Carrier 19XRV specifications A19 1846, VFD Configurations, Parameter Default Value

Page 6

a19-

1846

A United Technologies Company

MODEL NUMBER

SERIAL NUMBER

MACHINE NAMEPLATE SUPPLY DATA

VOLTS/PHASE/HERTZ

LOCKED ROTOR AMPS

OVERLOAD TRIP AMPS

MAX FUSE/CIRCUIT BREAKER SIZE

MIN SUPPLY CIRCUIT AMPACITY

MACHINE ELECTRICAL DATA

MOTOR NAMEPLATE VOLTAGE

COMPRESSOR 100% SPEED

RATED LINE VOLTAGE

RATED LINE AMPS

RATED LINE KILOWATTS

MOTOR RATED LOAD KW

MOTOR RATED LOAD AMPS

MOTOR NAMEPLATE AMPS

MOTOR NAMEPLATE RPM

MOTOR NAMEPLATE KW

INTERTER PWM FREQUENCY

SAFETY CODE CERTIFICATION

THE COMPRESSOR MOTOR CONTROLLER AND OVERLOAD PROTECTION MUST BE

IN ACCORDANCE WITH CARRIER SPECIFICATION Z-420.

19XV05008701 REV. 3

Fig. 8 — Machine Nameplate

a19-

1924

Fig. 9 — Drive Module Label

Configure the VFD — All configurations required by the VFD are supplied by the ICVC through the VFD Gateway. Any configuration changes necessary and possible are made on the ICVC screens. A complete set of configurations is transmit- ted to the VFD each time the controls are powered up.

The following is from the 19XRV PIC III ICVC screen. Pa- rameters in italics are to be entered or confirmed at start-up. Pa- rameters in bold are to be changed only after consulting with Carrier service engineering. See Table 2.

Table 2 VFD Configurations

PARAMETER

DEFAULT VALUE

Motor Nameplate Voltage

460

Compressor 100% Speed

 

Line Freq=60 Hz? (No=50)

Yes

Rated Line Voltage*

460

Rated Line Amps*

200

Rated Line Kilowatts *

100

Motor Rated Load kW*

100

Motor Rated Load Amps*

200

Motor Nameplate Amps

100

Motor Nameplate RPM

3456

Motor Nameplate KW

100

Inverter PWM Frequency (0 = 4 kHz, 1 =

1

2 kHz)

 

Skip Frequency 1 (Hz)

102.0

Skip Frequency 2 (Hz)

102.0

Skip Frequency 3 (Hz)

102.0

Skip Frequency Band Line (Hz)

0.0

Voltage % Imbalance

10

Line Volt Imbalance Time (sec)

10

Line Current % Imbalance

40

Line Current Imbal Time (sec)

10

Motor Current % Imbalance

40

Motor Current Imbal Time

10

Increase Ramp Time (sec)

30

Decrease Ramp Time (sec)

30

Single Cycle Dropout (DSABLE/ENABLE)

DSABLE

*Parameters marked with an * are not downloadable to the VFD but are used in other calculations and algorithms in the ICVC.

NOTES:

1.Parameters in italics are to be entered or confirmed at start-up.

2.Parameters in bold are to be changed only after consultation with ser- vice engineering.

Commissioning the Unit — The commission proce- dure is as follows:

1.If the chiller has been stored outdoors, allow at least 24 hours room temperature stabilization prior to commis- sioning. Ensure any condensation that occurs as a result of the ambient temperature is allowed to evaporate.

2.Enter parameters in the VFD_CONF screen.

3.Install surge suppression devices if required.

4.Review the power wiring and grounding to ensure that it has been properly connected.

5.Visually examine the inside of the drive enclosure to:

a.Look for signs of corrosion or moisture residue.

b.Remove any dirt or debris.

c.Make sure all vents are clear.

6.Apply power to the drive and take thermal measurements of the capacitor bank and power connections. Do this again before start-up.

7.Measure and record the incoming line voltage. Line-to- line voltages should be balanced within 3% as calculated by Rockwell’s procedure below:

Measure voltages phase-to-phase and phase-to-ground.

6

Image 6 Contents
Start-Up and Service Instructions Contents A19-1831 A19-1842A19-1814 A19 1832A19-1833 Wire Lugs A19-1834VFD Configurations Parameter Default ValueA19 1846 A19-1921 TB1 I/O Terminal DesignationsA19-1835 A19-18361815 Enet Drive Status Indicator DescriptionsName Color State Description LinkA19-1844 A19-1925Prestart Icvc Alert CodesMessage AlertRUN Capacity LimitedSensor Alert FaultPrimary Secondary Primary Cause Additional CAUSE/REMEDY LOW OILVFD Speed Alert LossCommunication System AlertIcvc Alarm Codes Failure to StopProtective Limit 235 233234 236Unused Unused StateSensor Fault VFD GatewayCode Fault Type Description Corrective Action On VFDVFD Hist Screen None113 Hist ScreenNone 124Diode Checks Meter Lead Meter ReadingA19-1814Fig Check DC Bus Terminals A19-1831Fig Open Access DoorFrames 6 and 7 Power Terminal Block A19-1816Fig Removing EnclosureA19-1837 A19-1838A19-1817A19-1818 Comm Card A19-1819CB2 FU1-FU3 PT1 Secondary Side Toward Door A19-1847CR1 EA1 Line CR6 CB1 TB4 TB4 Dist SideA19-1848 Frame 6 PartsAppendix a Wiring Schematics Chiller Control Schematic A19-1946RHS A19-1947Hgbp UPCA19-1966 A19-1967 ShldA48-8578 A48-8579Table B Baud Selection Table Appendix B Optional Bacnet Communications WiringTable a SW3 Protocol Switch Settings For MS/TP A48 8580Table C MS/TP Wiring Recommendations A48-8582Wiring Specifications Recommended Vendors and Part Numbers RmcorpCMP LED Status Table E LED Status IndicatorsRUN LED Error LED Status RunObject ID Object Name CHW Page Copyright 2011 Carrier Corporation