Carrier 50EW, 50EY, 50EK installation instructions Rigging Label, Model Weight 50EJ/EK/EW/EY

Page 8

Step 2 Ð Rig and Place Unit Ð Inspect unit for trans- portation damage. File any claim with transportation agency. Keep unit upright, and do not drop. Use spreader bars over unit to prevent sling or cable damage. Rollers may be used to move unit across a roof. Level by using unit frame as a reference; leveling tolerance is shown in Fig. 1 and 2. See Fig. 7 for additional information. Unit weight is shown in Table 1.

NOTE: On retro®t jobs, ductwork may be attached to old unit instead of roof curb. Be careful not to damage ductwork when removing unit. Attach existing ductwork to roof curb instead of unit.

Four lifting lugs are provided on the unit base rails as shown in Fig. 7. Refer to rigging instructions on unit.

POSITIONING Ð Provide clearance around and above unit for air¯ow, safety, and service access (Fig. 3-6).

Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air.

Although unit is weatherproof, guard against water from higher level runoff and overhangs.

NOTICE TO RIGGERS:

ALL PANELS MUST BE IN PLACE

WHEN RIGGING.

NOTE: Rig with four cables and spread with two 92 in. (2337 mm) spreader bars. Maintain a dis- tance of 74 in. (1880 mm) from top of unit to eyehook.

NOTE:

Add 32 lb (14.5 kg) for domestic crating.

Add 312 lb (142 kg) for export crating (024-034 units). Add 346 lb (157 kg) for export crating (038-048 units). Add 250 lb (113 kg) for power exhaust.

Add 220 lb (100 kg) for copper condenser coil (024-034 units). Add 285 lb (129 kg) for copper condenser coil (038-044 units). Add 380 lb (172 kg) for copper condenser coil (048 unit).

MODEL

WEIGHT

 

A

 

B

 

C

50EJ/EK/EW/EY

lb

kg

in.

 

mm

in.

 

mm

in.

 

mm

024

4016

1822

87.68

 

2227

71.4

 

1814

41.7

 

1059

028

 

 

 

 

 

 

 

 

 

 

 

030

4102

1860

87.68

 

2227

68.5

 

1740

43.6

 

1107

034

 

 

 

 

 

 

 

 

 

 

 

038*

4282

1942

 

 

 

91.3

 

2319

46.5

 

1181

044

4508

2045

150

 

3810

87.8

 

2230

46.5

 

1181

048*

4795

2175

 

 

 

86.2

 

2189

46.1

 

1171

 

 

 

 

 

 

 

 

 

 

 

 

*Sizes 038 and 048 are 50EJ,EW units only.

Fig. 7 Ð Rigging Label

8

Image 8
Contents Installation, Start-Up Service Instructions Unit Leveling Tolerances Dimensions Roof Curb SizesRoof Curb Sizes Base Unit Dimensions, 50EJ/EK024-034 Unit Size Operating Corner Weight 50EJ/EKBase Unit Dimensions, 50EJ038-048 and 50EK044 Unit Size Operating Corner WeightBase Unit Dimensions, 50EW/EY024-034 Unit Size Operating Corner Weight 50EW/EYBase Unit Dimensions, 50EW038-048 and 50EY044 WeightModel Weight 50EJ/EK/EW/EY Rigging LabelPhysical Data Unit 50EJ,EK,EW,EY4282 4508 4795 Make Unit Duct Connections Evaporator Fan Motor DataSAT Field Control Remote Start/Stop SIO CCNCOM Field Power Wiring Connections Make Electrical ConnectionsPage Electrical Data Ð 50EJ,EK,EW,EY024-048 FLA LRA MCA MOCP²24.2 187 254 57.1 266 39.1 228 46.2 225/200 82.4 100 12.6 23.6 95.0 110 43.3 86.6 104.1 187 254 69.2 345 59.4 187 254 82.1 446 69.2 345 74.8 Control Box Diagram Sizes Color Code Recommendations Make Outdoor-Air Inlet AdjustmentsCCN Connection Approved Shielded Cables Adding Seal Strip to Top of Hood Sides Adding Seal Strip to Hood Top Mounting Flange Attaching Seal Strip To Filter Cover Barometric Relief Damper and Power Exhaust Mounting Details Pressure Transducer Locations Ð Motormaster III Sensor Location SET Point VFD Set PointPressure Voltage VFD Power Exhaust Default Set Points Direct Digital Controls DIP Switch ConguraPotentiometer Signal Levels Setting Open SettingClosed POSSequence of Operation Fan Performance, 50EJ/EK024-034 Ð Vertical Discharge Units Airflow16,000 CFM CV Fan Performance, 50EJ048 Ð Vertical Discharge UnitsAir Quantity Limits Motor Limitations User Dened Set PointsPage Heat Interlock Relay Wiring Stages Cooling Capacity Staging Table CV Units with 2 CompressorsStages Economizer Manufacturer Lubricant Evaporator Fan Service and ReplacementLubrication Evaporator-Fan Motor Replacement Belt Tension Adjustment Ð To adjust belt tensionCondenser-Fan Adjustment Cooling Charging Chart Sizes Troubleshooting Typical Refrigerant Circuiting 50EJ,EK,EW,EY038,044 Typical Refrigerant Circuiting 50EJ,EW048 DIP Control Board LED AlarmsLED Error Description Troubleshooting Blinks Code Comments Base Module Ð VAV I/O Channel DesignationsBase Module Ð CV I/O Channel Designations Expansion Module Ð CV and VAV IAQPage Page Packaged Service Training START-UP Checklist START-UP Checklist General