Carrier 48HJD005-007 Economizer Static Pressure Drop in. wg, FIOP MoistureMiser Dehumidification

Page 28
Table 26 — Economizer Static Pressure Drop

Table 24 — 48HJ007 Fan Performance — Horizontal Discharge Units With Standard Motor

AIRFLOW

 

 

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

0.1

 

0.2

 

0.4

 

0.6

 

0.8

 

1.0

 

1.2

 

 

1.4

1.6

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

1800

885

 

0.63

942

 

0.73

1047

 

0.90

1139

 

1.05

1193

 

1.14

1276

 

1.30

1341

 

1.40

1413

 

1.55

1474

 

1.58

1900

928

 

0.73

982

 

0.83

1084

 

1.02

1160

 

1.11

1223

 

1.24

1301

 

1.38

1374

 

1.53

1437

 

1.62

1490

 

1.67

2000

971

 

0.84

1022

 

0.94

1121

 

1.12

1188

 

1.22

1254

 

1.36

1329

 

1.44

1396

 

1.66

1460

 

1.68

1509

 

1.77

2100

1015

 

0.97

1063

 

1.10

1140

 

1.18

1196

 

1.27

1272

 

1.45

1354

 

1.58

1413

 

1.75

1475

 

1.73

1529

 

1.92

2200

1060

 

1.10

1104

 

1.20

1159

 

1.23

1229

 

1.41

1306

 

1.53

1363

 

1.70

1434

 

1.81

1487

 

1.85

1554

 

2.07

2300

1104

 

1.25

1130

 

1.27

1196

 

1.37

1264

 

1.56

1340

 

1.66

1397

 

1.86

1459

 

1.88

1520

 

2.07

1576

 

2.24

2400

1138

 

1.30

1174

 

1.37

1245

 

1.57

1305

 

1.63

1373

 

1.84

1440

 

1.95

1502

 

2.06

1552

 

2.24

1604

 

2.42

2500

1183

 

1.43

1201

 

1.50

1284

 

1.65

1338

 

1.75

1402

 

1.99

1469

 

2.04

1524

 

2.24

 

 

 

1638

 

2.60

1585

 

2.42

 

2600

1210

 

1.58

1243

 

1.67

1312

 

1.76

1366

 

1.96

1435

 

2.10

1494

 

2.19

1552

 

2.40

1616

 

2.63

1671

 

2.80

2700

1254

 

1.76

1285

 

1.80

1354

 

1.95

1403

 

2.14

1474

 

2.21

1536

 

2.46

1584

 

2.61

1646

 

2.83

1706

 

2.97

2800

1274

 

1.82

1304

 

1.85

1374

 

2.12

1459

 

2.25

1514

 

2.42

1570

 

2.66

1624

 

2.85

1677

 

2.99

 

2900

1318

 

1.95

1345

 

2.05

1412

 

2.32

1496

 

2.45

1529

 

2.61

1603

 

2.87

1671

 

3.03

 

 

3000

1362

 

2.20

1378

 

2.30

1451

 

2.40

1534

 

2.66

1560

 

2.81

1611

 

3.01

 

 

 

Table 25 — 48HJ007 Fan Performance — Horizontal Discharge Units With High-Static Motor

AIRFLOW

 

 

 

 

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

0.2

 

0.4

 

0.6

 

0.8

 

1.0

 

1.2

 

1.4

 

1.6

1.8

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

1800

942

 

0.73

1047

 

0.90

1139

 

1.05

1193

 

1.14

1276

 

1.30

1341

 

1.40

1413

 

1.55

1474

1.58

1522

 

1.74

1566

 

1.89

1900

982

 

0.83

1084

 

1.02

1160

 

1.11

1223

 

1.24

1301

 

1.38

1374

 

1.53

1437

 

1.62

1490

1.67

1538

 

1.84

1583

 

2.00

2000

1022

 

0.94

1121

 

1.12

1188

 

1.22

1264

 

1.36

1329

 

1.44

1396

 

1.66

1460

 

1.68

1509

1.77

1558

 

1.95

1603

 

2.12

2100

1063

 

1.10

1140

 

1.18

1196

 

1.27

1272

 

1.45

1354

 

1.58

1413

 

1.75

1475

 

1.73

1529

1.92

1578

 

2.11

1624

 

2.30

2200

1104

 

1.20

1159

 

1.23

1229

 

1.41

1306

 

1.53

1363

 

1.70

1434

 

1.81

1487

 

1.85

1554

2.07

1604

 

2.28

1651

 

2.48

2300

1130

 

1.27

1196

 

1.37

1264

 

1.56

1340

 

1.66

1397

 

1.86

1459

 

1.88

1520

 

2.07

1576

2.24

1627

 

2.46

1674

 

2.68

2400

1174

 

1.37

1245

 

1.57

1305

 

1.63

1373

 

1.84

1440

 

1.95

1502

 

2.06

1552

 

2.24

1604

2.42

1656

 

2.66

1704

 

2.90

2500

1201

 

1.50

1284

 

1.65

1338

 

1.75

1402

 

1.99

1469

 

2.04

1524

 

2.24

1585

 

2.42

1638

2.60

1691

 

2.86

 

 

 

1740

 

3.12

2600

1246

 

1.67

1312

 

1.76

1366

 

1.96

1435

 

2.10

1494

 

2.19

1552

 

2.40

1616

 

2.63

1671

2.80

1726

 

3.09

1775

 

3.35

2700

1285

 

1.80

1354

 

1.95

1403

 

2.14

1474

 

2.21

1536

 

2.46

1584

 

2.61

1646

 

2.83

1706

2.97

1761

 

3.27

 

2800

1304

 

1.85

1374

 

2.12

1459

 

2.25

1514

 

2.42

1570

 

2.66

1624

 

2.85

 

 

 

1739

3.33

1795

 

3.67

 

 

 

1677

 

2.99

 

2900

1345

 

2.05

1412

 

2.32

1496

 

2.54

1529

 

2.61

1603

 

2.87

1671

 

3.03

1742

 

3.43

 

 

3000

1378

 

2.30

1451

 

2.40

1534

 

2.66

1560

 

2.81

1611

 

3.01

1692

 

3.49

1764

 

3.95

 

 

LEGEND AND NOTES FOR TABLES 24 AND 25

LEGEND

Bhp — Brake Horsepower Input to Fan

FIOP — Factory-Installed Option

NOTES:

1.Boldface indicates field-supplied drive required. (See Note 3.)

2.Table 27 — FIOP MoistureMiser DehumidificationPackage Static Pressure Drop (in. wg) indicates field-supplied motor and drive required.

3.Motor drive range is 1120 to 1585 rpm for standard motors; 1300 to 1685 rpm for high-static motors. All other rpms require a field-supplied drive.

4.Values include losses for filters, unit casing, and wet coils. See below for accessory/FIOP static pressure information.

5.Maximum continuous bhp is 2.4 for standard motors; 2.9 for high-static motors. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or pre- mature motor failure. Unit warranty will not be affected. See Evaporator- Fan Motor Data tables on page 20 for additional information.

6.Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify.

7.Interpolation is permissible. Do not extrapolate.

Table 26 — Economizer Static Pressure Drop

(in. wg)

UNIT

 

 

 

 

CFM

 

 

 

 

900

1200

1400

1600

1800

2000

2200

2400

2600

 

Durablade

.05

.05

.05

.05

.05

.05

.05

.05

.05

EconoMi$er

.05

.10

.13

.17

.22

.27

.32

.39

.45

Table 27 — FIOP MoistureMiser Dehumidification

Package Static Pressure Drop (in. wg)

UNIT SIZE

 

UNIT

CFM PER TON

48HJ

 

NOMINAL TONS

300

400

500

E/F004

 

3

.04

.07

.09

D/E/F005

 

4

.07

.12

.15

D/E/F006

 

5

.09

.15

.21

D/E/F007

 

6

.12

.20

.28

LEGEND

 

 

 

 

FIOP — Factory-Installed Option

28

Image 28
Contents CONTENTS SAFETY CONSIDERATIONSINSTALLATION Step 1 - Provide Unit SupportFig. 1 - Roof Curb Details 1′-4″Fig. 2 - Unit Leveling Tolerances Fig. 3 - Condensate Drain PanStep 7 - Make Electrical Connections Table 1 - Physical Data Table 1 - Physical Data cont 1/2″ Fig. 5 - Base Unit Dimensions - 48HJ004-0073/4″ Step 8 - Adjust Factory-Installed Options Fig. 7 - Gas Piping Guide With AccessoryThru-the-Curb Service Connections Fig. 6 - Flue Hood DetailsFig. 10 - Field Control Wiring Raceway Fig. 8 - Power Wiring ConnectionsFig. 9 - Low-Voltage Connections With or Without Economizer age is greater than 2%. Use the following formula to determine Never operate a motor where a phase imbalance in supply voltthe percent of voltage imbalance Table 2C - 48HJ High-Static Motor Units Without Electrical Convenience Outlet Fig. 11 - Accessory Field-Installed Humidistat 208/230-V Unit ShownFig. 13 - Typical Access Panel Locations Fig. 15 - Durablade Economizer Installed in UnitFig. 16 - Horizontal Durablade Economizer Installation Fig. 14 - Outdoor-Air Hood DetailsWiring Harness Fig. 19A - Durablade Economizer Damper Minimum Position SettingFig. 19B - Durablade Economizer Minimum Position Damper Setting Fig. 20 - Outdoor-Air Thermostat Enthalpy Control InstallationRelief Damper Characteristics Fig. 24 - Typical Access Panel LocationsFig. 25 - Exhaust Air Hood Assembly Fig. 22 - Durablade Economizer BarometricFig. 28 - Rear EconoMi$er Flange Installation Fig. 26 - Outdoor-Air Hood AssemblyFig. 27 - Completed Hood Assembly Fig. 29 - EconoMi$er InstalledFig. 31 - EconoMi$er Sensor Wiring Fig. 33 - Typical Access Panel LocationsFig. 32 - Wiring Diagram for Power Exhaust System POWER EXHAUST SYSTEM HIGH VOLTAGEFig. 34 - Supply-Air Sensor Placement Table 4 - Default Potentiometer SettingsFig. 35 - EconoMi$er Control Adjustment Potentiometers Factory SettingsFig. 38 - Evaporator-Fan Pulley Adjustment Step 9 - Adjust Evaporator-Fan Speed - AdFig. 37 - Belt-Drive Motor Mounting Table 6 - Evaporator-Fan Motor Data - Standard Motor Table 5A - 48HJ Fan Rpm at Motor Pulley Setting With Standard MotorTable 7 - Evaporator-Fan Motor Data - High-Static Motors Table 9 - Outdoor Sound Power Total Unit Table 8 - Motor Nominal HorsepowerBels Table 12 - 48HJ005 Fan Performance - Vertical Discharge Units With Standard Motor Single-Phase Units 3-Phase UnitsTable 16 - 48HJ007 Fan Performance - Vertical Discharge Units With Standard Motor Table 18 - 48HJ004 Fan Performance - Horizontal Discharge Units With Standard Motor Table 20 - 48HJ005 Fan Performance - Horizontal Discharge Units With Standard Motor 3-Phase Units FIOP - Factory-Installed Option Table 26 - Economizer Static Pressure Drop in. wgTable 27 - FIOP MoistureMiser Dehumidification Package Static Pressure Drop in. wgPRE-START-UP START-UPOperating Sequence HeatingTable 28 - Altitude Compensation When the supply-air temperature falls between 57 F and Fig. 39 - MoistureMiser Option Operation SERVICE LubricationFig. 40 - Cleaning Condenser Coil Fig. 41 - Propping Up Top Panel Fig. 42 - Separating Coil SectionsFig. 44 - Cooling Charging Chart Standard 48HJ004 Fig. 43 - Condenser-Fan AdjustmentFig. 45 - Cooling Charging Chart Standard 48HJ005 Fig. 46 - Cooling Charging Chart Standard 48HJ006 Fig. 47 - Cooling Charging Chart Standard 48HJ007Fig. 48 - Cooling Charging Chart, 48HJ004 with Optional MoistureMiser Dehumidification Package Table 29 - LED Error Code Description Fig. 52 - Burner Section Details Fig. 53 - Burner Tray DetailsFig. 54 - Spark Gap Adjustment LOW HEAT 48HJE004, 48HJD005-007 - 72,000 BTUH INPUTMEDIUM AND HIGH HEAT 48HJE005-007, 48HJF004 - 115,000 BTUH INPUT 48HJF005-007 - 150,000 BTUH INPUTTROUBLESHOOTING Table 30 - LED Error Code Service AnalysisTable 31 - Heating Service Analysis Table 32 - Durablade Economizer Service AnalysisTable 33 - EconoMi$er Flash Code Identification Table 34 - EconoMi$er TroubleshootingCritical Table 35 - MoistureMiser Dehumidification Subcooler Service Analysis Table 36 - Cooling Service Analysis Compressor operates continuouslyFig. 55 - Typical Wiring Schematic and Component Arrangement 208/230 3-Phase Unit ShownLEGEND AND NOTES FOR FIG NOTES FOR FIGReplaces 48HJ-17SI Page START-UP CHECKLIST Remove and Store in Job File I. PRELIMINARY INFORMATIONII. PRE-START-UP insert checkmark in box as each item is completed III. START-UP