Baldor mn1854 manual Configure Serial Communications, RS232C Setup, Echo UNIT#, ↑ Enabled ↓

Page 53

Configuring Scan Delay [ DYi ]

EDIT > SETUP > PROG > DELAY

Value: 100

Range: 0–99,999

– Scan Debounce – DELAY (ms):100

Select value, press ENTER

Sets the amount of time required for the program select inputs (BCD or Binary) to remain stable before they are valid. The minimum time is 2 ms. If program select inputs are not stable for a time equal to or greater than the specified delay, the program will not be executed. Use the numeric keys to enter a value in ms. Note: See Data Valid Input Configuration for an alternate approach.

Configure Serial Communications

To use the LinStep+ serial port, several things must be done first. Use the keypad to set the auto–echo and the unit’s daisy chain address. The baud rate and other parameters have fixed values and may not be changed.

SBaud rate: 9600

SData bits: 8

SStop bits: 1

SParity: none

Action

 

 

 

Display

Comments

 

 

 

 

 

 

 

 

 

 

 

 

 

Select a sub–menu, press F1 (ECHO),

 

 

 

–RS232C SETUP–

 

 

 

 

 

F2 (UNIT#).

 

 

 

ECHO

UNIT#

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Configuring Echo Enable

[ ECi ]

 

 

 

EDIT > SETUP > RS232 > ECHO

Value: Enabled

Range: Enabled, Disabled

Enable or disable the RS–232C ECHO feature. If ECHO is disabled, characters received by the control’s serial port will not be re–transmitted. ECHO must be enabled in daisy–chain applications.

Configuring Unit Number [ UNi ]

EDIT > SETUP > RS232 > UNIT#

Value: 1

Range: 1–99

– RS232C ECHO –

ENABLED

Select value, press ENTER

Unit Number NUMBER:1

Select value, press ENTER

Set the unit’s address. Each unit in an RS–232C serial daisy chain of multiple units must have a unique Unit Number.

5-16 Setup

MN1854

Image 53
Contents LinStep+ Dual-Axis Microstepping Indexer/Driver Table of Contents Increment/Decrement Variables Other Programming Samples Ii Table of Contents MN1854Arithmetic Operands and Equations Troubleshooting Serial Communications Problems Iv Table of Contents MN1854 CE Compliance Limited WarrantySection General Information Could result in injury or death Product Notice Intended useCould result in damage to property On next 2General Information MN1854Connection before you first ensure that power has been Do not touch any circuit board, power device or electricalDo not apply AC power before you ensure that grounds are Voltages that are conducted to its power input terminals.Instead, we recommend using a four wire Wye Extend more than 0.2 5 into keypad assemblyPower is removed from the drive Driver should have specifications compatible to the driveMotors Section Product OverviewOverview Product Overview MN1854 Power Dissipation Section Receiving and InstallationMechanical Installation Receiving & InspectionGND 2Receiving & Installation MN1854System Grounding Ungrounded Distribution System Input Power Conditioning4Receiving & Installation MN1854 Wire Size and Protection DevicesPower Connections Power connections are shown in Figure Connection Locations 115VAC, 2 Axis MN1854 Receiving & InstallationTools Required 6Receiving & Installation MN1854RS-232 PC Connections 9 & 25 Pin RS-232 Cable Connections for UL InstallationsDaisy Chain Connections 8Receiving & Installation MN1854Rules for Daisy Chain Operation PC / Host DeviceOptional Opto I/O Connections Programmable I/O ConnectionsThese input connections are made at terminals 6-40 Figure Typical connection each inputEncoder Signal PVS100 Danaher 9-Pin D 10Receiving & Installation MN1854Encoder Color Code +5VDCLD9068A00 Leadwire Connection 9 pin to flying leads Motor ConnectorInterlock Intlk Ground GNDPower Off Checks Start-Up ProcedureSwitch and Potentiometer Settings Section General InformationAction Display Comments Power On ChecksMotor should now be producing torque HighReceiving & Installation MN1854 Overview Section Keypad OperationKeypad layout with the LCD display is shown in Figure F1, F2, F3Copies one program to another within the LinStep+ Alpha Decimal PointComma Thus eliminating the need for a PC terminal connection TestTrace Output Move Shutdn RS232 EncoderPressing the Edit key displays a set of sub-menus Edit MenuEdit an existing program Save the program6Keypad Operation MN1854 Save Program? YesNoExample of Naming a Program Naming a programPress ESC. You will be prompted as shown in Figure Mine AC.3 VE2 DI1 GO8Keypad Operation MN1854 Entering Characters with the Alpha Key In edit modeUse the =O keys for additional alpha characters Submenu Setup Parameter Description of Setup Parameter Edit, Setup SubmenuPress EDIT, ↓ , List to Press EDIT, POS F3 Press YES F1 or no F3Display the number Programs stored Press ↓ to display the totalPressing Help in Menus and Sub-Menus Pressing Help in the Main MenuPressing Help In the Program Edit function Sequentially Eeprom message disappearsEnter the program number. Or, if COPY, to PAD SubmenuYou wish, you can scroll the list Program namesProcedure Format Definition Section SetupAxis One Motor Type Steper Setup MN1854Axis One Drive Res Axis One Motor DirOpen Loop Axis One ENC ModeApplication Notes Axis One Encoder RES ↑5000 cnts/in ↓Value IN-RANGE Setup WindowIN-RANGE Window PM GainMech Setup Configure Your Application MechanicsDist Vmax Accel AmaxEdit Axis One Vel Units In/sAxis One MAX Vel 500.0 in/s ↓→Char Keypad Display Input Character Description Configure the I/OIuuuuuuu ←↑↓→ Service routine program Inputs will work. See the RG command for more detailsTo summarize, when INT98CTRL=1 Reset to 1. This allows for input debounce and controllingPower-up program, if defined, will start Warm BootJog Speed InputsOUT1 Programmable Pppppppp ←↑↓→ OPTO9 Input Configure the Output StatesIiiiiiii OFFConfigure JOG Parameters Configure End of Travel Switch PolarityEnable Accel LO-VEL HI-VELOffset DIR Configure Home ParametersMode Edge Switch Negative ↑SETUP↓ Configure Power-up ProgramPower Up Program PROGRAM0 Axis One Final Dir PositiveRS232C Setup Configure Serial Communications↑ Enabled ↓ Echo UNIT#Data Type Description of Display Data Type Configure Miscellaneous Setup ParametersPassword Setup General Password RulesOpratr Admin Clear Password Type Description Gives access to these menusSection Keypad Programming Keypad Program Command ListAcceleration Start Home Outputs On/Off Function Key Message to DisplayValue Units Range Keypad Programming MN1854Example AC2 DE.5 VE12 DA3 GO DA3 GO DA3 GODC Distance to Change DCn * DCn*1 * Vn*1 2* Vnt w Example Distance to ChangeExamples of DC move profiles, AC = seconds, VE=ips DC n + 10 +AC.1 VE60 DI2 GO DI1 GO DI-4 GO DE DecelerationIF2,1 EN EB DI2 GO Value Units Range N/ALP2 DI3 GO EB =26 =27 =28 =12 =13 =17 =18 =22 =23RUN Edit Copy DELExample 3-Screen Menu Program GH Start Home Set in Edit Setup Mech Accel VELValue N/A Units N/A Range N/A Go Immediate Syntax GI or GIiValue N/A Units N/A Range i=1-16 GO Go Start a Move Syntax GO or GOiAC.05 DE.05 VE50 DI5 GO VE2 AC.1 DA4,2 GP=1-400, name = any legal program name Gosub Syntax GSi and GSnameIF10 Gtpart a EB If input 1 is on and input 2 is off, jump to program Part aIFPARTS=25 GS20 EB Units RangeDilength IV12,LENGTHLppieces Value Units N/A Range N/A Syntax LPi LP LoopSyntax MC+ MC Move Continuous Move Continuous 27 7th character, 2nd row MS27,COUNTGthome Powerup ONL,GTON EOTMain VE5 DA20 GO=0 input high. X=1 input low grounded = starting output number=anything else ignore input changes OT4,1 Turn on Output OT2,0D1Syntax RGr RG Registration Value N/A Units N/A SQRESULT=0 SQ27.96,SQRESULTST1 AC1 DE1 VE25 DA6 GO VE50 DA0 GO EN Value N/A Units seconds= starting input number Syntax VEr VE VelocityWTexpression Programming Overview Summary of Expressions, Operators and FunctionsHelpful Hints Programming your application Variable Names Example of Hosted ModeProgram Variable Name Description of Built-in Variable Type Examples of how to use Built-in VariablesBuilt-in Variables Using Built-in Variable Arowrel Lpnumber Non-Volatile VariablesParts Arithmetic Operands and Equations AO15=VOLTAGE + ErrorExamples of incorrect use Instead, you should useIncrement/Decrement Variables Logical OperatorsExpressions Other Programming SamplesCreate a Menu menu display on keypad display for operator Setting an Output=On on-the-flyCreate a Message and Read an Input Variable Reading an Analog Input Value Read a 4 Digit BCD number, 2 Digits at a timeGET 4 Bcds Digit BCD=4 Digit BCD+2TW1Operation Indicators Section Troubleshooting2Axis 1 and 2 Indicators Additional Information GeneralAdditional Information Troubleshooting MN1854Serial Communications Problems Troubleshooting MN1854 MN1854 Specifications & Product Data Section Specifications & Product DataIdentification LinStep+ LX 2 P 1 aProtection & Indicators Description General SpecificationsVAC VDC94.7 230.1 DimensionsOptional Keypad 10.08 256.0 Axis Driver 148.3 Specifications & Product Data MN1854 Section CE Guidelines Wiring of Shielded Screened CablesCE Declaration of Conformity EMC Conformity and CE MarkingCE Guidelines MN1854 EMC Wiring TechniqueCit Grounding EarthCable Screens Grounding EMC Installation InstructionsSimulated Encoder Output Cable Grounding Input Signal Cable GroundingEncoder Cable Grounding To ControllerMN1854 Appendix A-1 Appendix aProgramming Template Appendix MN1854 MN1854 Appendix A-3 122.88 Remote Keypad Mounting Template838 111.25Baldor Electric Company MN1854 01 C&J Baldor Electric CompanyLinStep+ Dual-Axis Microstepping Indexer/Driver