Table 6 Powerflex 755 Fault Code Descriptions and Corrective Actions

VFD

 

 

 

 

FAULT

ICVC

 

 

 

CODE

 

 

 

FAULT

FAULT TYPE

DESCRIPTION

CORRECTIVE ACTION

ON VFD

STATE

 

 

 

HIST

 

 

 

 

 

 

 

SCREEN

 

 

 

 

NONE

206

 

Processor memory fault

Consult VFD manual to resolve generic fault.

0

 

No Entry

 

 

 

 

 

 

Check Compressor Discharge High Pressure

 

 

 

 

switch wiring and accuracy.

2

207

Auxiliary Input

Input is open.

Check for high condenser water temperatures,

low water flow, fouled tubes.

 

 

 

 

 

 

 

 

Check for division plate/gasket bypass. Check for

 

 

 

 

noncondensables in refrigerant.

3

210

Power Loss

Line voltage dropout

Temporary loss of voltage. Disable Single Cycle

Dropout in VFD_CONF sceen.

 

 

 

 

4

 

 

 

Verify phase-to-phase and phase-to-ground line

215

Undervoltage

Low DC bus voltage

voltage. VFD Circuit Board malfunction.

 

 

 

 

Call Carrier Service.

5

 

 

 

Verify phase to phase and phase to ground line

166

Overvoltage

High DC bus voltage

voltage. Monitor AC line for high transient voltage

 

 

 

 

conditions.

 

 

 

 

Any phase current > 106% RLA. Can result from

 

 

 

 

significant load side current imbalance when

7

 

 

 

running at full load.

217

Motor Overload

An internal electronic overload trip has occurred.

Check entering condenser water temperature

 

 

 

 

and water flow rate.

 

 

 

 

Check Motor Rated Load Amps in VFD_CONF

 

 

 

 

screen.

 

 

 

 

Check that VFD refrigerant isolation valves are

 

 

 

 

open.

8

219

Heat Sink Over-

Heat sink temperature has exceeded the maxi-

Check VFD refrigerant cooling orifice and refrig-

temp

mum operating temperature

erant strainer.

 

 

 

 

 

 

Check for proper VFD cooling fan operation and

 

 

 

 

air flow blockage.

 

 

 

 

Check that VFD refrigerant isolation valves are

 

 

 

 

open.

9

219

Transistor Over-

The output transistors have exceeded the maxi-

Check VFD refrigerant cooling orifice and refrig-

temp

mum operating temperature

erant strainer.

 

 

 

 

 

 

Check for proper VFD cooling fan operation and

 

 

 

 

air flow blockage.

12

 

 

The drive output current has exceeded the hard-

Check for high entering water temperature or low

286

HW Overcurrent

condenser water flow. Check current settings in

ware current limit.

 

 

 

VFD_CONF screen.

 

 

 

 

13

 

 

A current path to earth ground greater than 25%

Check the motor, motor terminals, and external

220

Ground Fault

wiring to the drive output terminals for a

of drive rating has occurred.

 

 

 

grounded condition.

 

 

 

 

14

206

Ground Warning

The ground current has exceeded the level set in

P467

 

 

 

 

 

 

 

 

To reset the processor, cycle power to chiller,

15

206

Load Loss

If this fault appears, there may be a problem with

check ICVC VFD_CONF settings and save set-

software configuration.

tings when exiting VFD_CONF screen.

 

 

 

 

 

 

 

Check VFD parameters with Drive Explorer.

17

 

The DC bus ripple

 

Check phase-to-phase and phase-to-ground dis-

216

has exceeded a

Line Voltage imbalance

tribution bus voltage. Increase Line Voltage %

 

 

preset level.

 

Imbalance in VFD_CONF screen.

20

206

TorqPrv Spd Band

See VFD Fault Code 15

See VFD Fault Code 15

21

225

Output PhaseLoss

The current in one or more phases has been lost

Check Motor Current % Imbalance in

or remains below a preset level.

VFD_CONF screen.

 

 

 

 

 

 

 

Verify input voltage is within drive specified limits.

 

 

 

The drive is not following a commanded decelera-

Verify system ground impedance follows proper

24

204

Decel Inhibit

grounding techniques.

tion because it is attempting to limit the bus volt-

Disable bus regulation P186 and/or add dynamic

 

 

 

age.

 

 

 

brake resistor and/or extend deceleration time

 

 

 

 

 

 

 

 

P537 and P538.

33

206

AuRsts Exhausted

See VFD Fault Code 15

See VFD Fault Code 15

36

286

SW Overcurrent

The drive output current has exceeded the 1 ms

Check for excess load, improper DC boost set-

current rating.

ting, DC brake volts set too high.

 

 

 

20

Image 20 Contents
Start-Up and Service Instructions Contents A19-1814 A19-1831A19-1842 A19-1833 A191832 Wire Lugs A19-1834A19 1846 VFD ConfigurationsParameter Default Value A19-1921 TB1 I/O Terminal Designations1815 A19-1835A19-1836 Drive Status Indicator Descriptions Name Color State DescriptionEnet LinkA19-1844 A19-1925Icvc Alert Codes MessagePrestart AlertRUN Capacity LimitedFault Primary Secondary Primary Cause Additional CAUSE/REMEDYSensor Alert LOW OILLoss CommunicationVFD Speed Alert System AlertIcvc Alarm Codes Failure to StopProtective Limit 233 234235 236Unused Unused StateSensor Fault VFD GatewayFault Type Description Corrective Action On VFD VFDCode Hist Screen NoneHist Screen None113 124Diode Checks Meter Lead Meter ReadingA19-1831Fig Open Access Door Frames 6 and 7 Power Terminal BlockA19-1814Fig Check DC Bus Terminals A19-1816Fig Removing EnclosureA19-1817A19-1818 A19-1837A19-1838 Comm Card A19-1819A19-1847 CR1 EA1 Line CR6 CB1 TB4CB2 FU1-FU3 PT1 Secondary Side Toward Door TB4 Dist SideA19-1848 Frame 6 PartsAppendix a Wiring Schematics Chiller Control Schematic A19-1946A19-1947 HgbpRHS UPCA19-1966 A19-1967 ShldA48-8578 A48-8579Appendix B Optional Bacnet Communications Wiring Table a SW3 Protocol Switch Settings For MS/TPTable B Baud Selection Table A48 8580Table C MS/TP Wiring Recommendations A48-8582CMP Wiring Specifications Recommended Vendors and Part NumbersRmcorp Table E LED Status Indicators RUN LED Error LED StatusLED Status RunObject ID Object Name CHW Page Copyright 2011 Carrier Corporation