Carrier Manual for HH57AC078: Outdoor Air Damper Position and Economizer Settings

Page 28

Minimum Damper Position Setting Ð Setting of the out- door air damper position is performed in conjunction with a shortened version of the ®eld-run test. This is performed by ®rst opening DIP (Dual In-Line Package) switch no. 6 then no. 4. See Fig. 17 and Table 7.

The outdoor-air damper closes. The control allows 90 sec- onds for the damper to close in case it is in the full open position. Next, the indoor-fan contactor will energize. The outdoor-air damper will remain at 0% for 30 seconds. It will then move to the 10% position for another 30 seconds. This will be repeated at every 10% increment for 30 seconds until the damper reaches 100% open. Close DIP switch no. 6 dur- ing the 30 seconds immediately after the desired outdoor air minimum damper position. The 30-second time period is to allow time where DIP switch no. 6 can be closed. The de- fault value of the minimum outdoor air damper position is 20%. If the desired minimum position is 30%, allow the damper

BLACK SEAL STRIP (CENTERED)

FILTER COVER

Fig. 27 Ð Attaching Seal Strip

to Filter Cover

HH57AC077

ENTHALPY CONTROL

C7400A1004

HH57AC078

ENTHALPY SENSOR

+

(USED WITH ENTHALPY

 

CONTROL FOR DIFFERENTIAL

 

ENTHALPY OPERATION)

Fig. 28 Ð Differential Enthalpy Control

and Sensor

position to go to 10% for 30 seconds, then 20% for 30 sec- onds, and when it reaches 30% close DIP switch no. 6 dur- ing the 30-second period following the 30% position.

The minimum outdoor air damper position is now set.

ECONOMIZER SETTINGS

Accessory Enthalpy Control (Fig. 28) Ð The control (HH57AC077) is mounted in the economizer hood. See Fig. 19. The enthalpy setting adjustment is on the enthalpy control. For maximum bene®t of outdoor air, set enthalpy control to A. See Fig. 29 and 30.

Accessory Differential Enthalpy Control Ð The control (HH57AC077), in conjunction with the accessory enthalpy sensor (HH57AC078), controls economizer operation ac- cording to the differential enthalpy. The control is mounted in the economizer hood. The sensor is mounted in the return duct (50EJ/EK) or return air plenum (50EW/EY).

NOTE: Switches shown in high enthalpy state. Terminals 2 and 3 close on en- thalpy decrease.

Fig. 29 Ð Wire Connections for Solid State

Enthalpy Control (HH57AC077)

CONTROL

CONTROL POINT

CURVE

(APPROX. DEG.)

AT 50% RH

 

A73 (23)

B70 (21)

C67 (19)

D63 (17)

RH Ð Relative Humidity

Fig. 30 Ð Psychrometric Chart for

Enthalpy Control

28

Image 28
Contents Installation, Start-Up Service Instructions Unit Leveling Tolerances Dimensions Roof Curb SizesRoof Curb Sizes Base Unit Dimensions, 50EJ/EK024-034 Unit Size Operating Corner Weight 50EJ/EKBase Unit Dimensions, 50EJ038-048 and 50EK044 Unit Size Operating Corner WeightBase Unit Dimensions, 50EW/EY024-034 Unit Size Operating Corner Weight 50EW/EYBase Unit Dimensions, 50EW038-048 and 50EY044 WeightModel Weight 50EJ/EK/EW/EY Rigging LabelPhysical Data Unit 50EJ,EK,EW,EY4282 4508 4795 Make Unit Duct Connections Evaporator Fan Motor DataSAT Field Control Remote Start/Stop COM CCNSIO Field Power Wiring Connections Make Electrical ConnectionsPage Electrical Data Ð 50EJ,EK,EW,EY024-048 FLA LRA MCA MOCP²24.2 187 254 57.1 266 39.1 228 46.2 225/200 82.4 100 12.6 23.6 95.0 110 43.3 86.6 104.1 187 254 69.2 345 59.4 187 254 82.1 446 69.2 345 74.8 Control Box Diagram Sizes CCN Connection Approved Shielded Cables Make Outdoor-Air Inlet AdjustmentsColor Code Recommendations Adding Seal Strip to Top of Hood Sides Adding Seal Strip to Hood Top Mounting Flange Attaching Seal Strip To Filter Cover Barometric Relief Damper and Power Exhaust Mounting Details Pressure Transducer Locations Ð Motormaster III Sensor Location Pressure Voltage VFD VFD Set PointSET Point Potentiometer Signal Levels Direct Digital Controls DIP Switch ConguraPower Exhaust Default Set Points Setting Open SettingClosed POSSequence of Operation Fan Performance, 50EJ/EK024-034 Ð Vertical Discharge Units Airflow16,000 Air Quantity Limits Fan Performance, 50EJ048 Ð Vertical Discharge UnitsCFM CV Motor Limitations User Dened Set PointsPage Heat Interlock Relay Wiring Stages Economizer Cooling Capacity Staging Table CV Units with 2 CompressorsStages Lubrication Evaporator Fan Service and ReplacementManufacturer Lubricant Condenser-Fan Adjustment Belt Tension Adjustment Ð To adjust belt tensionEvaporator-Fan Motor Replacement Cooling Charging Chart Sizes Troubleshooting Typical Refrigerant Circuiting 50EJ,EK,EW,EY038,044 Typical Refrigerant Circuiting 50EJ,EW048 LED Error Description Troubleshooting Blinks Code Comments Control Board LED AlarmsDIP Base Module Ð CV I/O Channel DesignationsBase Module Ð VAV I/O Channel Designations Expansion Module Ð CV and VAV IAQPage Page Packaged Service Training START-UP Checklist START-UP Checklist General