NOTE: On units running Version 1.0 of the unit control software, the remote start/ stop switch is connected to R and Y1.
Fig. 16 Ð Field Control Thermostat Wiring
NOTE: Sensor part numbers are as follows:
T55 Ð HH51BX001
T56 Ð HH51BX004
T57 Ð
Fig. 17 Ð Field Control Temperature
Sensor Wiring
Remote Field Control (Units Running Version 2.0 of Unit Control Software) Ð A switch closure across terminals R and W1 on
Service Tool, Building Supervisor, and Comfort Works Ð Access to the control board can be achieved through the ter- minal marked CCN via a
IMPORTANT: Default bus address is 0. Default ele- ment number is 1. Refer to CCN literature for infor- mation on network addressing or changing CCN com- munication defaults.
Carrier Comfort Network Interface Ð The 50E units can be connected to the CCN. The communication bus wiring is sup- plied and installed in the ®eld. Wiring consists of shielded,
The system elements are connected to the communication bus in a daisy chain arrangement. The positive pin of each system element communication connector must be wired to the positive pins of the system element on either side of it, the negative pins must be wired to the negative pins, and the signal pins must be wired to signal ground pins. Wiring con- nections for CCN should be made at the
Conductors and drain wire must be 20 AWG minimum stranded, tinned copper. Individual conductors must be in- sulated with PVC, PVC/nylon, vinyl, Te¯on, or polyethyl- ene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Te¯on with a minimum operating temperature range of −20 C to 60 C (−4 F to 140 F) is required. Table 5 lists cables that meet the requirements.
Table 5 Ð CCN Connection Approved
Shielded Cables
MANUFACTURER | CABLE PART NO. |
Alpha | 2413 or 5463 |
American | A22503 |
Belden | 8772 |
Columbia | 02525 |
|
|
IMPORTANT: When connecting the CCN communi- cation bus to a system element, use a color coding sys- tem for the entire network to simplify installation and checkout. See Table 6.
Table 6 Ð Color Code Recommendations
SIGNAL | CCN BUS CONDUCTOR | CCN PLUG |
TYPE | INSULATION COLOR | PIN NO. |
Positive (+) | RED | 1 |
Ground | WHITE | 2 |
Negative (−) | BLACK | 3 |
NOTE: If a cable with a different color scheme is selected, a similar color code should be adopted for the entire network.
At each system element, the shields of the communica- tion bus cables must be tied together. If the communication bus is entirely within one building, the resulting continuous shield must be connected to a ground at one point only. If the communication bus cable exits from one building and enters another, the shields must be connected to grounds at the lightning suppressor in each building where the cable enters or exits the building (one point per building only).
To connect the unit to the network:
1.Turn off power to the control box.
2.Cut the CCN wire and strip the ends of the red (+), white (ground), and black (−) conductors. (If a different network color scheme is used, substitute appropriate colors.)
3.Remove the
a.Insert and secure the red (+) wire to terminal 1 of the
b.Insert and secure the white (ground) wire to ter- minal 2 of the
c.Insert and secure the black (−) wire to terminal 3 of the
4.Insert the plug into the existing
Step 8 Ð Make Outdoor-Air Inlet Adjustments
ECONOMIZER
NOTE: If accessory power exhaust or barometric relief pack- ages are being added to the unit, install power exhaust or barometric relief before installing economizer hoods.
Economizer Hood Assembly Ð The economizer hood is shipped in a package secured to the outside of the unit and must be
25