Table 4 — ICVC Alert Codes

PRE-START ALERTS: These alerts only delay start-up. When alert is corrected, the start-up will continue. No reset is necessary.

ICVC FAULT

PRIMARY

SECONDARY

PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

STATE

MESSAGE

MESSAGE

 

 

100

PRESTART

STARTS LIMIT

100Excessive compressor starts

Depress the RESET softkey if additional start

 

ALERT

EXCEEDED

(8 in 12 hours).

is required. Reassess start-up requirements.

101

PRESTART

HIGH BEARING

101Comp Thrust Brg Temp [VALUE]

Check oil heater for proper operation.

 

ALERT

TEMPERATURE

exceeded limit of [LIMIT]*.

Check for low oil level, partially closed oil sup-

 

 

 

 

ply valves, clogged oil filters.

 

 

 

 

Check the sensor wiring and accuracy.

 

 

 

 

Check Comp Thrust Brg Alert setting in

 

 

 

 

SETUP1 screen.

102

PRESTART

HIGH MOTOR

102Comp Motor Winding Temp

Check motor sensors for wiring and accuracy.

 

ALERT

TEMPERATURE

[VALUE] exceeded limit of [LIMIT]*.

Check motor cooling line for proper operation,

 

 

 

 

or restrictions.

 

 

 

 

Check for excessive starts within a short time

 

 

 

 

span.

 

 

 

 

Check Comp Motor Temperature Override

 

 

 

 

setting in SETUP1 screen.

103

PRESTART

HIGH

103Comp Discharge Temp [VALUE]

Allow discharge sensor to cool.

 

ALERT

DISCHARGE

exceeded limit of [LIMIT]*.

Check sensor wiring and accuracy.

 

 

TEMP

 

Check for excessive starts.

 

 

 

 

Check Comp Discharge Alert setting in

 

 

 

 

SETUP1 screen.

104

PRESTART

LOW

104Evaporator Refrig Temp [VALUE]

Check transducer wiring and accuracy.

 

ALERT

REFRIGERANT

exceeded limit of [LIMIT]*.

Check for low chilled fluid supply

 

 

TEMP

 

temperatures.

 

 

 

 

Check refrigerant charge.

 

 

 

 

Check Refrig Override Delta T in SETUP1

 

 

 

 

screen.

105

PRESTART

LOW OIL

105Oil Sump Temp [VALUE]

Check oil heater contactor/relay and power.

 

ALERT

TEMPERATURE

exceeded limit of [LIMIT]*.

Check oil level and oil pump operation.

106

PRESTART

HIGH

106Condenser Pressure [VALUE]

Check transducer wiring and accuracy.

 

ALERT

CONDENSER

exceeded limit of [LIMIT]*.

Check for high condenser water

 

 

PRESSURE

 

temperatures.

 

 

 

 

Check high condenser pressure switch wiring.

107

PRESTART

LOW LINE

107Percent Line Voltage [VALUE]

Check voltage supply.

 

ALERT

VOLTAGE

exceeded limit of [LIMIT]*.

Check voltage transformers and switch gear.

 

 

 

 

Consult power utility if voltage is low.

108

PRESTART

HIGH LINE

108Percent Line Voltage [VALUE]

Check voltage supply.

 

ALERT

VOLTAGE

exceeded limit of [LIMIT]*.

Check power transformers.

 

 

 

 

Consult power utility if voltage is high.

109

PRESTART

GUIDE VANE

109Actual Guide Vane Pos

Press STOP button on ICVC and perform

 

ALERT

CALIBRATION

Calibration Required Before Startup.

Guide Vane Calibration in Controls Test

 

 

 

 

screen.

 

 

 

 

Check guide vane actuator feedback

 

 

 

 

potentiometer.

110

PRESTART

HIGH

110Rectifier Temperature [VALUE]

Check that VFD refrigerant isolation valves

 

ALERT

RECTIFIER

exceeded limit of [LIMIT]*.

are open.

 

 

TEMP

 

Check VFD refrigerant cooling solenoid and

 

 

 

 

refrigerant strainer.

 

 

 

 

Check for proper VFD cooling fan operation

 

 

 

 

and blockage.

111

PRESTART

HIGH

111Inverter Temperature [VALUE]

Check that VFD refrigerant isolation valves

 

ALERT

INVERTER

exceeded limit of [LIMIT]*.

are open.

 

 

TEMP

 

Check VFD refrigerant cooling solenoid and

 

 

 

 

refrigerant strainer.

 

 

 

 

Check for proper VFD cooling fan operation

 

 

 

 

and blockage.

*[LIMIT] is shown on the ICVC as temperature, pressure, voltage, etc., predefined or selected by the operator as an override or an alert. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.

11

Image 11 Contents
Start-Up and Service Instructions Contents A19-1814 A19-1831A19-1842 A19-1833 A191832 A19-1834 Wire LugsA19 1846 VFD ConfigurationsParameter Default Value TB1 I/O Terminal Designations A19-19211815 A19-1835A19-1836 Link Drive Status Indicator DescriptionsName Color State Description EnetA19-1925 A19-1844Alert Icvc Alert CodesMessage PrestartLimited RUN CapacityLOW OIL FaultPrimary Secondary Primary Cause Additional CAUSE/REMEDY Sensor AlertSystem Alert LossCommunication VFD Speed AlertFailure to Stop Icvc Alarm CodesProtective Limit 236 233234 235Unused State UnusedVFD Gateway Sensor FaultHist Screen None Fault Type Description Corrective Action On VFDVFD Code124 Hist ScreenNone 113Meter Lead Meter Reading Diode ChecksA19-1816Fig Removing Enclosure A19-1831Fig Open Access DoorFrames 6 and 7 Power Terminal Block A19-1814Fig Check DC Bus TerminalsA19-1817A19-1818 A19-1837A19-1838 A19-1819 Comm CardTB4 Dist Side A19-1847CR1 EA1 Line CR6 CB1 TB4 CB2 FU1-FU3 PT1 Secondary Side Toward DoorFrame 6 Parts A19-1848A19-1946 Appendix a Wiring Schematics Chiller Control SchematicUPC A19-1947Hgbp RHSA19-1966 Shld A19-1967A48-8579 A48-8578A48 8580 Appendix B Optional Bacnet Communications WiringTable a SW3 Protocol Switch Settings For MS/TP Table B Baud Selection TableA48-8582 Table C MS/TP Wiring RecommendationsCMP Wiring Specifications Recommended Vendors and Part NumbersRmcorp Run Table E LED Status IndicatorsRUN LED Error LED Status LED StatusObject ID Object Name CHW Page Copyright 2011 Carrier Corporation