Carrier
48HJD005-007
specifications
Heating, Operating Sequence, Altitude Compensation
Troubleshooting
Relief Damper Characteristics
Install
Wiring Harness
Spark Gap Adjustment
Single-Phase Units
Service
Page 30
Page 29
Page 31
Image 30
Page 29
Page 31
Contents
INSTALLATION
CONTENTS
SAFETY CONSIDERATIONS
Step 1 - Provide Unit Support
Fig. 1 - Roof Curb Details
1′-4″
Fig. 2 - Unit Leveling Tolerances
Fig. 3 - Condensate Drain Pan
Step 7 - Make Electrical Connections
Table 1 - Physical Data
Table 1 - Physical Data cont
Fig. 5 - Base Unit Dimensions - 48HJ004-007
1/2″
3/4″
Thru-the-Curb Service Connections
Step 8 - Adjust Factory-Installed Options
Fig. 7 - Gas Piping Guide With Accessory
Fig. 6 - Flue Hood Details
Fig. 8 - Power Wiring Connections
Fig. 10 - Field Control Wiring Raceway
Fig. 9 - Low-Voltage Connections With or Without Economizer
Never operate a motor where a phase imbalance in supply volt
age is greater than 2%. Use the following formula to determine
the percent of voltage imbalance
Table 2C - 48HJ High-Static Motor Units Without Electrical Convenience Outlet
Fig. 11 - Accessory Field-Installed Humidistat
208/230-V Unit Shown
Fig. 16 - Horizontal Durablade Economizer Installation
Fig. 13 - Typical Access Panel Locations
Fig. 15 - Durablade Economizer Installed in Unit
Fig. 14 - Outdoor-Air Hood Details
Fig. 19B - Durablade Economizer Minimum Position Damper Setting
Wiring Harness
Fig. 19A - Durablade Economizer Damper Minimum Position Setting
Fig. 20 - Outdoor-Air Thermostat Enthalpy Control Installation
Fig. 25 - Exhaust Air Hood Assembly
Relief Damper Characteristics
Fig. 24 - Typical Access Panel Locations
Fig. 22 - Durablade Economizer Barometric
Fig. 27 - Completed Hood Assembly
Fig. 28 - Rear EconoMi$er Flange Installation
Fig. 26 - Outdoor-Air Hood Assembly
Fig. 29 - EconoMi$er Installed
Fig. 32 - Wiring Diagram for Power Exhaust System
Fig. 31 - EconoMi$er Sensor Wiring
Fig. 33 - Typical Access Panel Locations
POWER EXHAUST SYSTEM HIGH VOLTAGE
Fig. 35 - EconoMi$er Control Adjustment
Fig. 34 - Supply-Air Sensor Placement
Table 4 - Default Potentiometer Settings
Potentiometers Factory Settings
Step 9 - Adjust Evaporator-Fan Speed - Ad
Fig. 38 - Evaporator-Fan Pulley Adjustment
Fig. 37 - Belt-Drive Motor Mounting
Table 5A - 48HJ Fan Rpm at Motor Pulley Setting With Standard Motor
Table 6 - Evaporator-Fan Motor Data - Standard Motor
Table 7 - Evaporator-Fan Motor Data - High-Static Motors
Table 8 - Motor Nominal Horsepower
Table 9 - Outdoor Sound Power Total Unit
Bels
Table 12 - 48HJ005 Fan Performance - Vertical Discharge Units With Standard Motor
Single-Phase Units
3-Phase Units
Table 16 - 48HJ007 Fan Performance - Vertical Discharge Units With Standard Motor
Table 18 - 48HJ004 Fan Performance - Horizontal Discharge Units With Standard Motor
Table 20 - 48HJ005 Fan Performance - Horizontal Discharge Units With Standard Motor
3-Phase Units
Table 27 - FIOP MoistureMiser Dehumidification
FIOP - Factory-Installed Option
Table 26 - Economizer Static Pressure Drop in. wg
Package Static Pressure Drop in. wg
PRE-START-UP
START-UP
Heating
Operating Sequence
Table 28 - Altitude Compensation
When the supply-air temperature falls between 57 F and
Fig. 39 - MoistureMiser Option Operation
Fig. 40 - Cleaning Condenser Coil Fig. 41 - Propping Up Top Panel
SERVICE
Lubrication
Fig. 42 - Separating Coil Sections
Fig. 43 - Condenser-Fan Adjustment
Fig. 44 - Cooling Charging Chart Standard 48HJ004
Fig. 45 - Cooling Charging Chart Standard 48HJ005
Fig. 46 - Cooling Charging Chart Standard 48HJ006
Fig. 47 - Cooling Charging Chart Standard 48HJ007
Fig. 48 - Cooling Charging Chart, 48HJ004 with Optional MoistureMiser Dehumidification Package
Table 29 - LED Error Code Description
Fig. 52 - Burner Section Details Fig. 53 - Burner Tray Details
MEDIUM AND HIGH HEAT 48HJE005-007, 48HJF004 - 115,000 BTUH INPUT
Fig. 54 - Spark Gap Adjustment
LOW HEAT 48HJE004, 48HJD005-007 - 72,000 BTUH INPUT
48HJF005-007 - 150,000 BTUH INPUT
TROUBLESHOOTING
Table 30 - LED Error Code Service Analysis
Table 31 - Heating Service Analysis
Table 32 - Durablade Economizer Service Analysis
Table 34 - EconoMi$er Troubleshooting
Table 33 - EconoMi$er Flash Code Identification
Critical
Table 35 - MoistureMiser Dehumidification Subcooler Service Analysis
Table 36 - Cooling Service Analysis
Compressor operates continuously
Fig. 55 - Typical Wiring Schematic and Component Arrangement
208/230 3-Phase Unit Shown
LEGEND AND NOTES FOR FIG
NOTES FOR FIG
Replaces 48HJ-17SI
Page
II. PRE-START-UP insert checkmark in box as each item is completed
START-UP CHECKLIST Remove and Store in Job File
I. PRELIMINARY INFORMATION
III. START-UP
Related pages
Troubleshooting Ethernet Circuit Paths With Loopbacks for Cisco Systems ONS 15310-CL
Consumable Specifications F-1 for Epson TM-P60
Error Message for UTStarcom PN-820
Pen Model Chart Speed for Omega RD260A
How to use the menus for Mitsubishi Electronics SE1U
Parts List for Elkay LK393ABH6
Failure Code List Fault Code for Toshiba G9000
Other accessories may not be compatible with your device for Samsung GT2S5300ZKAXSK
What is the function of the CN600 connector on the Samsung 943NW?
(#)
Top
Page
Image
Contents