Carrier 50EW, 50EJ, 50EY, 50EK Barometric Relief Damper and Power Exhaust Mounting Details

Page 29

Step 9 Ð Position Power Exhaust/Barometric Relief Damper Hood Ð All electrical connections have been made and adjusted at the factory. The power exhaust blowers and barometric relief dampers are shipped as- sembled and tilted back into the unit for shipping. Brackets and extra screws are shipped in shrink wrap around the damp- ers. If ordered, each unit will have 4 power exhaust blowers and motors or 4 barometric relief dampers.

1.Remove 9 screws holding each damper assembly in place. See Fig. 31. Each damper assembly is secured with 3 screws on each side and 3 screws along the bottom. Save screws.

2.Pivot each damper assembly outward until edges of damper assembly rest against inside wall of unit.

Be careful when tilting blower assembly. Hoods and blowers are heavy and can cause injury if dropped.

3.Secure each damper assembly to unit with 6 screws across top (3 screws provided) and bottom (3 screws from Step 1) of damper.

4.With screws saved from Step 1, install brackets on each side of damper assembly.

5.Remove tape from damper blades.

VAV DUCT PRESSURE TRANSDUCER Ð The VAV duct pressure transducer (VAV inverter pressure transducer) is lo- cated behind the ®lter access door on the lower inner panel. See Fig. 32. A section of 1¤4-in. plastic tubing must be run from the high-pressure tap on the differential pressure switch and connected to a tap in the supply-air duct. The tap is usu- ally located 2¤3 of the way out on the main supply duct. Re- move plug button in panel to route tubing.

VAV BUILDING PRESSURE TRANSDUCER Ð The VAV building pressure transducer (modulating power exhaust pres- sure transducer) is located behind the ®lter access door on the inner panel. See Fig. 32. A section of 1¤4-in. plastic tub- ing must be run from the high-pressure tap on the differen- tial pressure switch to the conditioned space. The pressure tube must be terminated in the conditioned space where a constant pressure is required. This location is usually in an entrance lobby so that the building exterior doors will open and close properly. Remove plug button in panel to route tubing.

NOTES:

1.Unless otherwise speci®ed, all dimensions are to outside of part.

2.Dimensions are in inches.

Fig. 31 Ð Barometric Relief Damper and Power

Exhaust Mounting Details

29

Image 29
Contents Installation, Start-Up Service Instructions Roof Curb Sizes Unit Leveling Tolerances DimensionsRoof Curb Sizes Unit Size Operating Corner Weight 50EJ/EK Base Unit Dimensions, 50EJ/EK024-034Unit Size Operating Corner Weight Base Unit Dimensions, 50EJ038-048 and 50EK044Unit Size Operating Corner Weight 50EW/EY Base Unit Dimensions, 50EW/EY024-034Weight Base Unit Dimensions, 50EW038-048 and 50EY044Rigging Label Model Weight 50EJ/EK/EW/EYUnit 50EJ,EK,EW,EY Physical Data4282 4508 4795 Evaporator Fan Motor Data Make Unit Duct ConnectionsSAT Field Control Remote Start/Stop SIO CCNCOM Make Electrical Connections Field Power Wiring ConnectionsPage FLA LRA MCA MOCP² Electrical Data Ð 50EJ,EK,EW,EY024-04824.2 187 254 57.1 266 39.1 228 46.2 225/200 82.4 100 12.6 23.6 95.0 110 43.3 86.6 104.1 187 254 69.2 345 59.4 187 254 82.1 446 69.2 345 74.8 Control Box Diagram Sizes Color Code Recommendations Make Outdoor-Air Inlet AdjustmentsCCN Connection Approved Shielded Cables Adding Seal Strip to Top of Hood Sides Adding Seal Strip to Hood Top Mounting Flange Attaching Seal Strip To Filter Cover Barometric Relief Damper and Power Exhaust Mounting Details Pressure Transducer Locations Ð Motormaster III Sensor Location SET Point VFD Set PointPressure Voltage VFD Power Exhaust Default Set Points Direct Digital Controls DIP Switch ConguraPotentiometer Signal Levels Setting Setting OpenClosed POSSequence of Operation Airflow Fan Performance, 50EJ/EK024-034 Ð Vertical Discharge Units16,000 CFM CV Fan Performance, 50EJ048 Ð Vertical Discharge UnitsAir Quantity Limits User Dened Set Points Motor LimitationsPage Heat Interlock Relay Wiring Stages Cooling Capacity Staging Table CV Units with 2 CompressorsStages Economizer Manufacturer Lubricant Evaporator Fan Service and ReplacementLubrication Evaporator-Fan Motor Replacement Belt Tension Adjustment Ð To adjust belt tensionCondenser-Fan Adjustment Cooling Charging Chart Sizes Troubleshooting Typical Refrigerant Circuiting 50EJ,EK,EW,EY038,044 Typical Refrigerant Circuiting 50EJ,EW048 DIP Control Board LED AlarmsLED Error Description Troubleshooting Blinks Code Comments Base Module Ð VAV I/O Channel DesignationsBase Module Ð CV IAQ I/O Channel Designations Expansion Module Ð CV and VAVPage Page Packaged Service Training START-UP Checklist General START-UP Checklist