Carrier 50EW, 50EJ, 50EY, 50EK installation instructions Cooling Charging Chart Sizes

Page 45

Crankcase Heater Ð Each compressor has a crankcase heater to prevent absorption of liquid refrigerant by oil in the crank- case when the compressor is idle. Since power for the crank- case heaters is drawn from the unit incoming power, main unit power must be on for the heaters to be energized.

IMPORTANT: After a prolonged shutdown or serv- ice job, energize the crankcase heaters for 24 hours before starting the compressors.

EVAPORATOR-FAN MOTOR PROTECTION Ð A man- ual reset, calibrated trip, magnetic circuit breaker protects against overcurrent. Do not bypass connections or increase the size of the breaker to correct trouble. Determine the cause and correct it before resetting the breaker. If the evaporator- fan motor is replaced with a different horsepower motor, re- sizing of the circuit breaker is required. Contact Carrier Ap- plication Engineering.

CONDENSER-FAN MOTOR PROTECTION Ð Each condenser-fan motor is internally protected against overtemperature.

HIGH- AND LOW-PRESSURE SWITCHES Ð If either switch trips, or if the compressor overtemperature switch ac- tivates, that refrigerant circuit will be automatically locked out. To reset, manually move the thermostat setting.

FREEZE PROTECTION THERMOSTAT (FPT) Ð An FPT is located on the evaporator coil for each circuit. It detects frost build-up and turns off the compressor, allowing the coil to clear. Once the frost has melted, the compressor can be reenergized.

Fig. 41 Ð Cooling Charging Chart,

Sizes 024-034

Relief Devices Ð All units have relief devices to pro- tect against damage from excessive pressures (i.e., ®re). These devices are installed on the suction line, liquid line, and on the compressor.

Control Circuit, 24-V Ð This control circuit is pro- tected against overcurrent by a 3.2-amp circuit breaker (CB4). Breaker can be reset. If it trips, determine cause of trouble before resetting.

Control Circuit, 115-V Ð This control circuit is pro- tected against overcurrent by a 5.0-amp circuit breaker (CB3). Breaker can be reset. If it trips, determine cause of trouble before resetting.

Compressor Lockout Logic Ð If any of the safe- ties trip, the circuit will automatically reset (providing the safety has reset) and restart the compressor in 15 minutes. If any of the safeties trip 3 times within a 90-minute period, then the circuit will be locked out and will require manual resetting by turning off either the unit disconnect or the con- trol circuit breaker, or opening the thermostat.

Replacement Parts Ð A complete list of replacement parts may be obtained from any Carrier distributor upon request.

Fig. 42 Ð Cooling Charging Chart,

Sizes 038-048

45

Image 45
Contents Installation, Start-Up Service Instructions Roof Curb Sizes Unit Leveling Tolerances DimensionsRoof Curb Sizes Unit Size Operating Corner Weight 50EJ/EK Base Unit Dimensions, 50EJ/EK024-034Unit Size Operating Corner Weight Base Unit Dimensions, 50EJ038-048 and 50EK044Unit Size Operating Corner Weight 50EW/EY Base Unit Dimensions, 50EW/EY024-034Weight Base Unit Dimensions, 50EW038-048 and 50EY044Rigging Label Model Weight 50EJ/EK/EW/EYUnit 50EJ,EK,EW,EY Physical Data4282 4508 4795 Evaporator Fan Motor Data Make Unit Duct ConnectionsSAT Field Control Remote Start/Stop CCN COMSIO Make Electrical Connections Field Power Wiring ConnectionsPage FLA LRA MCA MOCP² Electrical Data Ð 50EJ,EK,EW,EY024-04824.2 187 254 57.1 266 39.1 228 46.2 225/200 82.4 100 12.6 23.6 95.0 110 43.3 86.6 104.1 187 254 69.2 345 59.4 187 254 82.1 446 69.2 345 74.8 Control Box Diagram Sizes Make Outdoor-Air Inlet Adjustments CCN Connection Approved Shielded CablesColor Code Recommendations Adding Seal Strip to Top of Hood Sides Adding Seal Strip to Hood Top Mounting Flange Attaching Seal Strip To Filter Cover Barometric Relief Damper and Power Exhaust Mounting Details Pressure Transducer Locations Ð Motormaster III Sensor Location VFD Set Point Pressure Voltage VFDSET Point Direct Digital Controls DIP Switch Congura Potentiometer Signal LevelsPower Exhaust Default Set Points Setting Setting OpenClosed POSSequence of Operation Airflow Fan Performance, 50EJ/EK024-034 Ð Vertical Discharge Units16,000 Fan Performance, 50EJ048 Ð Vertical Discharge Units Air Quantity LimitsCFM CV User Dened Set Points Motor LimitationsPage Heat Interlock Relay Wiring Cooling Capacity Staging Table CV Units with 2 Compressors Stages EconomizerStages Evaporator Fan Service and Replacement LubricationManufacturer Lubricant Belt Tension Adjustment Ð To adjust belt tension Condenser-Fan AdjustmentEvaporator-Fan Motor Replacement Cooling Charging Chart Sizes Troubleshooting Typical Refrigerant Circuiting 50EJ,EK,EW,EY038,044 Typical Refrigerant Circuiting 50EJ,EW048 Control Board LED Alarms LED Error Description Troubleshooting Blinks Code CommentsDIP I/O Channel Designations Base Module Ð CVBase Module Ð VAV IAQ I/O Channel Designations Expansion Module Ð CV and VAVPage Page Packaged Service Training START-UP Checklist General START-UP Checklist