SERVICE
When servicing unit, shut off all electrical power to unit to avoid shock hazard or injury from rotating parts.
Cleaning — Inspect unit interior at the beginning of heat- ing and cooling season and as operating conditions require.
EVAPORATOR COIL
1.Turn unit power off, tag disconnect. Remove evaporator coil access panel.
2.If economizer or
3.Slide filters out of unit.
4.Clean coil using a commercial coil cleaner or dishwasher detergent in a pressurized spray canister. Wash both sides of coil and flush with clean water. For best results,
5.Reinstall economizer and filters.
6.Reconnect wiring.
7.Replace access panels.
CONDENSER COIL — Inspect coil monthly. Clean con- denser coil annually, and as required by location and outdoor air conditions.
Clean coil as follows:
1.Turn off unit power, tag disconnecct.
2.Remove top panel screws on condenser end of unit.
3.Remove condenser coil corner post. See Fig. 40. To hold top panel open, place coil corner post between top panel and center post. See Fig. 41.
4.Remove screws securing coil to compressor plate and compressor access panel.
5.Remove fastener holding coil sections together at return end of condenser coil. Carefully separate the outer coil section 3 to 4 in. from the inner coil section. See Fig. 42.
6.Use a water hose or other suitable equipment to flush down between the 2 coil sections to remove dirt and de- bris. Clean the outer surfaces with a stiff brush in the nor- mal manner.
7.Secure inner and outer coil rows together with a field- supplied fastener.
8.Reposition the outer coil section and remove the coil cor- ner post from between the top panel and center post. Re- install the coil corner post and replace all screws.
CONDENSATE DRAIN — Check and clean each year at start of cooling season. In winter, keep drain dry or protect against
FILTERS — Clean or replace at start of each heating and cool- ing season, or more often if operating conditions require it. Re- placement filters must be same dimensions as original filters.
Lubrication
COMPRESSORS — Each compressor is charged with correct amount of oil at the factory.
FAN MOTOR BEARINGS — Fan motor bearings are of the permanently lubricated type. No further lubrication is required. No lubrication of condenser- or
Fig. 40 — Cleaning Condenser Coil
Fig. 41 — Propping Up Top Panel
Fig. 42 — Separating Coil Sections
33