Carrier 19XRV specifications RUN Capacity, Limited

Page 12

Table 4 — ICVC Alert Codes (cont)

NORMAL RUN WITH OVERRIDES

ICVC FAULT

PRIMARY

SECONDARY

PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

STATE

MESSAGE

MESSAGE

 

 

120

RUN CAPACITY

HIGH CONDENSER

120Condenser Pressure

Check condenser water pump operation.

 

LIMITED

PRESSURE

[VALUE] exceeded limit of

Check for high condenser water temperatures or

 

 

 

[LIMIT]*.

low flow rate. Verify that isolation valves are

 

 

 

 

open.

 

 

 

 

Check Cond Press Override setting in SETUP1.

121

RUN CAPACITY

HIGH MOTOR

121Comp Motor Winding

Check for closed valves or restriction in motor

 

LIMITED

TEMPERATURE

Temp [VALUE] exceeded

cooling lines.

 

 

 

limit of [LIMIT]*.

Check for closed refrigerant isolation valves.

 

 

 

 

Check Comp Motor Temp Override setting in

 

 

 

 

SETUP1.

122

RUN CAPACITY

LOW EVAP REFRIG

122Evaporator Refrig

Check refrigerant charge.

 

LIMITED

TEMP

Temp [VALUE] exceeded

Check that optional cooler liquid line isolation

 

 

 

limit of [LIMIT]*.

valve is fully open.

 

 

 

 

Check for excessive condenser flow or low

 

 

 

 

chilled water flow.

 

 

 

 

Check for low entering cooler temperature.

 

 

 

 

Check that condenser inlet and outlet water

 

 

 

 

nozzles are piped correctly.

 

 

 

 

Check for waterbox division plate gasket bypass.

123

RUN CAPACITY

HIGH COMPRESSOR

123Surge Prevention

Check for high condenser water temperature or

 

LIMITED

LIFT

Override: Lift Too High For

low suction temperature.

 

 

 

Compressor

Check for high Evaporator or Condenser

 

 

 

 

approaches.

 

 

 

 

Check surge prevention parameters in

 

 

 

 

OPTIONS screen.

124

RUN CAPACITY

MANUAL GUIDE VANE

124Run Capacity Limited:

Target Guide Vane Position has been forced in

 

LIMITED

TARGET

Manual Guide Vane Target.

the COMPRESS screen. Select and RELEASE

 

 

 

 

force to return to normal (automatic) operation.

125

RUN CAPACITY

LOW DISCHARGE

No Alert message.

Check for oil loss or excess refrigerant charge.

 

LIMITED

SUPERHEAT

 

Verify that the valves in the oil reclaim lines are

 

 

 

 

open.

126

RUN CAPACITY

HIGH RECTIFIER TEMP

126Rectifier Temperature

Check Rectifier Temp Override in SETUP1

 

LIMITED

 

[VALUE] exceeded limit of

screen.

 

 

 

[LIMIT]*.

Check that VFD refrigerant isolation valves are

 

 

 

 

open.

 

 

 

 

Check VFD refrigerant cooling solenoid.

 

 

 

 

Check for proper VFD cooling fan operation and

 

 

 

 

blockage.

127

RUN CAPACITY

MANUAL SPEED

No Alert message.

Chiller is not in automatic temperature control.

 

LIMITED

CONTROL

 

 

128

RUN CAPACITY

HIGH INVERTER TEMP

128Inverter Temperature

Check Inverter Temp Override in SETUP1

 

LIMITED

 

[VALUE] exceeded limit of

screen.

 

 

 

[LIMIT]*.

Check that VFD refrigerant isolation valves are

 

 

 

 

open.

 

 

 

 

Check VFD refrigerant cooling solenoid.

 

 

 

 

Check for proper VFD cooling fan operation and

 

 

 

 

blockage.

*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.

12

Image 12 Contents
Start-Up and Service Instructions Contents A19-1831 A19-1842A19-1814 A19 1832A19-1833 Wire Lugs A19-1834VFD Configurations Parameter Default ValueA19 1846 A19-1921 TB1 I/O Terminal DesignationsA19-1835 A19-18361815 Drive Status Indicator Descriptions Name Color State DescriptionEnet LinkA19-1844 A19-1925Icvc Alert Codes MessagePrestart AlertRUN Capacity LimitedFault Primary Secondary Primary Cause Additional CAUSE/REMEDYSensor Alert LOW OILLoss CommunicationVFD Speed Alert System AlertIcvc Alarm Codes Failure to StopProtective Limit 233 234235 236Unused Unused StateSensor Fault VFD GatewayFault Type Description Corrective Action On VFD VFDCode Hist Screen NoneHist Screen None113 124Diode Checks Meter Lead Meter ReadingA19-1831Fig Open Access Door Frames 6 and 7 Power Terminal BlockA19-1814Fig Check DC Bus Terminals A19-1816Fig Removing EnclosureA19-1837 A19-1838A19-1817A19-1818 Comm Card A19-1819A19-1847 CR1 EA1 Line CR6 CB1 TB4CB2 FU1-FU3 PT1 Secondary Side Toward Door TB4 Dist SideA19-1848 Frame 6 PartsAppendix a Wiring Schematics Chiller Control Schematic A19-1946A19-1947 HgbpRHS UPCA19-1966 A19-1967 ShldA48-8578 A48-8579Appendix B Optional Bacnet Communications Wiring Table a SW3 Protocol Switch Settings For MS/TPTable B Baud Selection Table A48 8580Table C MS/TP Wiring Recommendations A48-8582Wiring Specifications Recommended Vendors and Part Numbers RmcorpCMP Table E LED Status Indicators RUN LED Error LED StatusLED Status RunObject ID Object Name CHW Page Copyright 2011 Carrier Corporation