TROUBLESHOOTING
Refer to Tables
Table 30 — LED Error Code Service Analysis
SYMPTOM | CAUSE | REMEDY |
Hardware failure. | Loss of power to control module (IGC). | Check 5 amp fuse on IGC, power to unit, |
(LED OFF) |
| transformer. Units without a |
|
| overload in the |
|
| 10 minutes for automatic reset. |
Fan ON/OFF delay modified | High limit switch opens during heat | Ensure unit is fired on rate and temperature rise is correct. |
(LED/FLASH) | exchanger |
|
| delay expires. |
|
| Limit switch opens within three minutes | Ensure units’ external static pressure is within application guidelines. |
| after |
|
Limit switch fault. | High temperature limit switch is open. | Check the operation of the indoor (evaporator) fan motor. |
(LED 2 flashes) |
| Ensure that the |
|
| the range on the unit nameplate. |
Flame sense fault. | The IGC sensed flame that should not be | Reset unit. If problem persists, replace control board. |
(LED 3 flashes) | present. |
|
4 consecutive limit | Inadequate airflow to unit. | Check operation of indoor (evaporator) fan motor and that |
switch faults. |
| temperature rise agrees with range on unit nameplate information. |
(LED 4 flashes) |
|
|
Ignition lockout. | Unit unsuccessfully attempted ignition for | Check ignitor and flame sensor electrode spacing, gaps, etc. |
(LED 5 flashes) | 15 minutes. | Ensure that flame sense and ignition wires are properly |
|
| terminated. Verify that unit is obtaining proper amount of gas. |
IGC does not sense that | Check for proper voltage. If motor is operating, check the | |
(LED 6 flashes) | motor is operating. | speed sensor plug/IGC Terminal J2 connection. Proper |
|
| connection: PIN 1— White, PIN 2 — Red, PIN 3 — Black. |
Rollout switch fault. | Rollout switch has opened. | Rollout switch will automatically reset, but IGC will continue to |
(LED 7 flashes) |
| lock out unit. Check gas valve operation. Ensure that induced- |
|
| draft blower wheel is properly secured to motor shaft. |
|
| Reset unit at unit disconnect. |
Internal control fault. | Microprocessor has sensed an error in the | If error code is not cleared by resetting unit power, replace the IGC. |
(LED 8 flashes) | software or hardware. |
|
If the IGC must be replaced, be sure to ground yourself to dissi- pate any electrical charge that may be present before handling new control board. The IGC is sensitive to static electricity and may be damaged if the necessary precautions are not taken.
IMPORTANT: Refer to heating troubleshooting for additional heating section troubleshooting information.
LEGEND
IGC — Integrated Gas Unit Controller
LED —
39