Carrier 50EY, 50EJ, 50EW, 50EK I/O Channel Designations, Base Module Ð CV, Base Module Ð VAV

Page 50

Tables 21-23 show the input and output channel designations.

 

Table 21 Ð I/O Channel Designations

 

 

 

Base Module Ð CV

 

 

 

TERMINAL

 

ASSIGNMENT

NO.

 

 

 

 

 

T1-2

 

 

SPT (CCN) Ð 10K V Thermistor

T3-4

 

 

STO (CCN) Ð 10K V Thermistor

T5-6

 

 

OAT Ð 5K V Thermistor

T7-8

 

 

SAT Ð 5K V Thermistor

T9-10

 

 

Ð

T11-12

 

SAT Reset Ð AI (2-10 vdc)

T13-14

 

 

Ð

T15-16

 

 

Ð

T17-25

 

Y1 or Remote Start/Stop Ð DI (24 vac)

T18-25

 

Y2 Ð DI (24 vac)

 

T19-25

 

W1 Ð DI (24 vac)

T20-25

 

W2 Ð DI (24 vac)

T21-25

 

G Ð DI (24 vac)

 

T22-25

 

Compressor 1 Safety Ð DI (24 vac)

T23-25

 

Compressor 2 Safety Ð DI (24 vac)

T24-25

 

Outside Air Enthalpy Ð DI (24 vac)

T26-27

 

Economizer Pos. Ð AO (4-20 mA)

T28-29

 

Heat 1 Relay Ð DO (24 vac)

T30-29

 

Heat 2 Relay Ð DO (24 vac)

T31-32

 

CV Power Exhaust 1/Modulating Pwr Exht Ð DO

 

(115 vac)

 

 

 

 

 

T33-32

 

CV Power Exhaust 2 Ð DO (115 vac)

T34-35

 

Condenser Fan Ð DO (115 vac)

T36-35

 

OFC2 Ð DO (115 vac)

T37-38

 

 

Ð

T39-38

 

 

Ð

K1

 

 

Indoor Fan Relay Ð DO (HV)

K2

 

 

Compr. 1 Ð DO

(HV)

K3

 

 

Compr. 2 Ð DO

(HV)

 

 

LEGEND

 

 

(Tables 21 and 22)

 

AI

Ð

Analog Input

 

AO

Ð Analog Output

 

CCN Ð Carrier Comfort Network

CV

Ð Constant Volume

 

DI

Ð

Direct Input

 

DO

Ð Direct Output

 

HV

Ð High Voltage

 

KV

Ð Kilo-Ohms

 

OAT

Ð Outdoor-Air Temperature

OFC Ð Outdoor Fan Contactor

RAT

Ð Return-Air Temperature

SAT

Ð Supply-Air Temperature

SPT

Ð Space Temperature

 

STO

Ð Space Temperature Offset

TÐ Terminal

VAV Ð Variable Air Volume

Table 22 Ð I/O Channel Designations

 

Base Module Ð VAV

 

 

 

 

TERMINAL

ASSIGNMENT

NO.

 

 

 

T1-2

SPT (CCN) Ð 10K V Thermistor

T3-4

RAT Ð 5K V Thermistor

 

T5-6

OAT Ð 5K V Thermistor

T7-8

SAT Ð 5K V Thermistor

 

T9-10

 

Ð

 

T11-12

SAT Reset Ð AI (2-10 vdc)

T13-14

 

Ð

 

T15-16

 

Ð

 

T17-25

Remote Start/Stop Ð DI (24 vac)

T18-25

 

Ð

 

T19-25

 

Ð

 

T20-25

 

Ð

 

T21-25

 

Ð

 

T22-25

Compressor 1 Safety Ð DI (24 vac)

T23-25

Compressor 2 Safety Ð DI (24 vac)

T24-25

Outside Air Enthalpy Ð DI (24 vac)

T26-27

Economizer Pos. Ð AO (4-20 mA)

T28-29

Heat 1 Relay Ð DO (115 vac)

T30-29

Heat Interlock Relay Ð DO (115 vac)

T31-32

Modulated Power Exhaust Ð DO (115 vac)

T33-32

 

Ð

 

T34-35

Condenser Fan Ð DO (115 vac)

T36-35

OFC2 Ð DO (115 vac)

 

T37-38

Unloader 1 Ð DO (115

vac)

T39-38

Unloader 2 Ð DO (115

vac)

K1

Indoor Fan Relay Ð DO (HV)

K2

Compr. 1 Ð DO

(HV)

 

K3

Compr. 2 Ð DO

(HV)

 

 

 

 

 

50

Image 50
Contents Installation, Start-Up Service Instructions Unit Leveling Tolerances Dimensions Roof Curb SizesRoof Curb Sizes Base Unit Dimensions, 50EJ/EK024-034 Unit Size Operating Corner Weight 50EJ/EKBase Unit Dimensions, 50EJ038-048 and 50EK044 Unit Size Operating Corner WeightBase Unit Dimensions, 50EW/EY024-034 Unit Size Operating Corner Weight 50EW/EYBase Unit Dimensions, 50EW038-048 and 50EY044 WeightModel Weight 50EJ/EK/EW/EY Rigging LabelPhysical Data Unit 50EJ,EK,EW,EY4282 4508 4795 Make Unit Duct Connections Evaporator Fan Motor DataSAT Field Control Remote Start/Stop SIO CCNCOM Field Power Wiring Connections Make Electrical ConnectionsPage Electrical Data Ð 50EJ,EK,EW,EY024-048 FLA LRA MCA MOCP²24.2 187 254 57.1 266 39.1 228 46.2 225/200 82.4 100 12.6 23.6 95.0 110 43.3 86.6 104.1 187 254 69.2 345 59.4 187 254 82.1 446 69.2 345 74.8 Control Box Diagram Sizes Color Code Recommendations Make Outdoor-Air Inlet AdjustmentsCCN Connection Approved Shielded Cables Adding Seal Strip to Top of Hood Sides Adding Seal Strip to Hood Top Mounting Flange Attaching Seal Strip To Filter Cover Barometric Relief Damper and Power Exhaust Mounting Details Pressure Transducer Locations Ð Motormaster III Sensor Location SET Point VFD Set PointPressure Voltage VFD Power Exhaust Default Set Points Direct Digital Controls DIP Switch ConguraPotentiometer Signal Levels Closed Setting OpenSetting POSSequence of Operation Fan Performance, 50EJ/EK024-034 Ð Vertical Discharge Units Airflow16,000 CFM CV Fan Performance, 50EJ048 Ð Vertical Discharge UnitsAir Quantity Limits Motor Limitations User Dened Set PointsPage Heat Interlock Relay Wiring Stages Cooling Capacity Staging Table CV Units with 2 CompressorsStages Economizer Manufacturer Lubricant Evaporator Fan Service and ReplacementLubrication Evaporator-Fan Motor Replacement Belt Tension Adjustment Ð To adjust belt tensionCondenser-Fan Adjustment Cooling Charging Chart Sizes Troubleshooting Typical Refrigerant Circuiting 50EJ,EK,EW,EY038,044 Typical Refrigerant Circuiting 50EJ,EW048 DIP Control Board LED AlarmsLED Error Description Troubleshooting Blinks Code Comments Base Module Ð VAV I/O Channel DesignationsBase Module Ð CV I/O Channel Designations Expansion Module Ð CV and VAV IAQPage Page Packaged Service Training START-UP Checklist START-UP Checklist General