Carrier Understanding Diagnostic LEDs and Troubleshooting for 50EK and 50EJ Air Conditioners

Page 49

Diagnostic LEDs (Light-Emitting Diodes) Ð There are 3 LEDs (red, yellow, and green) on the lower right hand side of the control board. The red light is used to check unit operation and alarms. A constant pulse is normal unit operation. A series of quick blinks indicates an alarm. Refer

to Table 20 below for a description of alarms. The yellow LED blinks during transmission with the CCN (Carrier Com- fort Network). The green LED blinks during transmission with the expansion board.

Table 20 Ð Control Board LED Alarms

 

LED

 

ERROR

DESCRIPTION

TROUBLESHOOTING

 

BLINKS

 

CODE

COMMENTS

 

 

 

 

1

 

 

Normal Operation

The expansion board and control board ¯ash the red LED in one-

 

 

 

 

 

second intervals when the board is operating properly.

 

2

 

HF-13

Compressor 1 Safety

The high or low pressure safety switch for compressor no. 1 has

 

 

 

 

 

opened for 3 seconds. The error will be cleared and compressor

 

 

 

 

 

no. 1 will be allowed to turn on in 15 minutes. If the safeties have

 

 

 

 

 

been tripped 3 times in 90 minutes, compressor no. 1 will be

 

 

 

 

 

locked out until the control board has been manually reset.

 

3

 

HF-14

Compressor 2 Safety

The high or low pressure safety switch for compressor no. 2 has

 

 

 

 

 

opened for 3 seconds. The error will be cleared and compressor

 

 

 

 

 

no. 2 will be allowed to turn on in 15 minutes. If the safeties have

 

 

 

 

 

been tripped 3 times in 90 minutes, compressor no. 2 will be

 

 

 

 

 

locked out until the control board has been manually reset.

 

4

 

HF-15

Thermostat Failure

The thermostat is calling for both heating and cooling at the

 

 

 

 

 

same time. The unit will operate on a ®rst call basis and will auto-

 

 

 

 

 

matically reset.

 

5

 

HF-05

SAT Thermistor Failure

The supply-air temperature (SAT) sensor has failed. First check for

 

 

 

 

 

wiring errors, then replace sensor.

 

6

 

HF-06

OAT Thermistor Failure

The outside-air temperature (OAT) sensor has failed. First check

 

 

 

 

 

for wiring errors, then replace sensor.

 

7

 

HF-03

Space Temp. Sen. Failure

The space temperature sensor has failed. First check for wiring

 

 

 

 

 

errors, then replace sensor.

 

8

 

HF-12

RAT Thermistor Failure

The return-air temperature (RAT) sensor has failed. Ensure that

 

 

 

 

 

the unit is a VAV unit. If NOT a VAV unit set DIP switch position 1

 

 

 

 

 

to the closed position and reset power. Then check for wiring

 

 

 

 

 

errors. Finally, replace sensor.

 

9

 

SE-05

Loss of Communications

Communications between the expansion board and the control

 

 

 

 

with Expansion board

board have been interrupted. Ensure that an expansion board

 

 

 

 

 

is installed and wired using the wire harness supplied with the

 

 

 

 

 

expansion module. If an expansion board is not used ensure that

 

 

 

 

 

DIP switch position 3 is in the closed position, and reset power.

 

10

 

HF-16

Control Board Failure

Generated when hardware has failed on control board. Replace

 

 

 

 

 

the control board.

 

11

 

HF-17

Expansion Board Failure

Generated when hardware has failed on the expansion board.

 

 

 

 

 

Replace the expansion board.

 

LEGEND

 

 

 

DIP

Ð Dual In-Line Package

 

 

LED Ð Light-Emitting Diode

 

 

VAV

Ð Variable Air Volume

 

 

49

Image 49
Contents Installation, Start-Up Service Instructions Roof Curb Sizes Unit Leveling Tolerances DimensionsRoof Curb Sizes Unit Size Operating Corner Weight 50EJ/EK Base Unit Dimensions, 50EJ/EK024-034Unit Size Operating Corner Weight Base Unit Dimensions, 50EJ038-048 and 50EK044Unit Size Operating Corner Weight 50EW/EY Base Unit Dimensions, 50EW/EY024-034Weight Base Unit Dimensions, 50EW038-048 and 50EY044Rigging Label Model Weight 50EJ/EK/EW/EYUnit 50EJ,EK,EW,EY Physical Data4282 4508 4795 Evaporator Fan Motor Data Make Unit Duct ConnectionsSAT Field Control Remote Start/Stop COM CCNSIO Make Electrical Connections Field Power Wiring ConnectionsPage FLA LRA MCA MOCP² Electrical Data Ð 50EJ,EK,EW,EY024-04824.2 187 254 57.1 266 39.1 228 46.2 225/200 82.4 100 12.6 23.6 95.0 110 43.3 86.6 104.1 187 254 69.2 345 59.4 187 254 82.1 446 69.2 345 74.8 Control Box Diagram Sizes CCN Connection Approved Shielded Cables Make Outdoor-Air Inlet AdjustmentsColor Code Recommendations Adding Seal Strip to Top of Hood Sides Adding Seal Strip to Hood Top Mounting Flange Attaching Seal Strip To Filter Cover Barometric Relief Damper and Power Exhaust Mounting Details Pressure Transducer Locations Ð Motormaster III Sensor Location Pressure Voltage VFD VFD Set PointSET Point Potentiometer Signal Levels Direct Digital Controls DIP Switch ConguraPower Exhaust Default Set Points Setting Setting OpenClosed POSSequence of Operation Airflow Fan Performance, 50EJ/EK024-034 Ð Vertical Discharge Units16,000 Air Quantity Limits Fan Performance, 50EJ048 Ð Vertical Discharge UnitsCFM CV User Dened Set Points Motor LimitationsPage Heat Interlock Relay Wiring Stages Economizer Cooling Capacity Staging Table CV Units with 2 CompressorsStages Lubrication Evaporator Fan Service and ReplacementManufacturer Lubricant Condenser-Fan Adjustment Belt Tension Adjustment Ð To adjust belt tensionEvaporator-Fan Motor Replacement Cooling Charging Chart Sizes Troubleshooting Typical Refrigerant Circuiting 50EJ,EK,EW,EY038,044 Typical Refrigerant Circuiting 50EJ,EW048 LED Error Description Troubleshooting Blinks Code Comments Control Board LED AlarmsDIP Base Module Ð CV I/O Channel DesignationsBase Module Ð VAV IAQ I/O Channel Designations Expansion Module Ð CV and VAVPage Page Packaged Service Training START-UP Checklist General START-UP Checklist