Carrier 50EW, 50EY, 50EK installation instructions Physical Data, Unit 50EJ,EK,EW,EY

Page 9

Table 1 Ð Physical Data

UNIT 50EJ,EK,EW,EY

 

024

 

 

028

 

 

 

030

 

 

 

034

 

NOMINAL CAPACITY (tons)

 

20

 

 

25

 

 

 

27

 

 

 

30

 

OPERATING WEIGHT (lb)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Al/Al²

 

4016

 

 

4102

 

 

 

4102

 

 

 

4102

 

Al/Cu²

 

4236

 

 

4322

 

 

 

4322

 

 

 

4322

 

Roof Curb (14-in. curb)

 

365

 

 

365

 

 

 

365

 

 

 

365

 

COMPRESSOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type Ckt 1

 

06D328

 

 

06D328

 

 

 

06D537

 

 

06D537

 

Ckt 2

 

06D818

 

 

06D328

 

 

 

06D328

 

 

06D537

 

Number of Refrigerant Circuits

 

2

 

 

2

 

 

 

2

 

 

 

2

 

Oil (oz) (Ckt1, Ckt 2)

 

115, 88

 

 

115 ea.

 

 

 

115 ea.

 

 

115 ea.

 

REFRIGERANT TYPE

 

 

 

 

 

 

R-22

 

 

 

 

 

 

Operating Charge (lb-oz)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Circuit 1**

 

25-0

 

 

25-0

 

 

 

25-0

 

 

 

25-0

 

Circuit 2

 

31-0

 

 

25-0

 

 

 

25-0

 

 

 

25-0

 

CONDENSER COIL

 

 

 

Cross-Hatched 3¤8

Copper Tubes, Aluminum Lanced or Copper Fins

 

 

 

Quantity

 

1

 

 

1

 

 

 

1

 

 

 

1

 

Rows...Fins/in.

 

4...15

 

 

4...15

 

 

 

4...15

 

 

 

4...15

 

Total Face Area (sq ft)

 

33.3

 

 

33.3

 

 

 

33.3

 

 

 

33.3

 

CONDENSER FAN

 

 

 

 

 

Propeller Type

 

 

 

 

 

 

Nominal Cfm

 

13,420

 

 

13,420

 

 

 

13,420

 

 

 

13,420

 

Quantity...Diameter (in.)

 

2...30

 

 

2...30

 

 

 

2...30

 

 

 

2...30

 

Motor Hp (1075 Rpm)

 

1

 

 

1

 

 

 

1

 

 

 

1

 

EVAPORATOR COIL

 

 

Cross-Hatched 3¤8 Copper Tubes, Aluminum or Copper Plate Fins, Intertwined Circuits

 

 

Rows...Fins/in.

 

4...15

 

 

4...15

 

 

 

4...15

 

 

 

4...15

 

Total Face Area (sq ft)

 

31.7

 

 

31.7

 

 

 

31.7

 

 

 

31.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EVAPORATOR FAN

 

 

 

 

 

Centrifugal Type

 

 

 

 

 

 

Quantity...Size (in.)

 

2...20x15

 

 

2...20x15

 

 

 

2...20x15

 

 

2..20x15

 

Type Drive

 

Belt

 

 

Belt

 

 

 

Belt

 

 

Belt

 

Nominal Cfm

 

8,000

 

 

10,000

 

 

 

11,000

 

 

 

12,000

 

Motor Hp

5

10²²

15

7.5

10²²

15

 

10

15²²

 

20

10

15²²

20

Motor Frame Size

S184T

S215T

S254T

S213T

S215T

S254T

 

S215T

S254T

 

S256T

S215T

S254T

S256T

Motor Bearing Type

 

Ball

 

 

Ball

 

 

 

Ball

 

 

 

Ball

 

Maximum Allowable Rpm

 

1200

 

 

1200

 

 

 

1200

 

 

 

1200

 

Motor Pulley Pitch Diameter

4.6

6.6

6.9

4.9

6.1

7.1

 

6.6

6.7

 

7.5

6.4

6.9

7.5

Nominal Motor Shaft Diameter (in.)

11¤8

13¤8

15¤8

13¤8

13¤8

15¤8

 

13¤8

15¤8

 

15¤8

13¤8

15¤8

15¤8

Fan Pulley Pitch Diameter (in.)

11.1

12.5

11.1

11.1

11.1

11.1

 

13.7

11.1

 

11.1

12.5

11.1

11.1

Nominal Fan Shaft Diameter (in.)

 

111¤16

 

 

111¤16

 

 

 

111¤16

 

 

 

111¤16

 

Belt, Quantity...Type

1...BX59

1...BX60

1...5VX590

1...BX56

1...BX56

1...5VX590

1...BX62

1...5VX590

1...5VX600

1...BX60

1...5VX590

1...5VX600

Belt, Length (in.)

62

63

59

59

59

59

 

65

59

 

60

63

59

60

Pulley Center Line Distance (in.)

16.0-18.7

15.6-18.4

15.0-17.9

15.6-18.4

15.6-18.4

15.0-17.9

15.6-18.4

15.0-17.9

15.6-18.4

15.0-17.9

Factory Speed Setting (rpm)

725

924

1088

773

962

1119

 

843

1056

 

1182

896

1088

1182

HIGH-PRESSURE SWITCH (psig)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cutout

 

426

 

 

426

 

 

 

426

 

 

 

426

 

Reset (Auto.)

 

320

 

 

320

 

 

 

320

 

 

 

320

 

LOW-PRESSURE SWITCH (psig)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cutout

 

7

 

 

7

 

 

 

7

 

 

 

7

 

Reset (Auto.)

 

22

 

 

22

 

 

 

22

 

 

 

22

 

RETURN-AIR FILTERS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity...Size (in.)

 

10...20x24x2

 

10...20x24x2

 

 

10...20x24x2

 

 

10...20x24x2

OUTDOOR-AIR FILTERS

 

8...16x25

 

 

8...16x25

 

 

 

8...16x25

 

 

8...16x25

 

Quantity...Size (in.)

 

4...20x25

 

 

4...20x25

 

 

 

4...20x25

 

 

4...20x25

 

POWER EXHAUST

 

 

Direct Drive, 3-Speed, Single-Phase Motor (Factory-Wired For High Speed) and Forward Curved Fan

 

Motor, Quantity...Hp

 

 

 

 

 

 

4...1

 

 

 

 

 

 

Fan, Diameter...Width (in.)

 

 

 

 

 

 

11...10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

Al Ð Aluminum

Cu Ð Copper

*Weight of unit does not include variable frequency drive (VFD), barometric relief, or power exhaust. If a VAV unit (a VFD is installed), add the VFD weight in the table at right.

²Evaporator coil ®n material/condenser coil ®n material.

**Sizes 024-034: Circuit 1 uses the lower portion of condenser coil, Circuit 2 uses the upper portion. Sizes 038-048: Circuit 1 uses the left condenser coil, Circuit 2 the right. All units have intertwined evaporator coils.

²²Motor and drive shown will deliver approximately 2.5 in. wg net external static. For more drive information, see Table 2.

NOTES:

1.See Table 2 for evaporator fan motor data.

2.Sizes 038 and 048 are 50EJ,EW units only.

VFD

 

VFD WEIGHTS (lb)

 

(Hp)

208/230 v

 

460 v

575 v

5

20

 

22

60

7.5

51

 

37

64

10

51

 

61

64

15

61

 

63

109

20

63

 

111

109

25

105

 

112

174

30

172

 

118

180

 

 

 

 

 

9

Image 9
Contents Installation, Start-Up Service Instructions Roof Curb Sizes Unit Leveling Tolerances DimensionsRoof Curb Sizes Unit Size Operating Corner Weight 50EJ/EK Base Unit Dimensions, 50EJ/EK024-034Unit Size Operating Corner Weight Base Unit Dimensions, 50EJ038-048 and 50EK044Unit Size Operating Corner Weight 50EW/EY Base Unit Dimensions, 50EW/EY024-034Weight Base Unit Dimensions, 50EW038-048 and 50EY044Rigging Label Model Weight 50EJ/EK/EW/EYUnit 50EJ,EK,EW,EY Physical Data4282 4508 4795 Evaporator Fan Motor Data Make Unit Duct ConnectionsSAT Field Control Remote Start/Stop CCN COMSIO Make Electrical Connections Field Power Wiring ConnectionsPage FLA LRA MCA MOCP² Electrical Data Ð 50EJ,EK,EW,EY024-04824.2 187 254 57.1 266 39.1 228 46.2 225/200 82.4 100 12.6 23.6 95.0 110 43.3 86.6 104.1 187 254 69.2 345 59.4 187 254 82.1 446 69.2 345 74.8 Control Box Diagram Sizes Make Outdoor-Air Inlet Adjustments CCN Connection Approved Shielded CablesColor Code Recommendations Adding Seal Strip to Top of Hood Sides Adding Seal Strip to Hood Top Mounting Flange Attaching Seal Strip To Filter Cover Barometric Relief Damper and Power Exhaust Mounting Details Pressure Transducer Locations Ð Motormaster III Sensor Location VFD Set Point Pressure Voltage VFDSET Point Direct Digital Controls DIP Switch Congura Potentiometer Signal LevelsPower Exhaust Default Set Points Setting Setting OpenClosed POSSequence of Operation Airflow Fan Performance, 50EJ/EK024-034 Ð Vertical Discharge Units16,000 Fan Performance, 50EJ048 Ð Vertical Discharge Units Air Quantity LimitsCFM CV User Dened Set Points Motor LimitationsPage Heat Interlock Relay Wiring Cooling Capacity Staging Table CV Units with 2 Compressors Stages EconomizerStages Evaporator Fan Service and Replacement LubricationManufacturer Lubricant Belt Tension Adjustment Ð To adjust belt tension Condenser-Fan AdjustmentEvaporator-Fan Motor Replacement Cooling Charging Chart Sizes Troubleshooting Typical Refrigerant Circuiting 50EJ,EK,EW,EY038,044 Typical Refrigerant Circuiting 50EJ,EW048 Control Board LED Alarms LED Error Description Troubleshooting Blinks Code CommentsDIP I/O Channel Designations Base Module Ð CVBase Module Ð VAV IAQ I/O Channel Designations Expansion Module Ð CV and VAVPage Page Packaged Service Training START-UP Checklist General START-UP Checklist