Carrier 48HJD005-007 LED Error Code Description, Burner Section Details - Burner Tray Details

Page 37
Table 29 — LED Error Code Description*

Burner Ignition — Unit is equipped with a direct spark ignition 100% lockout system. Integrated Gas Unit Controller (IGC) is located in the control box (Fig. 10). A single LED on the IGC provides a visual display of operational or sequential problems when the power supply is uninterrupted. The LED can be observed through the viewport. When a break in power occurs, the IGC will be reset (resulting in a loss of fault history) and the evaporator fan on/off times delay will be reset. During servicing, refer to the label on the control box cover or Table 29 for an explanation of LED error code descriptions.

If lockout occurs, unit may be reset by interrupting power supply to unit for at least 5 seconds.

Table 29 — LED Error Code Description*

LED INDICATION

ERROR CODE DESCRIPTION

ON

Normal Operation

OFF

Hardware Failure

1 Flash†

Evaporator Fan On/Off Delay Modified

2 Flashes

Limit Switch Fault

3 Flashes

Flame Sense Fault

4 Flashes

4 Consecutive Limit Switch Faults

5 Flashes

Ignition Lockout Fault

6 Flashes

Induced-Draft Motor Fault

7 Flashes

Rollout Switch Fault

8 Flashes

Internal Control Fault

LEGEND

 

LED — Light-Emitting Diode

*A 3-second pause exists between LED error code flashes. If more than one error code exists, all applicable codes will be displayed in numerical sequence.

†Indicates a code that is not an error. The unit will continue to oper- ate when this code is displayed.

IMPORTANT: Refer to Troubleshooting Tables 30-36 for addi- tional information.

Main Burners — At the beginning of each heating sea- son, inspect for deterioration or blockage due to corrosion or other causes. Observe the main burner flames and adjust, if necessary.

When servicing gas train, do not hit or plug orifice spuds.

REMOVAL AND REPLACEMENT OF GAS TRAIN (See Fig. 52 and 53)

1.Shut off manual gas valve.

2.Shut off power to unit, tag disconnect.

3.Remove compressor access panel.

4.Slide out burner compartment side panel.

5.Disconnect gas piping at unit gas valve.

6.Remove wires connected to gas valve. Mark each wire.

7.Remove induced-draft motor, ignitor, and sensor wires at the Integrated Gas Unit Controller (IGC).

8.Remove the 2 screws that attach the burner rack to the vestibule plate.

9.Remove the gas valve bracket.

10.Slide the burner tray out of the unit (Fig. 53).

11.To reinstall, reverse the procedure outlined above.

INDUCED-

ROLLOUT

DRAFT

SWITCH

MOTOR

 

MOUNTING

 

PLATE

 

BURNER

 

SECTION

FLUE

 

EXHAUST

 

VESTIBULE

INDUCED-

PLATE

DRAFT

BLOWER

MOTOR

 

HOUSING

MANIFOLD

GAS

PRESSURE

TAP

VALVE

Fig. 52 — Burner Section Details

Fig. 53 — Burner Tray Details

CLEANING AND ADJUSTMENT

1.Remove burner rack from unit as described above.

2.Inspect burners and, if dirty, remove burners from rack.

3.Using a soft brush, clean burners and cross-over port as required.

4.Adjust spark gap. See Fig. 54.

5.Reinstall burners on rack.

6.Reinstall burner rack as described above.

Replacement Parts — A complete list of replace- ment parts may be obtained from any Carrier distributor upon request. Refer to Fig. 55 for a typical unit wiring schematic.

37

Image 37
Contents SAFETY CONSIDERATIONS CONTENTSINSTALLATION Step 1 - Provide Unit Support1′-4″ Fig. 1 - Roof Curb DetailsFig. 3 - Condensate Drain Pan Fig. 2 - Unit Leveling TolerancesStep 7 - Make Electrical Connections Table 1 - Physical Data Table 1 - Physical Data cont 1/2″ Fig. 5 - Base Unit Dimensions - 48HJ004-0073/4″ Fig. 7 - Gas Piping Guide With Accessory Step 8 - Adjust Factory-Installed OptionsThru-the-Curb Service Connections Fig. 6 - Flue Hood DetailsFig. 10 - Field Control Wiring Raceway Fig. 8 - Power Wiring ConnectionsFig. 9 - Low-Voltage Connections With or Without Economizer age is greater than 2%. Use the following formula to determine Never operate a motor where a phase imbalance in supply voltthe percent of voltage imbalance Table 2C - 48HJ High-Static Motor Units Without Electrical Convenience Outlet 208/230-V Unit Shown Fig. 11 - Accessory Field-Installed HumidistatFig. 15 - Durablade Economizer Installed in Unit Fig. 13 - Typical Access Panel LocationsFig. 16 - Horizontal Durablade Economizer Installation Fig. 14 - Outdoor-Air Hood DetailsFig. 19A - Durablade Economizer Damper Minimum Position Setting Wiring HarnessFig. 19B - Durablade Economizer Minimum Position Damper Setting Fig. 20 - Outdoor-Air Thermostat Enthalpy Control InstallationFig. 24 - Typical Access Panel Locations Relief Damper CharacteristicsFig. 25 - Exhaust Air Hood Assembly Fig. 22 - Durablade Economizer BarometricFig. 26 - Outdoor-Air Hood Assembly Fig. 28 - Rear EconoMi$er Flange InstallationFig. 27 - Completed Hood Assembly Fig. 29 - EconoMi$er InstalledFig. 33 - Typical Access Panel Locations Fig. 31 - EconoMi$er Sensor WiringFig. 32 - Wiring Diagram for Power Exhaust System POWER EXHAUST SYSTEM HIGH VOLTAGETable 4 - Default Potentiometer Settings Fig. 34 - Supply-Air Sensor PlacementFig. 35 - EconoMi$er Control Adjustment Potentiometers Factory SettingsFig. 38 - Evaporator-Fan Pulley Adjustment Step 9 - Adjust Evaporator-Fan Speed - AdFig. 37 - Belt-Drive Motor Mounting Table 6 - Evaporator-Fan Motor Data - Standard Motor Table 5A - 48HJ Fan Rpm at Motor Pulley Setting With Standard MotorTable 7 - Evaporator-Fan Motor Data - High-Static Motors Table 9 - Outdoor Sound Power Total Unit Table 8 - Motor Nominal HorsepowerBels Table 12 - 48HJ005 Fan Performance - Vertical Discharge Units With Standard Motor 3-Phase Units Single-Phase UnitsTable 16 - 48HJ007 Fan Performance - Vertical Discharge Units With Standard Motor Table 18 - 48HJ004 Fan Performance - Horizontal Discharge Units With Standard Motor Table 20 - 48HJ005 Fan Performance - Horizontal Discharge Units With Standard Motor 3-Phase Units Table 26 - Economizer Static Pressure Drop in. wg FIOP - Factory-Installed OptionTable 27 - FIOP MoistureMiser Dehumidification Package Static Pressure Drop in. wgSTART-UP PRE-START-UPOperating Sequence HeatingTable 28 - Altitude Compensation When the supply-air temperature falls between 57 F and Fig. 39 - MoistureMiser Option Operation Lubrication SERVICEFig. 40 - Cleaning Condenser Coil Fig. 41 - Propping Up Top Panel Fig. 42 - Separating Coil SectionsFig. 44 - Cooling Charging Chart Standard 48HJ004 Fig. 43 - Condenser-Fan AdjustmentFig. 45 - Cooling Charging Chart Standard 48HJ005 Fig. 47 - Cooling Charging Chart Standard 48HJ007 Fig. 46 - Cooling Charging Chart Standard 48HJ006Fig. 48 - Cooling Charging Chart, 48HJ004 with Optional MoistureMiser Dehumidification Package Fig. 52 - Burner Section Details Fig. 53 - Burner Tray Details Table 29 - LED Error Code DescriptionLOW HEAT 48HJE004, 48HJD005-007 - 72,000 BTUH INPUT Fig. 54 - Spark Gap AdjustmentMEDIUM AND HIGH HEAT 48HJE005-007, 48HJF004 - 115,000 BTUH INPUT 48HJF005-007 - 150,000 BTUH INPUTTable 30 - LED Error Code Service Analysis TROUBLESHOOTINGTable 32 - Durablade Economizer Service Analysis Table 31 - Heating Service AnalysisTable 33 - EconoMi$er Flash Code Identification Table 34 - EconoMi$er TroubleshootingCritical Table 35 - MoistureMiser Dehumidification Subcooler Service Analysis Compressor operates continuously Table 36 - Cooling Service Analysis208/230 3-Phase Unit Shown Fig. 55 - Typical Wiring Schematic and Component ArrangementNOTES FOR FIG LEGEND AND NOTES FOR FIGReplaces 48HJ-17SI Page I. PRELIMINARY INFORMATION START-UP CHECKLIST Remove and Store in Job FileII. PRE-START-UP insert checkmark in box as each item is completed III. START-UP