APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING

Optional BACnet* Communications Wiring —

The following section is used to configure the UPC Open con- troller which is used when the BACnet communications option is selected. The UPC Open controller is mounted in a separate enclosure below the main control box.

TO ADDRESS THE UPC OPEN CONTROLLER — The user must give the UPC Open controller an address that is unique on the BACnet network. Perform the following proce- dure to assign an address:

1.If the UPC Open controller is powered, pull the screw ter- minal connector from the controller's power terminals la- beled Gnd and HOT. The controller reads the address each time power is applied to it.

2.Using the rotary switches (see Fig. A and B), set the con- troller's address. Set the Tens (10's) switch to the tens dig- it of the address, and set the Ones (1's) switch to the ones digit.

As an example in Fig. B, if the controller’s address is 25, point the arrow on the Tens (10's) switch to 2 and the arrow on the Ones (1's) switch to 5.

9

0

1

 

 

8

 

2

10's

 

7

 

 

3

a48-8578

6

 

4

 

5

 

 

 

 

 

 

 

 

9

0

1

 

 

8

 

2

 

 

7

 

 

3

1's

 

6

 

4

 

 

5

 

 

 

 

 

 

 

 

Fig. B — Address Rotary Switches

BACNET DEVICE INSTANCE ADDRESS — The UPC Open controller also has a BACnet Device Instance address. This Device Instance MUST be unique for the complete BAC- net system in which the UPC Open controller is installed. The Device Instance is auto generated by default and is derived by adding the MAC address to the end of the Network Number. The Network Number of a new UPC Open controller is 16101, but it can be changed using i-Vu®Tools or BACView device. By default, a MAC address of 20 will result in a Device In- stance of 16101 + 20 which would be a Device Instance of 1610120.

BT485

TERMINATOR

BACNET CONNECTION (BAS PORT)

Tx1 LED Rx1 LED

POWER LED

Tx2 LED

Rx2 LED

EIA-485

JUMPERS

Fig. A — UPC Open Controller

a48-8579

6

78

 

 

9

5

 

 

0

4

 

1

 

3

2

 

 

 

 

 

7

8

 

6

9

5

 

 

0

4

2

1

 

3

 

 

 

 

BACNET

BAUD RATE

DIP SWITCHES

ADDRESS

ROTARY

SWITCHES

RUN LED

ERROR LED

*Sponsored by ASHRAE (American Society of Heating, Refrigerat- ing and Air Conditioning Engineers).

32

Image 32 Contents
Start-Up and Service Instructions Contents A19-1814 A19-1831A19-1842 A19-1833 A191832 Wire Lugs A19-1834A19 1846 VFD ConfigurationsParameter Default Value A19-1921 TB1 I/O Terminal Designations1815 A19-1835A19-1836 Drive Status Indicator Descriptions Name Color State DescriptionEnet LinkA19-1844 A19-1925Icvc Alert Codes MessagePrestart AlertRUN Capacity LimitedFault Primary Secondary Primary Cause Additional CAUSE/REMEDYSensor Alert LOW OILLoss CommunicationVFD Speed Alert System AlertIcvc Alarm Codes Failure to StopProtective Limit 233 234235 236Unused Unused StateSensor Fault VFD GatewayFault Type Description Corrective Action On VFD VFDCode Hist Screen NoneHist Screen None113 124Diode Checks Meter Lead Meter ReadingA19-1831Fig Open Access Door Frames 6 and 7 Power Terminal BlockA19-1814Fig Check DC Bus Terminals A19-1816Fig Removing EnclosureA19-1817A19-1818 A19-1837A19-1838 Comm Card A19-1819A19-1847 CR1 EA1 Line CR6 CB1 TB4CB2 FU1-FU3 PT1 Secondary Side Toward Door TB4 Dist SideA19-1848 Frame 6 PartsAppendix a Wiring Schematics Chiller Control Schematic A19-1946A19-1947 HgbpRHS UPCA19-1966 A19-1967 ShldA48-8578 A48-8579Appendix B Optional Bacnet Communications Wiring Table a SW3 Protocol Switch Settings For MS/TPTable B Baud Selection Table A48 8580Table C MS/TP Wiring Recommendations A48-8582CMP Wiring Specifications Recommended Vendors and Part NumbersRmcorp Table E LED Status Indicators RUN LED Error LED StatusLED Status RunObject ID Object Name CHW Page Copyright 2011 Carrier Corporation