APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)

COMMUNICATION LEDS — The LEDs indicate if the controller is communicating with the devices on the network. See Tables E and F. The LEDs should reflect communication traffic based on the baud rate set. The higher the baud rate the more solid the LEDs become. See Fig. B for location of LEDs on UPC Open module.

REPLACING THE UPC OPEN BATTERY — The UPC Open controller's 10-year lithium CR2032 battery provides a minimum of 10,000 hours of data retention during power outages.

IMPORTANT: Power must be ON to the UPC Open when replacing the battery, or the date, time, and trend data will be lost.

Remove the battery from the controller, making note of the battery's polarity. Insert the new battery, matching the battery's polarity with the polarity indicated on the UPC Open controller.

NETWORK POINTS LIST — The points list for the control- ler is shown in Table G.

 

Table E — LED Status Indicators

 

 

LED

STATUS

Power

Lights when power is being supplied to the controller. The UPC Open controller is protected by internal solid-state polyswitches on

the incoming power and network connections. These polyswitches are not replaceable and will reset themselves if the condition

 

that caused the fault returns to normal.

Rx

Lights when the controller receives data from the network segment; there is an Rx LED for Ports 1 and 2.

Tx

Lights when the controller transmits data to the network segment; there is a Tx LED for Ports 1 and 2.

Run

Lights based on controller status. See Table F.

Error

Lights based on controller status. See Table F.

Table F — Run and Error LEDs Controller and Network Status Indication

RUN LED

 

ERROR LED

STATUS

2 flashes per second

Off

 

Normal

2 flashes per second

2 flashes,

alternating with Run LED

Five minute auto-restart delay after system error

2 flashes per second

3 flashes,

then off

Controller has just been formatted

2 flashes per second

1 flash per second

Controller is alone on the network

2 flashes per second

On

 

Exec halted after frequent system errors or control programs halted

5 flashes per second

On

 

Exec start-up aborted, Boot is running

5 flashes per second

Off

 

Firmware transfer in progress, Boot is running

7 flashes per second

7 flashes per second, alternating with Run LED

Ten second recovery period after brownout

14 flashes per second

14 flashes per second, alternating with Run LED

Brownout

36

Image 36
Contents Start-Up and Service Instructions Contents A19-1831 A19-1842A19-1814 A19 1832A19-1833 Wire Lugs A19-1834VFD Configurations Parameter Default ValueA19 1846 A19-1921 TB1 I/O Terminal DesignationsA19-1835 A19-18361815 Drive Status Indicator Descriptions Name Color State DescriptionEnet LinkA19-1844 A19-1925Icvc Alert Codes MessagePrestart AlertRUN Capacity LimitedFault Primary Secondary Primary Cause Additional CAUSE/REMEDYSensor Alert LOW OILLoss CommunicationVFD Speed Alert System AlertIcvc Alarm Codes Failure to StopProtective Limit 233 234235 236Unused Unused StateSensor Fault VFD GatewayFault Type Description Corrective Action On VFD VFDCode Hist Screen NoneHist Screen None113 124Diode Checks Meter Lead Meter ReadingA19-1831Fig Open Access Door Frames 6 and 7 Power Terminal BlockA19-1814Fig Check DC Bus Terminals A19-1816Fig Removing EnclosureA19-1837 A19-1838A19-1817A19-1818 Comm Card A19-1819A19-1847 CR1 EA1 Line CR6 CB1 TB4CB2 FU1-FU3 PT1 Secondary Side Toward Door TB4 Dist SideA19-1848 Frame 6 PartsAppendix a Wiring Schematics Chiller Control Schematic A19-1946A19-1947 HgbpRHS UPCA19-1966 A19-1967 ShldA48-8578 A48-8579Appendix B Optional Bacnet Communications Wiring Table a SW3 Protocol Switch Settings For MS/TPTable B Baud Selection Table A48 8580Table C MS/TP Wiring Recommendations A48-8582Wiring Specifications Recommended Vendors and Part Numbers RmcorpCMP Table E LED Status Indicators RUN LED Error LED StatusLED Status RunObject ID Object Name CHW Page Copyright 2011 Carrier Corporation

19XRV specifications

The Carrier 19XRV is a cutting-edge rooftop chiller designed to provide reliable and efficient cooling solutions for a wide range of applications, including commercial buildings and industrial facilities. This advanced system integrates the latest technologies and innovative features to ensure optimal performance, energy efficiency, and ease of use.

One of the most prominent features of the 19XRV is its advanced inverter-driven compressor technology. This allows the chiller to adjust its capacity seamlessly based on the building's cooling demand. By varying the speed of the compressor, the 19XRV maximizes energy efficiency and minimizes operational costs, especially during partial load conditions. This capability not only enhances comfort but also contributes to reduced energy consumption, making it a sustainable choice for environmentally conscious users.

In addition to the inverter technology, the 19XRV incorporates a microchannel coil design. This design optimizes heat exchange efficiency and reduces the refrigerant charge, which is an essential factor in lowering greenhouse gas emissions. The microchannel coils also allow for more compact dimensions, making installation easier and maximizing rooftop space usage.

Another significant aspect of the Carrier 19XRV is its robust controls system. Equipped with Carrier’s advanced ComfortLink™ controls, this chiller offers precise monitoring and control over its operation. Users can easily integrate the chiller into building management systems for real-time data access and efficiency analytics. This connectivity ensures that operators can make informed decisions to optimize performance continuously.

The 19XRV also includes features aimed at enhancing reliability and durability. Its structural design incorporates corrosion-resistant materials, allowing the unit to withstand harsh environmental conditions. This reliability translates to lower maintenance requirements and extended equipment lifespan, providing excellent value over time.

Moreover, the chiller is designed for quiet operation, making it suitable for applications where low noise levels are essential. Sound-dampening measures ensure that the 19XRV can be utilized in urban environments or near sensitive areas without causing disturbances.

In conclusion, the Carrier 19XRV is a state-of-the-art rooftop chiller that combines efficiency, technology, and durability. Its inverter-driven compressor, microchannel coil design, advanced controls, and robust construction make it an ideal choice for those looking to maintain comfort while minimizing energy usage and environmental impact. Whether for commercial or industrial applications, the 19XRV stands out as a reliable and innovative cooling solution for the modern age.