Carrier 19XRV specifications Loss, Communication, VFD Speed Alert, System Alert

Page 14

Table 4 — ICVC Alert Codes (cont)

CHILLER ALERTS (cont)

ICVC FAULT

PRIMARY

SECONDARY

PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

STATE

MESSAGE

MESSAGE

 

 

159

SENSOR ALERT

SPARE TEMPERATURE

159Spare Temperature 2

Check sensor resistance or voltage drop.

 

 

#2

[VALUE] exceeded limit of

Check for proper wiring to CCM connector J4.

 

 

 

[LIMIT]*.

Check Spare Temp #2 Limit in SETUP1 screen.

161

LOSS OF

WITH WSM

161WSM Cool Source —

Check settings in WSMDEFME screen.

 

COMMUNICATION

 

Loss of Communication.

Check CCN communications link with WSM

 

 

 

 

(Water System Manager) Module.

 

 

 

 

Check Supervisory Part of WSM.

162

SENSOR ALERT

EVAPORATOR

162Evaporator Approach

Check that refrigerant charge level is adequate,

 

 

APPROACH

[VALUE] Exceeded Limit of

waterbox division plate gaskets are sealing,

 

 

 

[LIMIT]*.

evaporator tubes are not fouled and that oil

 

 

 

 

reclaim system is working.

 

 

 

 

Check sensor resistance or voltage drop.

 

 

 

 

Check for proper wiring.

 

 

 

 

Check Evap Approach Alert setting in SETUP1

 

 

 

 

screen.

163

SENSOR ALERT

CONDENSER APPROACH

163Condenser Approach

Check sensors resistance or voltage drop.

 

 

 

[VALUE] Exceeded Limit of

Check for proper wiring.

 

 

 

[LIMIT]*.

Check Cond Approach Alert setting in SETUP1

 

 

 

 

screen.

 

 

 

 

Check for noncondensable gas in the

 

 

 

 

condenser.

 

 

 

 

Check that the condenser tubes are not fouled.

164

VFD SPEED ALERT

LOW VFD SPEED

164Actual VFD Speed

Actual VFD Speed on COMPRESS screen must

 

 

 

exceeded limit of Target VFD

be at least 90% of Target VFD Speed.

 

 

 

Speed –10%.

 

165

AUTORESTART

LOW DC BUS VOLTAGE

165Low DC Bus Voltage:

Verify phase to phase and phase to ground line

 

PENDING

 

[VALUE] Exceeded Limit of

voltage.

 

 

 

[LIMIT]*.

 

166

AUTORESTART

HIGH DC BUS VOLTAGE

166High DC Bus Voltage:

Verify phase to phase and phase to ground line

 

PENDING

 

[VALUE] Exceeded Limit of

voltage. Monitor AC line for high transient volt-

 

 

 

[LIMIT]*.

age conditions.

167

SYSTEM ALERT

HIGH DISCHARGE TEMP

167Comp Discharge Temp

Check sensor resistance or voltage drop.

 

 

 

[VALUE] exceeded limit of

Check for proper wiring.

 

 

 

[LIMIT]*.

Check for excessive starts.

 

 

 

 

Check Comp Discharge Alert setting in SETUP1

 

 

 

 

screen.

168

SENSOR ALERT

HUMIDITY SENSOR

168Sensor Fault: Check

Check humidity sensor wiring on CCM connec-

 

 

INPUT

Humidity Sensor Input Sensor.

tors J3 and J5. CCM switch SW2-1 must be in

 

 

 

 

“OFF” position.

 

 

 

 

Check Humidity Sensor Input in Controls Test.

*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.

14

Image 14
Contents Start-Up and Service Instructions Contents A19-1814 A19-1831A19-1842 A19-1833 A191832 Wire Lugs A19-1834A19 1846 VFD ConfigurationsParameter Default Value A19-1921 TB1 I/O Terminal Designations1815 A19-1835A19-1836 Enet Drive Status Indicator DescriptionsName Color State Description LinkA19-1844 A19-1925Prestart Icvc Alert CodesMessage AlertRUN Capacity LimitedSensor Alert FaultPrimary Secondary Primary Cause Additional CAUSE/REMEDY LOW OILVFD Speed Alert LossCommunication System AlertIcvc Alarm Codes Failure to StopProtective Limit 235 233234 236Unused Unused StateSensor Fault VFD GatewayCode Fault Type Description Corrective Action On VFDVFD Hist Screen None113 Hist ScreenNone 124Diode Checks Meter Lead Meter ReadingA19-1814Fig Check DC Bus Terminals A19-1831Fig Open Access DoorFrames 6 and 7 Power Terminal Block A19-1816Fig Removing EnclosureA19-1817A19-1818 A19-1837A19-1838 Comm Card A19-1819CB2 FU1-FU3 PT1 Secondary Side Toward Door A19-1847CR1 EA1 Line CR6 CB1 TB4 TB4 Dist SideA19-1848 Frame 6 PartsAppendix a Wiring Schematics Chiller Control Schematic A19-1946RHS A19-1947Hgbp UPCA19-1966 A19-1967 ShldA48-8578 A48-8579Table B Baud Selection Table Appendix B Optional Bacnet Communications WiringTable a SW3 Protocol Switch Settings For MS/TP A48 8580Table C MS/TP Wiring Recommendations A48-8582CMP Wiring Specifications Recommended Vendors and Part NumbersRmcorp LED Status Table E LED Status IndicatorsRUN LED Error LED Status RunObject ID Object Name CHW Page Copyright 2011 Carrier Corporation

19XRV specifications

The Carrier 19XRV is a cutting-edge rooftop chiller designed to provide reliable and efficient cooling solutions for a wide range of applications, including commercial buildings and industrial facilities. This advanced system integrates the latest technologies and innovative features to ensure optimal performance, energy efficiency, and ease of use.

One of the most prominent features of the 19XRV is its advanced inverter-driven compressor technology. This allows the chiller to adjust its capacity seamlessly based on the building's cooling demand. By varying the speed of the compressor, the 19XRV maximizes energy efficiency and minimizes operational costs, especially during partial load conditions. This capability not only enhances comfort but also contributes to reduced energy consumption, making it a sustainable choice for environmentally conscious users.

In addition to the inverter technology, the 19XRV incorporates a microchannel coil design. This design optimizes heat exchange efficiency and reduces the refrigerant charge, which is an essential factor in lowering greenhouse gas emissions. The microchannel coils also allow for more compact dimensions, making installation easier and maximizing rooftop space usage.

Another significant aspect of the Carrier 19XRV is its robust controls system. Equipped with Carrier’s advanced ComfortLink™ controls, this chiller offers precise monitoring and control over its operation. Users can easily integrate the chiller into building management systems for real-time data access and efficiency analytics. This connectivity ensures that operators can make informed decisions to optimize performance continuously.

The 19XRV also includes features aimed at enhancing reliability and durability. Its structural design incorporates corrosion-resistant materials, allowing the unit to withstand harsh environmental conditions. This reliability translates to lower maintenance requirements and extended equipment lifespan, providing excellent value over time.

Moreover, the chiller is designed for quiet operation, making it suitable for applications where low noise levels are essential. Sound-dampening measures ensure that the 19XRV can be utilized in urban environments or near sensitive areas without causing disturbances.

In conclusion, the Carrier 19XRV is a state-of-the-art rooftop chiller that combines efficiency, technology, and durability. Its inverter-driven compressor, microchannel coil design, advanced controls, and robust construction make it an ideal choice for those looking to maintain comfort while minimizing energy usage and environmental impact. Whether for commercial or industrial applications, the 19XRV stands out as a reliable and innovative cooling solution for the modern age.