Carrier 48HJD005-007 48HJ004 Fan Performance - Horizontal Discharge Units With Standard Motor

Page 25

Table 18 — 48HJ004 Fan Performance — Horizontal Discharge Units With Standard Motor

AIRFLOW

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

0.1

 

0.2

0.3

 

 

0.4

 

0.5

 

0.6

(Cfm)

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

900

526

 

0.06

584

 

0.08

656

 

0.12

734

 

0.22

818

 

0.25

875

 

0.27

1000

570

 

0.09

627

 

0.13

738

 

0.19

800

 

0.26

848

 

0.29

895

 

0.31

1100

614

 

0.13

670

 

0.16

758

 

0.23

812

 

0.29

863

 

0.32

914

 

0.35

1200

658

 

0.16

710

 

0.23

780

 

0.28

840

 

0.32

889

 

0.36

938

 

0.40

1300

703

 

0.20

752

 

0.27

808

 

0.32

868

 

0.37

916

 

0.41

963

 

0.45

1400

725

 

0.29

776

 

0.31

845

 

0.38

891

 

0.42

937

 

0.47

983

 

0.51

1500

755

 

0.33

816

 

0.38

870

 

0.43

924

 

0.48

969

 

0.53

1014

 

0.58

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

0.7

 

0.8

0.9

 

 

1.0

 

1.1

 

1.2

(Cfm)

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

900

924

 

0.32

953

 

0.35

989

 

0.38

1028

 

0.42

1074

 

0.45

1120

 

0.50

1000

936

 

0.35

977

 

0.39

1020

 

0.44

1064

 

0.48

1124

 

0.52

1185

 

0.55

1100

960

 

0.39

1005

 

0.43

1052

 

0.49

1100

 

0.52

1163

 

0.56

1225

 

0.60

1200

988

 

0.45

1038

 

0.50

1076

 

0.53

1136

 

0.59

1201

 

0.61

1266

 

0.64

1300

1012

 

0.51

1061

 

0.56

1094

 

0.61

1172

 

0.65

1239

 

0.69

1306

 

0.72

1400

1027

 

0.56

1071

 

0.60

1108

 

0.67

1208

 

0.70

1278

 

0.75

1347

 

0.79

1500

1056

 

0.63

1097

 

0.68

1117

 

0.70

1245

 

0.74

1315

 

0.80

1385

 

0.85

Table 19 — 48HJ004 Fan Performance — Horizontal Discharge Units With High-Static Motor

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

0.4

 

 

0.6

 

0.8

 

1.0

(Cfm)

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

900

584

 

0.08

734

 

0.22

875

 

0.27

953

 

0.36

1028

 

0.42

1000

627

 

0.13

800

 

0.26

895

 

0.31

977

 

0.39

1064

 

0.48

1100

670

 

0.16

812

 

0.29

914

 

0.35

1005

 

0.43

1100

 

0.52

1200

710

 

0.23

840

 

0.32

938

 

0.40

1038

 

0.50

1136

 

0.59

1300

752

 

0.27

868

 

0.37

963

 

0.45

1061

 

0.56

1172

 

0.65

1400

776

 

0.31

891

 

0.42

983

 

0.51

1071

 

0.60

1208

 

0.70

1500

816

 

0.38

924

 

0.48

1014

 

0.58

1097

 

0.68

1245

 

0.74

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

1.2

1.4

 

 

1.6

 

1.8

 

2.0

(Cfm)

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

900

1120

 

0.54

1155

 

0.59

1186

 

0.64

1215

 

0.69

1240

 

0.73

1000

1185

 

0.60

1222

 

0.66

1255

 

0.71

1285

 

0.77

1312

 

0.82

1100

1225

 

0.65

1263

 

0.71

1298

 

0.77

1328

 

0.83

1357

 

0.88

1200

1266

 

0.72

1306

 

0.79

1341

 

0.86

1373

 

0.92

1402

 

0.98

1300

1306

 

0.79

1347

 

0.87

1383

 

0.94

1416

 

1.01

1446

 

1.07

1400

1347

 

0.87

1389

 

0.95

1427

 

1.03

1461

 

1.11

1492

 

1.18

1500

1385

 

0.96

1428

 

1.05

1467

 

1.14

1502

 

1.22

1534

 

1.30

LEGEND AND NOTES FOR TABLES 18 AND 19

LEGEND

Bhp — Brake Horsepower Input to Fan

FIOP — Factory-Installed Option

NOTES:

1.Boldface indicates field-supplied drive required. (See Note 3.)

2.Motor drive range is 760 to 1090 rpm for standard motors; 1075 to 1455 rpm for high-static motors. All other rpms require a field-supplied drive.

3.Values include losses for filters, unit casing, and wet coils. See page 28 for accessory/FIOP static pressure information.

4.Maximum continuous bhp is 1.20 for standard motors; 2.40 for high-static motors. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or pre- mature motor failure. Unit warranty will not be affected. See Evaporator- Fan Motor Data tables on page 20 for additional information.

5.Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify.

6.Interpolation is permissible. Do not extrapolate.

25

Image 25
Contents SAFETY CONSIDERATIONS CONTENTSINSTALLATION Step 1 - Provide Unit Support1′-4″ Fig. 1 - Roof Curb DetailsFig. 3 - Condensate Drain Pan Fig. 2 - Unit Leveling TolerancesStep 7 - Make Electrical Connections Table 1 - Physical Data Table 1 - Physical Data cont 1/2″ Fig. 5 - Base Unit Dimensions - 48HJ004-0073/4″ Fig. 7 - Gas Piping Guide With Accessory Step 8 - Adjust Factory-Installed OptionsThru-the-Curb Service Connections Fig. 6 - Flue Hood DetailsFig. 10 - Field Control Wiring Raceway Fig. 8 - Power Wiring ConnectionsFig. 9 - Low-Voltage Connections With or Without Economizer age is greater than 2%. Use the following formula to determine Never operate a motor where a phase imbalance in supply voltthe percent of voltage imbalance Table 2C - 48HJ High-Static Motor Units Without Electrical Convenience Outlet 208/230-V Unit Shown Fig. 11 - Accessory Field-Installed HumidistatFig. 15 - Durablade Economizer Installed in Unit Fig. 13 - Typical Access Panel LocationsFig. 16 - Horizontal Durablade Economizer Installation Fig. 14 - Outdoor-Air Hood DetailsFig. 19A - Durablade Economizer Damper Minimum Position Setting Wiring HarnessFig. 19B - Durablade Economizer Minimum Position Damper Setting Fig. 20 - Outdoor-Air Thermostat Enthalpy Control InstallationFig. 24 - Typical Access Panel Locations Relief Damper CharacteristicsFig. 25 - Exhaust Air Hood Assembly Fig. 22 - Durablade Economizer BarometricFig. 26 - Outdoor-Air Hood Assembly Fig. 28 - Rear EconoMi$er Flange InstallationFig. 27 - Completed Hood Assembly Fig. 29 - EconoMi$er InstalledFig. 33 - Typical Access Panel Locations Fig. 31 - EconoMi$er Sensor WiringFig. 32 - Wiring Diagram for Power Exhaust System POWER EXHAUST SYSTEM HIGH VOLTAGETable 4 - Default Potentiometer Settings Fig. 34 - Supply-Air Sensor PlacementFig. 35 - EconoMi$er Control Adjustment Potentiometers Factory SettingsFig. 38 - Evaporator-Fan Pulley Adjustment Step 9 - Adjust Evaporator-Fan Speed - AdFig. 37 - Belt-Drive Motor Mounting Table 6 - Evaporator-Fan Motor Data - Standard Motor Table 5A - 48HJ Fan Rpm at Motor Pulley Setting With Standard MotorTable 7 - Evaporator-Fan Motor Data - High-Static Motors Table 9 - Outdoor Sound Power Total Unit Table 8 - Motor Nominal HorsepowerBels Table 12 - 48HJ005 Fan Performance - Vertical Discharge Units With Standard Motor 3-Phase Units Single-Phase UnitsTable 16 - 48HJ007 Fan Performance - Vertical Discharge Units With Standard Motor Table 18 - 48HJ004 Fan Performance - Horizontal Discharge Units With Standard Motor Table 20 - 48HJ005 Fan Performance - Horizontal Discharge Units With Standard Motor 3-Phase Units Table 26 - Economizer Static Pressure Drop in. wg FIOP - Factory-Installed OptionTable 27 - FIOP MoistureMiser Dehumidification Package Static Pressure Drop in. wgSTART-UP PRE-START-UPOperating Sequence HeatingTable 28 - Altitude Compensation When the supply-air temperature falls between 57 F and Fig. 39 - MoistureMiser Option Operation Lubrication SERVICEFig. 40 - Cleaning Condenser Coil Fig. 41 - Propping Up Top Panel Fig. 42 - Separating Coil SectionsFig. 44 - Cooling Charging Chart Standard 48HJ004 Fig. 43 - Condenser-Fan AdjustmentFig. 45 - Cooling Charging Chart Standard 48HJ005 Fig. 47 - Cooling Charging Chart Standard 48HJ007 Fig. 46 - Cooling Charging Chart Standard 48HJ006Fig. 48 - Cooling Charging Chart, 48HJ004 with Optional MoistureMiser Dehumidification Package Fig. 52 - Burner Section Details Fig. 53 - Burner Tray Details Table 29 - LED Error Code DescriptionLOW HEAT 48HJE004, 48HJD005-007 - 72,000 BTUH INPUT Fig. 54 - Spark Gap AdjustmentMEDIUM AND HIGH HEAT 48HJE005-007, 48HJF004 - 115,000 BTUH INPUT 48HJF005-007 - 150,000 BTUH INPUTTable 30 - LED Error Code Service Analysis TROUBLESHOOTINGTable 32 - Durablade Economizer Service Analysis Table 31 - Heating Service AnalysisTable 33 - EconoMi$er Flash Code Identification Table 34 - EconoMi$er TroubleshootingCritical Table 35 - MoistureMiser Dehumidification Subcooler Service Analysis Compressor operates continuously Table 36 - Cooling Service Analysis208/230 3-Phase Unit Shown Fig. 55 - Typical Wiring Schematic and Component ArrangementNOTES FOR FIG LEGEND AND NOTES FOR FIGReplaces 48HJ-17SI Page I. PRELIMINARY INFORMATION START-UP CHECKLIST Remove and Store in Job FileII. PRE-START-UP insert checkmark in box as each item is completed III. START-UP