Carrier 48HJD005-007 specifications Legend And Notes For Fig

Page 45
LEGEND AND NOTES FOR FIG. 55

LEGEND AND NOTES FOR FIG. 55

AHA — Adjustable Heat Anticipator

CContactor, Compressor CAP — Capacitor

CCCooling Compensator CLO — Compressor Lockout COMP — Compressor Motor

DDiode

EC

Enthalpy Control

ECON — Economizer

EPS

Emergency Power Supply

EQUIP — Equipment

ER

Economizer Relay

FPT

Freeze-Protection Thermostat

FSS

Filter-Status Switch

FU

Fuse

GND

Ground

GVR

Gas Valve Relay

HPS

High-Pressure Switch

HS

Hall-Effect Sensor

HV

High Voltage

IIgnitor

IDM

Induced-Draft Motor

IFC

Indoor (Evaporator) Fan Contactor

IFM

Indoor (Evaporator) Fan Motor

IGC

Integrated Gas Unit Controller

LED

Light-Emitting Diode

LPS

Low-Pressure/Loss-of-Charge Switch

LS

Limit Switch

MGV

Main Gas Valve

MTR

Motor

OAT

Outdoor-Air Thermostat

OFM

Outdoor (Condenser) Fan Motor

PPlug

PL — Plug Assembly

QT — Quadruple Terminal

RRelay

RS

Rollout Switch

SAT

Supply-Air Thermostat

SEN

Sensor

SW1

Switch Fully Open

SW2

Switch Fully Closed

SW3

Switch Minimum Vent Position

SW4

Switch Maximum Vent Position

TC

Thermostat-Cooling

TH

Thermostat-Heating

TRAN — Transformer

Field Splice

Marked Wire

Terminal (Marked)

Terminal (Unmarked)

Terminal Block

Splice

Splice (Marked)

Factory Wiring

Field Control Wiring

Field Power Wiring

Accessory or Optional Wiring

To indicate common potential only. Not to represent wiring.

NOTES FOR FIG. 55

1.If any of the original wire furnished must be replaced, it must be replaced with Type 90 C wire or its equivalent.

2.Three-phase motors are protected under primary single-phasing conditions.

3.Thermostats: HH07AT170, 172

Subbase: HH93AZ176, 177, 178 and 179

4.Set heat anticipator at .14 amp for first stage and .14 amp for second stage.

5.Use copper conductors only.

6.TRAN is wired for 230 v unit. If unit is to be run with 208 v power supply, disconnect BLK wire from 230 v tap and connect to 208 v tap (RED). Insulate end of 230 v tap.

45

Image 45
Contents SAFETY CONSIDERATIONS CONTENTSINSTALLATION Step 1 - Provide Unit Support1′-4″ Fig. 1 - Roof Curb DetailsFig. 3 - Condensate Drain Pan Fig. 2 - Unit Leveling TolerancesStep 7 - Make Electrical Connections Table 1 - Physical Data Table 1 - Physical Data cont Fig. 5 - Base Unit Dimensions - 48HJ004-007 1/2″3/4″ Fig. 7 - Gas Piping Guide With Accessory Step 8 - Adjust Factory-Installed OptionsThru-the-Curb Service Connections Fig. 6 - Flue Hood DetailsFig. 8 - Power Wiring Connections Fig. 10 - Field Control Wiring RacewayFig. 9 - Low-Voltage Connections With or Without Economizer Never operate a motor where a phase imbalance in supply volt age is greater than 2%. Use the following formula to determinethe percent of voltage imbalance Table 2C - 48HJ High-Static Motor Units Without Electrical Convenience Outlet 208/230-V Unit Shown Fig. 11 - Accessory Field-Installed HumidistatFig. 15 - Durablade Economizer Installed in Unit Fig. 13 - Typical Access Panel LocationsFig. 16 - Horizontal Durablade Economizer Installation Fig. 14 - Outdoor-Air Hood DetailsFig. 19A - Durablade Economizer Damper Minimum Position Setting Wiring HarnessFig. 19B - Durablade Economizer Minimum Position Damper Setting Fig. 20 - Outdoor-Air Thermostat Enthalpy Control InstallationFig. 24 - Typical Access Panel Locations Relief Damper CharacteristicsFig. 25 - Exhaust Air Hood Assembly Fig. 22 - Durablade Economizer BarometricFig. 26 - Outdoor-Air Hood Assembly Fig. 28 - Rear EconoMi$er Flange InstallationFig. 27 - Completed Hood Assembly Fig. 29 - EconoMi$er InstalledFig. 33 - Typical Access Panel Locations Fig. 31 - EconoMi$er Sensor WiringFig. 32 - Wiring Diagram for Power Exhaust System POWER EXHAUST SYSTEM HIGH VOLTAGETable 4 - Default Potentiometer Settings Fig. 34 - Supply-Air Sensor PlacementFig. 35 - EconoMi$er Control Adjustment Potentiometers Factory SettingsStep 9 - Adjust Evaporator-Fan Speed - Ad Fig. 38 - Evaporator-Fan Pulley AdjustmentFig. 37 - Belt-Drive Motor Mounting Table 5A - 48HJ Fan Rpm at Motor Pulley Setting With Standard Motor Table 6 - Evaporator-Fan Motor Data - Standard MotorTable 7 - Evaporator-Fan Motor Data - High-Static Motors Table 8 - Motor Nominal Horsepower Table 9 - Outdoor Sound Power Total UnitBels Table 12 - 48HJ005 Fan Performance - Vertical Discharge Units With Standard Motor 3-Phase Units Single-Phase UnitsTable 16 - 48HJ007 Fan Performance - Vertical Discharge Units With Standard Motor Table 18 - 48HJ004 Fan Performance - Horizontal Discharge Units With Standard Motor Table 20 - 48HJ005 Fan Performance - Horizontal Discharge Units With Standard Motor 3-Phase Units Table 26 - Economizer Static Pressure Drop in. wg FIOP - Factory-Installed OptionTable 27 - FIOP MoistureMiser Dehumidification Package Static Pressure Drop in. wgSTART-UP PRE-START-UPHeating Operating SequenceTable 28 - Altitude Compensation When the supply-air temperature falls between 57 F and Fig. 39 - MoistureMiser Option Operation Lubrication SERVICEFig. 40 - Cleaning Condenser Coil Fig. 41 - Propping Up Top Panel Fig. 42 - Separating Coil SectionsFig. 43 - Condenser-Fan Adjustment Fig. 44 - Cooling Charging Chart Standard 48HJ004Fig. 45 - Cooling Charging Chart Standard 48HJ005 Fig. 47 - Cooling Charging Chart Standard 48HJ007 Fig. 46 - Cooling Charging Chart Standard 48HJ006Fig. 48 - Cooling Charging Chart, 48HJ004 with Optional MoistureMiser Dehumidification Package Fig. 52 - Burner Section Details Fig. 53 - Burner Tray Details Table 29 - LED Error Code DescriptionLOW HEAT 48HJE004, 48HJD005-007 - 72,000 BTUH INPUT Fig. 54 - Spark Gap AdjustmentMEDIUM AND HIGH HEAT 48HJE005-007, 48HJF004 - 115,000 BTUH INPUT 48HJF005-007 - 150,000 BTUH INPUTTable 30 - LED Error Code Service Analysis TROUBLESHOOTINGTable 32 - Durablade Economizer Service Analysis Table 31 - Heating Service AnalysisTable 34 - EconoMi$er Troubleshooting Table 33 - EconoMi$er Flash Code IdentificationCritical Table 35 - MoistureMiser Dehumidification Subcooler Service Analysis Compressor operates continuously Table 36 - Cooling Service Analysis208/230 3-Phase Unit Shown Fig. 55 - Typical Wiring Schematic and Component ArrangementNOTES FOR FIG LEGEND AND NOTES FOR FIGReplaces 48HJ-17SI Page I. PRELIMINARY INFORMATION START-UP CHECKLIST Remove and Store in Job FileII. PRE-START-UP insert checkmark in box as each item is completed III. START-UP