Table 1 — Physical Data (cont)
BASE UNIT 48 | HJE/F/H/K/M/N004 | HJD/E/F/G/H/K/L/M/N005 |
| HJD/E/F/G/H/K/L/M/N006 | HJD/HJE/HJF007 | |||
FURNACE SECTION |
|
|
|
|
|
|
|
|
Rollout Switch Cutout Temp (F)† | 195 |
| 195 |
|
| 195 |
| 195 |
Burner Orifice Diameter (in. ...drill size)** |
|
|
|
|
|
|
|
|
Natural Gas — Std | HJE .113...33 | HJD .113...33 |
| HJD .113...33 | HJD .113...33 | |||
| HJF .113...33 | HJE .113...33 |
| HJE .113...33 | HJE .113...33 | |||
| — | HJF .129...30 |
| HJF .129...30 | HJF .129...30 | |||
| HJH .113...33 | HJG .113...33 |
| HJG .113...33 |
| — | ||
| HJK .113...33 | HJH .113...33 |
| HJH .113...33 |
| — | ||
| — | HJK .129...30 |
| HJK .129...30 |
| — | ||
| HJM .102...38 | HJL .102...38 |
| HJL .102...38 |
| — | ||
| HJN .102...38 | HJM .102...38 |
| HJM .102...38 |
| — | ||
| — | HJN .116...32 |
| HJN .116...32 |
| — | ||
Liquid Propane — Alt†† | HJE .089...43 | HJD .089...43 |
| HJD .089...43 | HJD .089...43 | |||
| HJF .089...43 | HJE .089...43 |
| HJE .089...43 | HJE .089...43 | |||
| — | HJF .102...38 |
| HJF .102...38 | HJF .102...38 | |||
| HJH .082...45 | HJG .089...43 |
| HJG .089...43 |
| — | ||
| HJK .082...45 | HJH .089...43 |
| HJH .089...43 |
| — | ||
| — | HJK .102...38 |
| HJK .102...38 |
| — | ||
| HJM .082...45 | HJL .082...45 |
| HJL .082...45 |
| — | ||
| HJN .082...45 | HJM .082...45 |
| HJM .082...45 |
| — | ||
Thermostat Heat Anticipator Setting (amps) 208/230/460 v | — | HJN .094...42 |
| HJN .094...42 |
| — | ||
|
|
|
|
|
|
|
| |
First Stage | .14 |
| .14 |
|
| .14 |
| .14 |
Second Stage | .14 |
| .14 |
|
| .14 |
| .14 |
Gas Input (Btuh) |
|
|
|
|
|
|
|
|
First Stage/Second Stage | HJE 50,000/ 72,000 | HJD | 50,000/ 72,000 |
| HJD | 50,000/ 72,000 | HJD | 50,000/ 72,000 |
| HJF 82,000/115,000 | HJE | 82,000/115,000 |
| HJE | 82,000/115,000 | HJE | 82,000/115,000 |
| — | HJF 120,000/150,000 |
| HJF 120,000/150,000 | HJF 120,000/150,000 | |||
| HJH*** | HJG*** |
| HJG*** |
| — | ||
| HJH*** |
| HJH*** |
| — | |||
| — | HJK*** |
| HJK*** |
| — | ||
| HJM††† | HJL††† |
| HJL††† |
| — | ||
| HJN††† | HJM††† |
|
| — | |||
| — | HJN††† |
| HJN††† |
| — | ||
Efficiency (Steady State) (%) | HJE 82 | HJD 82 |
| HJD 82 | HJD 82 | |||
| HJF 81 | HJE 81 |
| HJE 81 | HJE 81 | |||
| — | HJF 80 |
| HJF 80 | HJF 80 | |||
| HJH 82 | HJG 82 |
| HJG 82 |
| — | ||
| HJK 81 | HJH 81 |
| HJH 81 |
| — | ||
| — | HJK 80 |
| HJK 80 |
| — | ||
| HJM 81 | HJL 81 |
| HJL 81 |
| — | ||
| HJN 81 | HJM 81 |
| HJM 81 |
| — | ||
| — | HJN 82 |
| HJN 82 |
| — | ||
Temperature Rise Range | HJE | HJD |
| HJD | HJD | |||
| HJF | HJE |
| HJE | HJE | |||
| — | HJF |
| HJF | HJF | |||
| HJH | HJG |
| HJG |
| — | ||
| HJK | HJH |
| HJH |
| — | ||
| — | HJK |
| HJK |
| — | ||
| HJM | HJL |
| HJL |
| — | ||
| HJN | HJM |
| HJM |
| — | ||
Manifold Pressure (in. wg) | — | HJN |
| HJN |
| — | ||
|
|
|
|
|
|
|
| |
Natural Gas — Std | 3.5 |
| 3.5 |
|
| 3.5 |
| 3.5 |
Liquid Propane — Alt†† | 3.5 |
| 3.5 |
|
| 3.5 |
| 3.5 |
Maximum Static Pressure (in. wg) | 1.0 |
| 1.0 |
|
| 1.0 |
| 1.0 |
Field Gas Connection Size (in.) | 1/2 |
| 1/2 |
|
| 1/2 |
| 1/2 |
|
|
|
|
|
|
|
| |
Standard Compressor Internal Relief |
|
| 450 ± 50 |
|
|
| ||
Cutout |
|
|
| 428 |
|
|
| |
Reset (Auto.) |
|
|
| 320 |
|
|
| |
|
|
|
|
|
|
|
| |
SWITCH (Liquid LIne) (psig) |
|
|
|
|
|
|
|
|
Cutout |
|
|
| 7 ± 3 |
|
|
| |
Reset (Auto.) |
|
| 22 ± 5 |
|
|
| ||
FREEZE PROTECTION THERMOSTAT |
|
|
|
|
|
|
|
|
Opens (F) |
|
| 30 ± 5 |
|
|
| ||
Closes (F) |
|
| 45 ± 5 |
|
|
| ||
|
| Cleanable |
|
|
| |||
Quantity...Size (in.) |
|
| 1...20 x 24 x 1 |
|
|
| ||
|
| Throwaway |
|
|
| |||
Quantity...Size (in.) |
|
| 2...16 x 25 x 2 |
|
|
|
LEGEND
Bhp — Brake Horsepower
*Single phase/three phase. †Indicates automatic reset.
††An LP kit is available as an accessory.
48HJE004, 48HJD005,006 — 72,000 Btuh
48HJF004, 48HJE005,006 — 115,000 Btuh 48HJF005,006 — 150,000 Btuh
***California compliant
†††California SCAQMD compliant low NOx models have combustion products that are controlled to 40 nanograms per joule or less.
6