50EY044 WeightModel Weight 50EJ/EK/EW/EY Rigging LabelPhysical Data Unit 50EJ,EK,EW,EY4282 4508 4795 Make Unit Duct Connections Evaporator Fan Motor DataSAT Field Control Remote Start/Stop CCN COMSIO Field Power Wiring Connections Make Electrical ConnectionsPage Electrical Data Ð 50EJ,EK,EW,EY024-048 FLA LRA MCA MOCP²24.2 187 254 57.1 266 39.1 228 46.2 225/200 82.4 100 12.6 23.6 95.0 110 43.3 86.6 104.1 187 254 69.2 345 59.4 187 254 82.1 446 69.2 345 74.8 Control Box Diagram Sizes Make Outdoor-Air Inlet Adjustments CCN Connection Approved Shielded CablesColor Code Recommendations Adding Seal Strip to Top of Hood Sides Adding Seal Strip to Hood Top Mounting Flange Attaching Seal Strip To Filter Cover Barometric Relief Damper and Power Exhaust Mounting Details Pressure Transducer Locations Ð Motormaster III Sensor Location VFD Set Point Pressure Voltage VFDSET Point Direct Digital Controls DIP Switch Congura Potentiometer Signal LevelsPower Exhaust Default Set Points Setting Open SettingClosed POSSequence of Operation Fan Performance, 50EJ/EK024-034 Ð Vertical Discharge Units Airflow16,000 Fan Performance, 50EJ048 Ð Vertical Discharge Units Air Quantity LimitsCFM CV Motor Limitations User Dened Set PointsPage Heat Interlock Relay Wiring Cooling Capacity Staging Table CV Units with 2 Compressors Stages EconomizerStages Evaporator Fan Service and Replacement LubricationManufacturer Lubricant Belt Tension Adjustment Ð To adjust belt tension Condenser-Fan AdjustmentEvaporator-Fan Motor Replacement Cooling Charging Chart Sizes Troubleshooting Typical Refrigerant Circuiting 50EJ,EK,EW,EY038,044 Typical Refrigerant Circuiting 50EJ,EW048 Control Board LED Alarms LED Error Description Troubleshooting Blinks Code CommentsDIP I/O Channel Designations Base Module Ð CVBase Module Ð VAV I/O Channel Designations Expansion Module Ð CV and VAV IAQPage Page Packaged Service Training START-UP Checklist START-UP Checklist General