Carrier 19XRV Appendix B Optional Bacnet Communications Wiring, Table B Baud Selection Table

Page 33

APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)

CONFIGURING THE BAS PORT FOR BACNET MS/ TP — Use the same baud rate and communication settings for all controllers on the network segment. The UPC Open con- troller is fixed at 8 data bits, No Parity, and 1 Stop bit for this protocol's communications.

If the UPC Open controller has been wired for power, pull the screw terminal connector from the controller's power termi- nals labeled Gnd and HOT. The controller reads the DIP Switches and jumpers each time power is applied to it.

Set the BAS Port DIP switch DS3 to “enable.” Set the BAS Port DIP switch DS4 to “EIA-485.” Set the BMS Protocol DIP switches DS8 through DS5 to “MSTP.” See Table A.

Table A — SW3 Protocol Switch Settings

for MS/TP

DS8

DS7

DS6

DS5

DS4

DS3

Off

Off

Off

Off

On

Off

Verify that the EIA-485 jumpers below the CCN Port are set to EIA-485 and 2W.

The example in Fig. C shows the BAS Port DIP Switches set for 76.8k (Carrier default) and MS/TP.

Set the BAS Port DIP Switches DS2 and DS1 for the appro- priate communications speed of the MS/TP network (9600, 19.2k, 38.4k, or 76.8k bps). See Fig. C and Table B.

Table B — Baud Selection Table

BAUD RATE

DS2

DS1

9,600

Off

Off

19,200

On

Off

38,400

Off

On

76,800

On

On

WIRING THE UPC OPEN CONTROLLER TO THE MS/ TP NETWORK — The UPC Open controller communicates using BACnet on an MS/TP network segment communications at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps.

a48-

8580

Fig. C — DIP Switches

Wire the controllers on an MS/TP network segment in a dai- sy-chain configuration. Wire specifications for the cable are 22 AWG (American Wire Gage) or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire. The maximum length is 2000 ft.

Install a BT485 terminator on the first and last controller on a network segment to add bias and prevent signal distortions due to echoing. See Fig. B, D, and E.

To wire the UPC Open controller to the BAS network:

1.Pull the screw terminal connector from the controller's BAS Port.

2.Check the communications wiring for shorts and grounds.

3.Connect the communications wiring to the BAS port’s screw terminals labeled Net +, Net -, and Shield.

NOTE: Use the same polarity throughout the network segment.

4.Insert the power screw terminal connector into the UPC Open controller's power terminals if they are not current- ly connected.

5.Verify communication with the network by viewing a module status report. To perform a module status report using the BACview keypad/display unit, press and hold the “FN” key then press the “.” Key.

a48-8581

Fig. D — Network Wiring

33

Image 33 Contents
Start-Up and Service Instructions Contents A19-1831 A19-1842A19-1814 A19 1832A19-1833 A19-1834 Wire LugsVFD Configurations Parameter Default ValueA19 1846 TB1 I/O Terminal Designations A19-1921A19-1835 A19-18361815 Name Color State Description Drive Status Indicator DescriptionsEnet LinkA19-1925 A19-1844Message Icvc Alert CodesPrestart AlertLimited RUN CapacityPrimary Secondary Primary Cause Additional CAUSE/REMEDY FaultSensor Alert LOW OILCommunication LossVFD Speed Alert System AlertFailure to Stop Icvc Alarm CodesProtective Limit 234 233235 236Unused State UnusedVFD Gateway Sensor FaultVFD Fault Type Description Corrective Action On VFDCode Hist Screen NoneNone Hist Screen113 124Meter Lead Meter Reading Diode ChecksFrames 6 and 7 Power Terminal Block A19-1831Fig Open Access DoorA19-1814Fig Check DC Bus Terminals A19-1816Fig Removing EnclosureA19-1837 A19-1838A19-1817A19-1818 A19-1819 Comm CardCR1 EA1 Line CR6 CB1 TB4 A19-1847CB2 FU1-FU3 PT1 Secondary Side Toward Door TB4 Dist SideFrame 6 Parts A19-1848A19-1946 Appendix a Wiring Schematics Chiller Control SchematicHgbp A19-1947RHS UPCA19-1966 Shld A19-1967A48-8579 A48-8578Table a SW3 Protocol Switch Settings For MS/TP Appendix B Optional Bacnet Communications WiringTable B Baud Selection Table A48 8580A48-8582 Table C MS/TP Wiring RecommendationsWiring Specifications Recommended Vendors and Part Numbers RmcorpCMP RUN LED Error LED Status Table E LED Status IndicatorsLED Status RunObject ID Object Name CHW Page Copyright 2011 Carrier Corporation