Carrier Understanding Alarm Codes for Air Conditioners

Page 16

Table 5 — ICVC Alarm Codes (cont)

CHILLER PROTECTIVE LIMIT FAULTS (cont)

ICVC FAULT

PRIMARY

SECONDARY

PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

STATE

MESSAGE

MESSAGE

 

 

220

PROTECTIVE LIMIT

GROUND FAULT

220Ground Fault Trip;

Check for condensation on motor terminals.

 

 

 

Check Motor and Current

Check motor power leads for phase to phase or

 

 

 

Sensors.

phase to ground shorts. Disconnect motor from

 

 

 

 

VFD and megger motor.

 

 

 

 

Call Carrier Service.

221

PROTECTIVE LIMIT

UNUSED

221UNUSED

 

222

PROTECTIVE LIMIT

LINE FREQUENCY TRIP

222Line Frequency —

If operating from a generator, check generator

 

 

 

[VALUE] exceeded limit of

size and speed.

 

 

 

[LIMIT]; Check Power Supply.

Check utility power supply.

223

LOSS OF

WITH VFD GATEWAY

223Loss of SIO Comm with

Check VFD communication wiring and

 

COMMUNICATION

MODULE

VFD Gateway: Check VFG

connectors on VFD Gateway and DPI board.

 

 

 

Module and Power.

Check for compatibility between ICVC and

 

 

 

 

Gateway software.

224

PROTECTIVE LIMIT

VFD COMMUNICATIONS

224Loss of DPI Comm with

Check VFD communication wiring and

 

 

FAULT

VFD Gateway: Check VFG to

connectors.

 

 

 

VFD Comm.

Check status lights on DPI Communications

 

 

 

 

Interface Board.

 

 

 

 

Call Carrier Service.

225

PROTECTIVE LIMIT

MOTOR CURRENT

225Motor Current Imbal-

Check Motor Current % Imbalance in

 

 

IMBALANCE

ance: Check VFD Fault

VFD_CONF screen.

 

 

 

History for Values.

 

226

PROTECTIVE LIMIT

LINE PHASE REVERSAL

226Line Phase Reversal:

Reverse connections of any two line conductors

 

 

 

Check Line Phases.

to circuit breaker.

227

PROTECTIVE LIMIT

OIL PRESS SENSOR

227Oil Pressure Delta P

Check transducer wiring and accuracy.

 

 

FAULT

[VALUE] (Pump Off): Check

Check power supply to pump.

 

 

 

Pump/Transducers.

Check pump operation.

 

 

 

 

Check transducer calibration.

228

PROTECTIVE LIMIT

LOW OIL PRESSURE

228Low Operating Oil

Check transducer wiring and accuracy.

 

 

 

Pressure [VALUE]: Check Oil

Check power supply to pump.

 

 

 

Pump and Filter.

Check pump operation.

 

 

 

 

Check oil level.

 

 

 

 

Check for partially closed service valves.

 

 

 

 

Check oil filters.

 

 

 

 

Check for foaming oil at start-up.

 

 

 

 

Check transducer calibration.

229

PROTECTIVE LIMIT

LOW CHILLED WATER

229Low Chilled Water Flow;

Perform pump control test.

 

 

FLOW

Check Switch/Delta P Config

Check optional transducer calibration and

 

 

 

& Calibration.

wiring.

 

 

 

 

Check Evaporator Refrigerant Temperature

 

 

 

 

sensor.

 

 

 

 

Check chilled water valves.

 

 

 

 

Check for evaporator saturation temperature

 

 

 

 

< 34 F if not in Pumpdown Lockout mode. Place

 

 

 

 

unit in Pumpdown mode before removing

 

 

 

 

charge.

230

PROTECTIVE LIMIT

LOW CONDENSER

230Low Condenser Water

Perform pump control test.

 

 

WATER FLOW

Flow; Check Switch/Delta P

Check optional transducer calibration and

 

 

 

Config & Calibration.

wiring.

 

 

 

 

Check condenser water valves.

 

 

 

 

Check for COND PRESS OVERRIDE + 5 psig.

231

PROTECTIVE LIMIT

HIGH DISCHARGE TEMP

231Comp Discharge Temp

Check for closed compressor discharge isola-

 

 

 

[VALUE] Exceeded Limit of

tion valve.

 

 

 

[LIMIT]*.

Check if chiller was operating in surge.

 

 

 

 

Check sensor resistance or voltage drop.

 

 

 

 

Check for proper wiring.

 

 

 

 

Check for proper condenser flow and

 

 

 

 

temperature.

 

 

 

 

Check compressor discharge isolation valve.

 

 

 

 

Check for proper inlet guide vane and optional

 

 

 

 

diffuser actuator operation.

232

PROTECTIVE LIMIT

LOW REFRIGERANT

232Evaporator Refrig Temp

Check for proper refrigerant charge.

 

 

TEMP

[VALUE] exceeded limit of

Check float valve operation.

 

 

 

[LIMIT]*.

Check for closed condenser liquid line isolation

 

 

 

 

valve. If problem occurs at high load, check for

 

 

 

 

low condenser pressure which causes inade-

 

 

 

 

quate flasc orifice differential pressure.

 

 

 

 

Check for proper water flow and temperature.

 

 

 

 

Confirm that condenser water enters bottom row

 

 

 

 

of condenser tubes first.

 

 

 

 

Check Evaporator Refrigerant Temperature

 

 

 

 

sensor.

 

 

 

 

Check for division plate gasket bypass.

 

 

 

 

Check for fouled tubes.

*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.

16

Image 16 Contents
Start-Up and Service Instructions Contents A19-1842 A19-1831A19-1814 1832 A19A19-1833 Wire Lugs A19-1834Parameter Default Value VFD ConfigurationsA19 1846 A19-1921 TB1 I/O Terminal DesignationsA19-1836 A19-18351815 Drive Status Indicator Descriptions Name Color State DescriptionEnet LinkA19-1844 A19-1925Icvc Alert Codes MessagePrestart AlertRUN Capacity LimitedFault Primary Secondary Primary Cause Additional CAUSE/REMEDYSensor Alert LOW OILLoss CommunicationVFD Speed Alert System AlertIcvc Alarm Codes Failure to StopProtective Limit 233 234235 236Unused Unused StateSensor Fault VFD GatewayFault Type Description Corrective Action On VFD VFDCode Hist Screen NoneHist Screen None113 124Diode Checks Meter Lead Meter ReadingA19-1831Fig Open Access Door Frames 6 and 7 Power Terminal BlockA19-1814Fig Check DC Bus Terminals A19-1816Fig Removing EnclosureA19-1838 A19-1837A19-1817A19-1818 Comm Card A19-1819A19-1847 CR1 EA1 Line CR6 CB1 TB4CB2 FU1-FU3 PT1 Secondary Side Toward Door TB4 Dist SideA19-1848 Frame 6 PartsAppendix a Wiring Schematics Chiller Control Schematic A19-1946A19-1947 HgbpRHS UPCA19-1966 A19-1967 ShldA48-8578 A48-8579Appendix B Optional Bacnet Communications Wiring Table a SW3 Protocol Switch Settings For MS/TPTable B Baud Selection Table A48 8580Table C MS/TP Wiring Recommendations A48-8582Rmcorp Wiring Specifications Recommended Vendors and Part NumbersCMP Table E LED Status Indicators RUN LED Error LED StatusLED Status RunObject ID Object Name CHW Page Copyright 2011 Carrier Corporation