Configuring Home Direction [ HFi ]

EDIT > SETUP > HOME > DIR

Value: POSITIVE

Range: NEGATIVE, POSITIVE

–Axis One Final Dir–

Positive

Select value, press ENTER

Sets the direction for the Go Home (GH) move. This is the direction used to search for the encoder index mark (Z channel) after the appropriate home switch edge is found.

Configure Power–up Program

The Program Setup menu allows selection of (1) a program to be immediately run when LinStep+ is powered–up and (2) scanning conditions for the BCD or binary program select inputs.

Action

 

 

Display

 

 

Comments

 

 

 

 

 

 

 

Press F1 (PROG) key for more

 

 

 

 

 

Select a sub–menu, press F1 (PROG),

 

SETUP

 

sub menu selections.

 

 

 

 

F2 (RS232), or F3 (MISC).

 

PROG

RS232

MISC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Configuring Power–up Program [ PUi ]

EDIT > SETUP > PROG > PWR–UP

Value: 0

Range: 0–400

Sets the program to run at power–up. The selected program is executed (run) when power is applied or after a reset. If a value of 0 is entered in this menu, or if the specified program does not exist, no program is run. Use numeric keys to enter program number.

Configuring Scan Conditions [ SNaaaaaaaa ]

EDIT > SETUP > PROG > SCAN

Value: YYYYYYY

Range: YYYYYYY, NNNNNNN

– Power Up Program – PROGRAM:0

Select value, press ENTER

– Stop After Scan – ←↑ YYYYYYY ESC ↓→

Select value, press ENTER

Selects the events that cause the control to stop scanning program–select configured inputs. The selected event is listed to the right of these 7 characters: ESCape, STOP, LIMIT+, LIMIT–, KILL, FAULT or INTerrupt.

If a stop–scan event is enabled, the system will stop scanning the inputs for program numbers when that condition occurs. To resume scanning, a reset (Warm Boot input or cycle power Off then On) must be given. This option has no effect if the inputs are not configured as program select inputs (either BCD or Binary).

MN1854

Setup 5-15

Image 52
Contents LinStep+ Dual-Axis Microstepping Indexer/Driver Table of Contents Arithmetic Operands and Equations Other Programming Samples Ii Table of Contents MN1854Increment/Decrement Variables Troubleshooting Serial Communications Problems Iv Table of Contents MN1854 Section General Information Limited WarrantyCE Compliance Product Notice Intended use Could result in injury or deathCould result in damage to property On next 2General Information MN1854Do not touch any circuit board, power device or electrical Connection before you first ensure that power has beenDo not apply AC power before you ensure that grounds are Voltages that are conducted to its power input terminals.Extend more than 0.2 5 into keypad assembly Instead, we recommend using a four wire WyePower is removed from the drive Driver should have specifications compatible to the driveOverview Section Product OverviewMotors Product Overview MN1854 Section Receiving and Installation Power DissipationMechanical Installation Receiving & Inspection2Receiving & Installation MN1854 GNDInput Power Conditioning System Grounding Ungrounded Distribution SystemPower Connections Power connections are shown in Figure Wire Size and Protection Devices4Receiving & Installation MN1854 MN1854 Receiving & Installation Connection Locations 115VAC, 2 Axis6Receiving & Installation MN1854 Tools Required9 & 25 Pin RS-232 Cable Connections for UL Installations RS-232 PC Connections8Receiving & Installation MN1854 Daisy Chain ConnectionsRules for Daisy Chain Operation PC / Host DeviceProgrammable I/O Connections Optional Opto I/O ConnectionsThese input connections are made at terminals 6-40 Figure Typical connection each input10Receiving & Installation MN1854 Encoder Signal PVS100 Danaher 9-Pin DEncoder Color Code +5VDCMotor Connector LD9068A00 Leadwire Connection 9 pin to flying leadsInterlock Intlk Ground GNDStart-Up Procedure Power Off ChecksSwitch and Potentiometer Settings Section General InformationPower On Checks Action Display CommentsMotor should now be producing torque HighReceiving & Installation MN1854 Section Keypad Operation OverviewKeypad layout with the LCD display is shown in Figure F1, F2, F3Copies one program to another within the LinStep+ Comma Decimal PointAlpha Test Thus eliminating the need for a PC terminal connectionTrace Output Move Shutdn RS232 EncoderEdit Menu Pressing the Edit key displays a set of sub-menusSave the program Edit an existing program6Keypad Operation MN1854 Save Program? YesNoNaming a program Example of Naming a ProgramPress ESC. You will be prompted as shown in Figure Mine AC.3 VE2 DI1 GOUse the =O keys for additional alpha characters Entering Characters with the Alpha Key In edit mode8Keypad Operation MN1854 Edit, Setup Submenu Submenu Setup Parameter Description of Setup ParameterPress EDIT, POS F3 Press YES F1 or no F3 Press EDIT, ↓ , List toDisplay the number Programs stored Press ↓ to display the totalPressing Help in the Main Menu Pressing Help in Menus and Sub-MenusPressing Help In the Program Edit function Sequentially Eeprom message disappearsCOPY, to PAD Submenu Enter the program number. Or, ifYou wish, you can scroll the list Program namesSection Setup Procedure Format DefinitionSetup MN1854 Axis One Motor Type SteperAxis One Drive Res Axis One Motor DirAxis One ENC Mode Open LoopApplication Notes Axis One Encoder RES ↑5000 cnts/in ↓IN-RANGE Setup Window ValueIN-RANGE Window PM GainConfigure Your Application Mechanics Mech SetupDist Vmax Accel AmaxAxis One Vel Units In/s EditAxis One MAX Vel 500.0 in/s ↓→Iuuuuuuu ←↑↓→ Configure the I/OChar Keypad Display Input Character Description Inputs will work. See the RG command for more details Service routine programTo summarize, when INT98CTRL=1 Reset to 1. This allows for input debounce and controllingWarm Boot Power-up program, if defined, will startJog Speed InputsOUT1 Programmable Pppppppp ←↑↓→ Configure the Output States OPTO9 InputIiiiiiii OFFConfigure End of Travel Switch Polarity Configure JOG ParametersEnable Accel LO-VEL HI-VELMode Edge Switch Configure Home ParametersOffset DIR Negative Configure Power-up Program ↑SETUP↓Power Up Program PROGRAM0 Axis One Final Dir PositiveConfigure Serial Communications RS232C Setup↑ Enabled ↓ Echo UNIT#Configure Miscellaneous Setup Parameters Data Type Description of Display Data TypeGeneral Password Rules Password SetupOpratr Admin Clear Password Type Description Gives access to these menusKeypad Program Command List Section Keypad ProgrammingAcceleration Start Home Outputs On/Off Function Key Message to DisplayKeypad Programming MN1854 Value Units RangeExample AC2 DE.5 VE12 DA3 GO DA3 GO DA3 GODC Distance to Change Example Distance to Change DCn * DCn*1 * Vn*1 2* Vnt wExamples of DC move profiles, AC = seconds, VE=ips DC n + 10 +DE Deceleration AC.1 VE60 DI2 GO DI1 GO DI-4 GOLP2 DI3 GO EB Value Units Range N/AIF2,1 EN EB DI2 GO =12 =13 =17 =18 =22 =23 =26 =27 =28RUN Edit Copy DELExample 3-Screen Menu Program Set in Edit Setup Mech Accel VEL GH Start HomeGo Immediate Syntax GI or GIi Value N/A Units N/A Range N/AGO Go Start a Move Syntax GO or GOi Value N/A Units N/A Range i=1-16AC.05 DE.05 VE50 DI5 GO VE2 AC.1 DA4,2 GPGosub Syntax GSi and GSname =1-400, name = any legal program nameIF10 Gtpart a EB If input 1 is on and input 2 is off, jump to program Part aUnits Range IFPARTS=25 GS20 EBLppieces IV12,LENGTHDilength Syntax LPi LP Loop Value Units N/A Range N/ASyntax MC+ MC Move Continuous Move Continuous MS27,COUNT 27 7th character, 2nd rowPowerup ONL,GTON EOT GthomeMain VE5 DA20 GO= starting output number =0 input high. X=1 input low grounded=anything else ignore input changes OT4,1 Turn on Output OT2,0D1Syntax RGr RG Registration SQRESULT=0 SQ27.96,SQRESULT Value N/A Units N/AST1 AC1 DE1 VE25 DA6 GO VE50 DA0 GO EN Value N/A Units secondsWTexpression Syntax VEr VE Velocity= starting input number Helpful Hints Programming your application Summary of Expressions, Operators and FunctionsProgramming Overview Program Example of Hosted ModeVariable Names Built-in Variables Examples of how to use Built-in VariablesVariable Name Description of Built-in Variable Type Using Built-in Variable Arowrel Parts Non-Volatile VariablesLpnumber AO15=VOLTAGE + Error Arithmetic Operands and EquationsExamples of incorrect use Instead, you should useLogical Operators Increment/Decrement VariablesExpressions Other Programming SamplesCreate a Message and Read an Input Variable Setting an Output=On on-the-flyCreate a Menu menu display on keypad display for operator Read a 4 Digit BCD number, 2 Digits at a time Reading an Analog Input ValueGET 4 Bcds Digit BCD=4 Digit BCD+2TWSection Troubleshooting 1Operation Indicators2Axis 1 and 2 Indicators Additional Information GeneralTroubleshooting MN1854 Additional InformationSerial Communications Problems Troubleshooting MN1854 Section Specifications & Product Data MN1854 Specifications & Product DataIdentification LinStep+ LX 2 P 1 aGeneral Specifications Protection & Indicators DescriptionVAC VDCOptional Keypad 10.08 256.0 Axis Driver 148.3 Dimensions94.7 230.1 Specifications & Product Data MN1854 Wiring of Shielded Screened Cables Section CE GuidelinesCE Declaration of Conformity EMC Conformity and CE MarkingEMC Wiring Technique CE Guidelines MN1854Cit Grounding EarthEMC Installation Instructions Cable Screens GroundingInput Signal Cable Grounding Simulated Encoder Output Cable GroundingEncoder Cable Grounding To ControllerProgramming Template Appendix aMN1854 Appendix A-1 Appendix MN1854 MN1854 Appendix A-3 Remote Keypad Mounting Template 122.88838 111.25Baldor Electric Company Baldor Electric Company MN1854 01 C&JLinStep+ Dual-Axis Microstepping Indexer/Driver