Carrier 19XRV Primary Secondary Primary Cause Additional CAUSE/REMEDY, Sensor Alert, Low Oil

Page 13

Table 4 — ICVC Alert Codes (cont)

CHILLER ALERTS

ICVC FAULT

PRIMARY

SECONDARY

PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

STATE

MESSAGE

MESSAGE

 

 

140

SENSOR ALERT

LEAVING COND WATER

140Sensor Fault: Check

Check sensor resistance or voltage drop.

 

 

TEMP

Leaving Cond Water Sensor.

Check for proper wiring.

141

SENSOR ALERT

ENTERING COND WATER

141Sensor Fault: Check

Check sensor resistance or voltage drop.

 

 

TEMP

Entering Cond Water Sensor.

Check for proper wiring.

142

LOW OIL

CHECK OIL FILTER

142Low Oil Pressure Alert.

Check for partially or closed shut-off valves.

 

PRESSURE ALERT

 

Check Oil Filter.

Check oil filter.

 

 

 

 

Check oil pump and power supply.

 

 

 

 

Check oil level.

 

 

 

 

Check for foaming oil at start-up.

 

 

 

 

Check transducer wiring and accuracy.

143

AUTORESTART

LINE CURRENT

143Line Current Imbal-

Power loss has been detected in any phase.

 

PENDING

IMBALANCE

ance: Check VFD Fault His-

Chiller automatically restarting.

 

 

 

tory for Values.

 

144

AUTORESTART

LINE VOLTAGE

144Single Cycle Line

A drop in line voltage has been detected within

 

PENDING

DROP OUT

Voltage Dropout.

2 voltage cycles.

 

 

 

 

Chiller automatically restarting if Auto Restart is

 

 

 

 

enabled in OPTIONS screen.

145

AUTORESTART

HIGH LINE VOLTAGE

145High Percent Line

Check phase to phase and phase to ground line

 

PENDING

 

Voltage [VALUE].

power.

146

AUTORESTART

LOW LINE VOLTAGE

146Low Percent Line

Check phase to phase and phase to ground line

 

PENDING

 

Voltage [VALUE].

power.

147

AUTORESTART

VFD MODULE RESET

147->VFD Module Power-On

VFD Module has detected a hardware fault due

 

PENDING

 

Reset When Running.

to electrical noise, power loss or software and

 

 

 

 

has reset. Chiller automatically restarting.

 

 

 

 

Check for power loss and sources of electro-

 

 

 

 

magnetic interference.

148

AUTORESTART

POWER LOSS

148Control Power-Loss

Check 24 vac control power supply to ICVC.

 

PENDING

 

When Running.

 

149

SENSOR ALERT

HIGH DISCHARGE TEMP

149Comp Discharge Temp

Check sensor resistance or voltage drop.

 

 

 

[VALUE] Exceeded Limit of

Check for proper wiring.

 

 

 

[LIMIT]*.

Check for proper inlet guide vane and optional

 

 

 

 

diffuser actuator operation.

 

 

 

 

Check for proper condenser flow and

 

 

 

 

temperature.

 

 

 

 

Check for high lift or low load.

 

 

 

 

Check for fouled tubes or noncondensables in

 

 

 

 

the chiller.

150

SENSOR ALERT

HIGH BEARING

150Comp Thrust Brg Temp

Check sensor resistance or voltage drop.

 

 

TEMPERATURE

[VALUE] exceeded limit of

Check for proper wiring.

 

 

 

[LIMIT]*.

Check for partially closed service valves.

 

 

 

 

Check oil cooler TXV.

 

 

 

 

Check oil level and oil temperature.

151

CONDENSER

PUMP RELAY

151High Condenser Pres-

Check sensor wiring and accuracy.

 

PRESSURE ALERT

ENERGIZED

sure [VALUE]: Pump Ener-

Check condenser flow and water temperature.

 

 

 

gized to Reduce Pressure.

Check for fouled tubes.

 

 

 

 

This alarm is not caused by the High Pressure

 

 

 

 

Switch.

152

RECYCLE ALERT

EXCESSIVE RECYCLE

152Excessive recycle

Chiller load is too low to keep compressor on

 

 

STARTS

starts.

line and there has been more than 5 starts in

 

 

 

 

4 hours.

 

 

 

 

Increase chiller load, adjust hot gas bypass,

 

 

 

 

increase RECYCLE RESTART DELTA T from

 

 

 

 

SETUP1 Screen.

153

no message:

no message; ALERT only

153Lead/Lag Disabled-

Illegal chiller address configuration in Lead/Lag

 

ALERT

 

Config: Duplicate Chiller

screen. Both chillers require a different address.

 

only

 

Address.

 

154

POTENTIAL

COND PRESS/TEMP

154Condenser freeze up

The condenser pressure transducer is reading a

 

FREEZE-UP

TOO LOW

prevention.

pressure that could freeze the condenser tubes.

 

 

 

 

Check for condenser refrigerant leaks.

 

 

 

 

Check fluid temperature.

 

 

 

 

Check sensor wiring and accuracy.

 

 

 

 

Place the chiller in PUMPDOWN mode if the

 

 

 

 

vessel is evacuated.

155

OPTION SENSOR

REMOTE RESET

155Sensor Fault/Option

Check sensor resistance or voltage drop.

 

FAULT

SENSOR

Disabled: Remote Reset

Check for proper wiring to CCM connector J4.

 

 

 

Sensor.

 

156

OPTION SENSOR

AUTO CHILLED WATER

156Sensor Fault/Option

Check sensor resistance or voltage drop.

 

FAULT

RESET

Disabled: Auto Chilled Water

Check for proper wiring to CCM connector J5.

 

 

 

Reset.

 

157

OPTION SENSOR

AUTO DEMAND LIMIT

157Sensor Fault/Option

Check sensor resistance or voltage drop.

 

FAULT

INPUT

Disabled: Auto Demand Limit

Check for proper wiring to CCM connector J5.

 

 

 

Input.

 

158

SENSOR ALERT

SPARE TEMPERATURE

158Spare Temperature 1

Check sensor resistance or voltage drop.

 

 

#1

[VALUE] exceeded limit of

Check for proper wiring to CCM connector J4.

 

 

 

[LIMIT]*.

Check Spare Temp #1 Limit in SETUP1 screen.

*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.

13

Image 13 Contents
Start-Up and Service Instructions Contents A19-1842 A19-1831A19-1814 1832 A19A19-1833 A19-1834 Wire LugsParameter Default Value VFD ConfigurationsA19 1846 TB1 I/O Terminal Designations A19-1921A19-1836 A19-18351815 Name Color State Description Drive Status Indicator DescriptionsEnet LinkA19-1925 A19-1844Message Icvc Alert CodesPrestart AlertLimited RUN CapacityPrimary Secondary Primary Cause Additional CAUSE/REMEDY FaultSensor Alert LOW OILCommunication LossVFD Speed Alert System AlertFailure to Stop Icvc Alarm CodesProtective Limit 234 233235 236Unused State UnusedVFD Gateway Sensor FaultVFD Fault Type Description Corrective Action On VFDCode Hist Screen NoneNone Hist Screen113 124Meter Lead Meter Reading Diode ChecksFrames 6 and 7 Power Terminal Block A19-1831Fig Open Access DoorA19-1814Fig Check DC Bus Terminals A19-1816Fig Removing EnclosureA19-1838 A19-1837A19-1817A19-1818 A19-1819 Comm CardCR1 EA1 Line CR6 CB1 TB4 A19-1847CB2 FU1-FU3 PT1 Secondary Side Toward Door TB4 Dist SideFrame 6 Parts A19-1848A19-1946 Appendix a Wiring Schematics Chiller Control SchematicHgbp A19-1947RHS UPCA19-1966 Shld A19-1967A48-8579 A48-8578Table a SW3 Protocol Switch Settings For MS/TP Appendix B Optional Bacnet Communications WiringTable B Baud Selection Table A48 8580A48-8582 Table C MS/TP Wiring RecommendationsRmcorp Wiring Specifications Recommended Vendors and Part NumbersCMP RUN LED Error LED Status Table E LED Status IndicatorsLED Status RunObject ID Object Name CHW Page Copyright 2011 Carrier Corporation