Table 4 — ICVC Alert Codes (cont)
NORMAL RUN WITH OVERRIDES
ICVC FAULT | PRIMARY | SECONDARY | PRIMARY CAUSE | ADDITIONAL CAUSE/REMEDY | |
STATE | MESSAGE | MESSAGE | |||
|
| ||||
120 | RUN CAPACITY | HIGH CONDENSER | 120→Condenser Pressure | Check condenser water pump operation. | |
| LIMITED | PRESSURE | [VALUE] exceeded limit of | Check for high condenser water temperatures or | |
|
|
| [LIMIT]*. | low flow rate. Verify that isolation valves are | |
|
|
|
| open. | |
|
|
|
| Check Cond Press Override setting in SETUP1. | |
121 | RUN CAPACITY | HIGH MOTOR | 121→Comp Motor Winding | Check for closed valves or restriction in motor | |
| LIMITED | TEMPERATURE | Temp [VALUE] exceeded | cooling lines. | |
|
|
| limit of [LIMIT]*. | Check for closed refrigerant isolation valves. | |
|
|
|
| Check Comp Motor Temp Override setting in | |
|
|
|
| SETUP1. | |
122 | RUN CAPACITY | LOW EVAP REFRIG | 122→Evaporator Refrig | Check refrigerant charge. | |
| LIMITED | TEMP | Temp [VALUE] exceeded | Check that optional cooler liquid line isolation | |
|
|
| limit of [LIMIT]*. | valve is fully open. | |
|
|
|
| Check for excessive condenser flow or low | |
|
|
|
| chilled water flow. | |
|
|
|
| Check for low entering cooler temperature. | |
|
|
|
| Check that condenser inlet and outlet water | |
|
|
|
| nozzles are piped correctly. | |
|
|
|
| Check for waterbox division plate gasket bypass. | |
123 | RUN CAPACITY | HIGH COMPRESSOR | 123→Surge Prevention | Check for high condenser water temperature or | |
| LIMITED | LIFT | Override: Lift Too High For | low suction temperature. | |
|
|
| Compressor | Check for high Evaporator or Condenser | |
|
|
|
| approaches. | |
|
|
|
| Check surge prevention parameters in | |
|
|
|
| OPTIONS screen. | |
124 | RUN CAPACITY | MANUAL GUIDE VANE | 124→Run Capacity Limited: | Target Guide Vane Position has been forced in | |
| LIMITED | TARGET | Manual Guide Vane Target. | the COMPRESS screen. Select and RELEASE | |
|
|
|
| force to return to normal (automatic) operation. | |
125 | RUN CAPACITY | LOW DISCHARGE | No Alert message. | Check for oil loss or excess refrigerant charge. | |
| LIMITED | SUPERHEAT |
| Verify that the valves in the oil reclaim lines are | |
|
|
|
| open. | |
126 | RUN CAPACITY | HIGH RECTIFIER TEMP | 126→Rectifier Temperature | Check Rectifier Temp Override in SETUP1 | |
| LIMITED |
| [VALUE] exceeded limit of | screen. | |
|
|
| [LIMIT]*. | Check that VFD refrigerant isolation valves are | |
|
|
|
| open. | |
|
|
|
| Check VFD refrigerant cooling solenoid. | |
|
|
|
| Check for proper VFD cooling fan operation and | |
|
|
|
| blockage. | |
127 | RUN CAPACITY | MANUAL SPEED | No Alert message. | Chiller is not in automatic temperature control. | |
| LIMITED | CONTROL |
|
| |
128 | RUN CAPACITY | HIGH INVERTER TEMP | 128→Inverter Temperature | Check Inverter Temp Override in SETUP1 | |
| LIMITED |
| [VALUE] exceeded limit of | screen. | |
|
|
| [LIMIT]*. | Check that VFD refrigerant isolation valves are | |
|
|
|
| open. | |
|
|
|
| Check VFD refrigerant cooling solenoid. | |
|
|
|
| Check for proper VFD cooling fan operation and | |
|
|
|
| blockage. |
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.