Carrier 48HJD005-007 C - 48HJ High-Static Motor Units Without Electrical Convenience Outlet

Page 11
Table 2C — 48HJ High-Static Motor Units Without Electrical Convenience Outlet

Table 2C — 48HJ High-Static Motor Units Without Electrical Convenience Outlet

 

NOMINAL

VOLTAGE

COMPRESSOR

 

 

COMBUSTION

POWER

MINIMUM UNIT

UNIT

OFM

IFM

DISCONNECT

VOLTAGE

RANGE

(each)

FAN MOTOR

SUPPLY

48HJ

 

 

 

SIZE*

(V-Ph-Hz)

 

 

 

 

 

 

 

 

 

 

 

Min

Max

RLA

LRA

FLA

FLA

RLA

MCA

MOCP†

FLA

 

LRA

 

 

 

 

208/230-3-60

187

254

10.3

77.0

0.7

5.8

0.6

19.4/19.4

25/25

19/19

 

120/120

004

460-3-60

414

508

5.1

39.0

0.4

2.6

0.3

9.4

15

9

 

60

 

575-3-60

518

632

4.2

31.0

0.4

2.6

0.3

7.7

15

8

 

48

 

208/230-3-60

187

254

13.5

99.0

0.7

5.8

0.6

23.4/23.4

30/30

23/23

 

142/142

005

460-3-60

414

508

7.4

49.5

0.4

2.6

0.3

12.3

15

12

 

71

 

575-3-60

518

632

5.8

40.0

0.4

2.6

0.3

9.7

15

9

 

57

 

208/230-3-60

187

254

17.3

123.0

1.5

7.5

0.6

30.6/30.6

35/35

30/30

 

187/187

006

460-3-60

414

508

9.0

62.0

0.8

3.4

0.3

15.5

20

15

 

94

 

575-3-60

518

632

7.1

50.0

0.8

3.4

0.3

12.2

15

12

 

76

 

208/230-3-60

187

254

20.5

156.0

1.4

7.5

0.6

30.6/30.6

35/35

30/30

 

187/187

007

460-3-60

414

508

9.6

70.0

0.6

3.4

0.3

15.5

20

15

 

94

 

575-3-60

518

632

7.7

56.0

0.6

3.4

0.3

12.2

15

12

 

76

Table 2D — 48HJ High-Static Motor Units With Electrical Convenience Outlet

 

NOMINAL

VOLTAGE

COMPRESSOR

 

 

COMBUSTION

POWER

MINIMUM UNIT

UNIT

OFM

IFM

DISCONNECT

VOLTAGE

RANGE

(each)

FAN MOTOR

SUPPLY

48HJ

 

 

 

SIZE*

(V-Ph-Hz)

 

 

 

 

 

 

 

 

 

 

 

Min

Max

RLA

LRA

FLA

FLA

RLA

MCA

MOCP†

FLA

LRA

 

 

 

208/230-3-60

187

254

10.3

77.0

0.7

5.8

0.6

25.4/25.4

30/30

25

124/124

004

460-3-60

414

508

5.1

39.0

0.4

2.6

0.3

12.1

15

12

63

 

575-3-60

518

632

4.2

31.0

0.4

2.6

0.3

9.8

15

10

50

 

208/230-3-60

187

254

13.5

99.0

0.7

5.8

0.6

29.4/29.4

35/35

29

146/146

005

460-3-60

414

508

7.4

49.5

0.4

2.6

0.3

15.0

20

14

73

 

575-3-60

518

632

5.8

40.0

0.4

2.6

0.3

11.8

15

11

59

 

208/230-3-60

187

254

17.3

123.0

1.5

7.5

0.6

36.6/36.6

40/40

36

192/192

006

460-3-60

414

508

9.0

62.0

0.8

3.4

0.3

18.2

20

18

96

 

575-3-60

518

632

7.1

50.0

0.8

3.4

0.3

14.4

20

14

77

 

208/230-3-60

187

254

20.5

156.0

1.4

7.5

0.6

40.5/40.5

45/45

39

224/224

007

460-3-60

414

508

9.6

70.0

0.6

3.4

0.3

18.7

25

18

104

 

575-3-60

518

632

7.7

56.0

0.6

3.4

0.3

15.0

20

15

89

LEGEND

FLA — Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration

IFM — Indoor (Evaporator) Fan Motor

LRA — Locked Rotor Amps

MCA — Minimum Circuit Amps

MOCP— Maximum Overcurrent Protection

NEC — National Electrical Code

OFM — Outdoor (Condenser) Fan Motor

RLA — Rated Load Amps

UL — Underwriters’ Laboratories

*Used to determine minimum disconnect per NEC.

†Fuse or HACR circuit breaker.

NOTES:

1.In compliance with NEC requirements for multimotor and combi- nation load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt- age is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

= 100 x

max voltage deviation from average voltage

average voltage

 

Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

Average Voltage = 452 + 464 + 455 3

1371

=

3

= 457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

7

% Voltage Imbalance= 100 x 457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

11

Image 11
Contents Step 1 - Provide Unit Support CONTENTSSAFETY CONSIDERATIONS INSTALLATION1′-4″ Fig. 1 - Roof Curb DetailsFig. 3 - Condensate Drain Pan Fig. 2 - Unit Leveling TolerancesStep 7 - Make Electrical Connections Table 1 - Physical Data Table 1 - Physical Data cont 3/4″ Fig. 5 - Base Unit Dimensions - 48HJ004-0071/2″ Fig. 6 - Flue Hood Details Step 8 - Adjust Factory-Installed OptionsFig. 7 - Gas Piping Guide With Accessory Thru-the-Curb Service ConnectionsFig. 9 - Low-Voltage Connections With or Without Economizer Fig. 8 - Power Wiring ConnectionsFig. 10 - Field Control Wiring Raceway the percent of voltage imbalance Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine Table 2C - 48HJ High-Static Motor Units Without Electrical Convenience Outlet 208/230-V Unit Shown Fig. 11 - Accessory Field-Installed HumidistatFig. 14 - Outdoor-Air Hood Details Fig. 13 - Typical Access Panel LocationsFig. 15 - Durablade Economizer Installed in Unit Fig. 16 - Horizontal Durablade Economizer InstallationFig. 20 - Outdoor-Air Thermostat Enthalpy Control Installation Wiring HarnessFig. 19A - Durablade Economizer Damper Minimum Position Setting Fig. 19B - Durablade Economizer Minimum Position Damper SettingFig. 22 - Durablade Economizer Barometric Relief Damper CharacteristicsFig. 24 - Typical Access Panel Locations Fig. 25 - Exhaust Air Hood AssemblyFig. 29 - EconoMi$er Installed Fig. 28 - Rear EconoMi$er Flange InstallationFig. 26 - Outdoor-Air Hood Assembly Fig. 27 - Completed Hood AssemblyPOWER EXHAUST SYSTEM HIGH VOLTAGE Fig. 31 - EconoMi$er Sensor WiringFig. 33 - Typical Access Panel Locations Fig. 32 - Wiring Diagram for Power Exhaust SystemPotentiometers Factory Settings Fig. 34 - Supply-Air Sensor PlacementTable 4 - Default Potentiometer Settings Fig. 35 - EconoMi$er Control AdjustmentFig. 37 - Belt-Drive Motor Mounting Step 9 - Adjust Evaporator-Fan Speed - AdFig. 38 - Evaporator-Fan Pulley Adjustment Table 7 - Evaporator-Fan Motor Data - High-Static Motors Table 5A - 48HJ Fan Rpm at Motor Pulley Setting With Standard MotorTable 6 - Evaporator-Fan Motor Data - Standard Motor Bels Table 8 - Motor Nominal HorsepowerTable 9 - Outdoor Sound Power Total Unit Table 12 - 48HJ005 Fan Performance - Vertical Discharge Units With Standard Motor 3-Phase Units Single-Phase UnitsTable 16 - 48HJ007 Fan Performance - Vertical Discharge Units With Standard Motor Table 18 - 48HJ004 Fan Performance - Horizontal Discharge Units With Standard Motor Table 20 - 48HJ005 Fan Performance - Horizontal Discharge Units With Standard Motor 3-Phase Units Package Static Pressure Drop in. wg FIOP - Factory-Installed OptionTable 26 - Economizer Static Pressure Drop in. wg Table 27 - FIOP MoistureMiser DehumidificationSTART-UP PRE-START-UPTable 28 - Altitude Compensation HeatingOperating Sequence When the supply-air temperature falls between 57 F and Fig. 39 - MoistureMiser Option Operation Fig. 42 - Separating Coil Sections SERVICELubrication Fig. 40 - Cleaning Condenser Coil Fig. 41 - Propping Up Top PanelFig. 45 - Cooling Charging Chart Standard 48HJ005 Fig. 43 - Condenser-Fan AdjustmentFig. 44 - Cooling Charging Chart Standard 48HJ004 Fig. 47 - Cooling Charging Chart Standard 48HJ007 Fig. 46 - Cooling Charging Chart Standard 48HJ006Fig. 48 - Cooling Charging Chart, 48HJ004 with Optional MoistureMiser Dehumidification Package Fig. 52 - Burner Section Details Fig. 53 - Burner Tray Details Table 29 - LED Error Code Description48HJF005-007 - 150,000 BTUH INPUT Fig. 54 - Spark Gap AdjustmentLOW HEAT 48HJE004, 48HJD005-007 - 72,000 BTUH INPUT MEDIUM AND HIGH HEAT 48HJE005-007, 48HJF004 - 115,000 BTUH INPUTTable 30 - LED Error Code Service Analysis TROUBLESHOOTINGTable 32 - Durablade Economizer Service Analysis Table 31 - Heating Service AnalysisCritical Table 34 - EconoMi$er TroubleshootingTable 33 - EconoMi$er Flash Code Identification Table 35 - MoistureMiser Dehumidification Subcooler Service Analysis Compressor operates continuously Table 36 - Cooling Service Analysis208/230 3-Phase Unit Shown Fig. 55 - Typical Wiring Schematic and Component ArrangementNOTES FOR FIG LEGEND AND NOTES FOR FIGReplaces 48HJ-17SI Page III. START-UP START-UP CHECKLIST Remove and Store in Job FileI. PRELIMINARY INFORMATION II. PRE-START-UP insert checkmark in box as each item is completed