Carrier 19XRV specifications Comm Card, A19-1819

Page 25

0.45-0.67 N-m

(4.0-6.0 lb.-in.)

3 PLACES

GATEWAY

MOUNTING PLATE

RIBBON CABLE

CHILL PLATE FAN AND INTERNAL FAN REPLACE- MENT — The following are the steps to replace the chill plate fan and internal fan in Frames 6 and 7.

Frame 6:

1.Disconnect power to the drive. Before removing the en- closure, open the access door on the front of the drive. See Fig. 16.

2.Check to be sure that the voltage between DC+ and DC- and from each DC terminal to the chassis is zero before proceeding. See Fig. 17.

3.Remove the enclosure. See Fig. 18.

4.Remove and replace the chill plate fan. See Fig. 23.

5.Remove and replace the internal fan. See Fig. 24.

6.Install the enclosure. See Fig. 18.

CHILL PLATE

FAN POWER

CONNECTION

Fig. 21 — COMM Card

A19-1819

CHILL PLATE FAN

MOUNTING PLATE

GATEWAY

Fig. 22 — Mount COMM Card Plate to Drive A19-1820

T20

2.6 N•m (23 lb•in.)

Fig. 23 — Chill Plate Fan, Frame 6

A19-1839

2.6 N•m

(23 lb•in.) T20

INTERNAL FAN

T20

2.6 N•m

(23 lb•in.)

A19-1840

Fig. 24 — Internal Fan, Frame 6

25

711

Image 25 Contents
Start-Up and Service Instructions Contents A19-1842 A19-1831A19-1814 1832 A19A19-1833 A19-1834 Wire LugsParameter Default Value VFD ConfigurationsA19 1846 TB1 I/O Terminal Designations A19-1921A19-1836 A19-18351815 Name Color State Description Drive Status Indicator DescriptionsEnet LinkA19-1925 A19-1844Message Icvc Alert CodesPrestart AlertLimited RUN CapacityPrimary Secondary Primary Cause Additional CAUSE/REMEDY FaultSensor Alert LOW OILCommunication LossVFD Speed Alert System AlertFailure to Stop Icvc Alarm CodesProtective Limit 234 233235 236Unused State UnusedVFD Gateway Sensor FaultVFD Fault Type Description Corrective Action On VFDCode Hist Screen NoneNone Hist Screen113 124Meter Lead Meter Reading Diode ChecksFrames 6 and 7 Power Terminal Block A19-1831Fig Open Access DoorA19-1814Fig Check DC Bus Terminals A19-1816Fig Removing EnclosureA19-1838 A19-1837A19-1817A19-1818 A19-1819 Comm CardCR1 EA1 Line CR6 CB1 TB4 A19-1847CB2 FU1-FU3 PT1 Secondary Side Toward Door TB4 Dist SideFrame 6 Parts A19-1848A19-1946 Appendix a Wiring Schematics Chiller Control SchematicHgbp A19-1947RHS UPCA19-1966 Shld A19-1967A48-8579 A48-8578Table a SW3 Protocol Switch Settings For MS/TP Appendix B Optional Bacnet Communications WiringTable B Baud Selection Table A48 8580A48-8582 Table C MS/TP Wiring RecommendationsRmcorp Wiring Specifications Recommended Vendors and Part NumbersCMP RUN LED Error LED Status Table E LED Status IndicatorsLED Status RunObject ID Object Name CHW Page Copyright 2011 Carrier Corporation