Baldor mn1854 Section Troubleshooting, Additional Information General, 1Operation Indicators

Page 88

Section 7

Troubleshooting

Overview

The system troubleshooting procedures involve observing the status of the LED’s.

 

The tables in this section provide information related to the indications provided by

 

these devices.

Table 7-1Operation Indicators

LED

Color

Status

Comments

Power

Green

Indicates that AC power is applied and the

LED’s will flash during power up tests but only

 

 

supplies are operating.

the Power LED should remain on.

Regen

Yellow

On during Regen activity.

Should remain off. On when Regen circuit is

 

 

 

active to dump excess bus energy.

 

 

 

 

OverVoltage/

Red

Regen circuit cannot handle excess energy or

This fault condition is reset by cycling power.

INTLK

 

Interlock circuit is open.

 

 

 

 

 

Temperature

Red

On when internal heatsink temperature exceeds

This fault condition is reset by cycling power.

 

 

158° F (70° C).

Install a fan kit, reduce the load, reduce ambient

 

 

 

temperature, use the Standby current setting.

 

 

Table 7-2Axis 1 and 2 Indicators

 

 

 

 

Stepping

Green

Indicates LinStep+ is sending CW (right LED) or

Above several steps per second the LED

 

 

CCW (left LED) step pulses.

becomes continuously illuminated.

Disable/Short

Yellow

On when the Shutdown input is activated by an

This fault condition is reset by cycling power.

 

 

external control. The Shutdown signal also

To isolate the problem, disconnect and insulate

 

 

activates the Short output, but does not turn on

the motor leads from the drive connector, but

 

 

the Short LED.

leave the Interlock jumper installed. Apply

 

 

Short LED indicates that a Short Circuit or

power and step pulses. If the drive does not

 

 

Undervoltage condition has occurred. A short

invoke the short circuit fault, then it is likely that

 

 

circuit problem can occur because of shorted

the defect is in the motor, wires or the

 

 

or miswired motor leads, or internal fault.

connections at the drive.

Note: The fault LED and fault Output do NOT activate the same. The fault Output indicates that one of several fault conditions has occurred. The fault LEDs provide a means of resolving the source of the fault.

Additional Information (General)

Symptom

Possible Cause

Possible Remedies

The keypad is blank

The keypad is not receiving +5VDC.

Verify all wiring is correct.

with no backlight.

 

Verify that the +5VDC is between 4.8 and 5.2V.

Display is difficult to

Contrast ratio is incorrectly set

Adjust the contrast with the pot on the back of the keypad.

read

 

 

The ON LED is yellow.

FLASH memory is corrupt.

The operating system and user programs must be reloaded.

The ON LED is red.

A Fault has occurred.

The fault can be determined with the keypad or by using

 

 

serial status commands (SS, SA, SD).

Motor moves the wrong

Wrong Gear Ratio.

Check distance units

distance

 

 

Motor stalled.

Check motor current, inductance, anti–resonance settings

 

 

Check Speed Torque required for move, reduce

 

 

acceleration.

Motor stalls

Acceleration and/or velocity too high.

Reduce acceleration and/or velocity.

 

Motor configured incorrectly.

Check motor current, inductance and anti–resonance

 

 

settings.

Motor direction is wrong

The motor phases are miswired.

Verify connections, or swap A+ with A–.

 

The system real direction is reversed.

Change the control’s direction parameter.

The control does not re-

The keypad is disabled.

Check the switch settings on the back of the keypad.

spond to keypad input.

 

 

The motor “whines”

The inductance or anti–resonance

Verify the Inductance setting. Operation is best with motors

 

setting is incorrect.

4 mH or above. Otherwise, verify the anti–resonance setting.

MN1854

Troubleshooting 7-1

Image 88
Contents LinStep+ Dual-Axis Microstepping Indexer/Driver Table of Contents Arithmetic Operands and Equations Other Programming Samples Ii Table of Contents MN1854Increment/Decrement Variables Troubleshooting Serial Communications Problems Iv Table of Contents MN1854 Section General Information Limited WarrantyCE Compliance Product Notice Intended use Could result in injury or deathCould result in damage to property On next 2General Information MN1854Do not touch any circuit board, power device or electrical Connection before you first ensure that power has beenDo not apply AC power before you ensure that grounds are Voltages that are conducted to its power input terminals.Extend more than 0.2 5 into keypad assembly Instead, we recommend using a four wire WyePower is removed from the drive Driver should have specifications compatible to the driveOverview Section Product OverviewMotors Product Overview MN1854 Section Receiving and Installation Power DissipationMechanical Installation Receiving & Inspection2Receiving & Installation MN1854 GNDInput Power Conditioning System Grounding Ungrounded Distribution SystemPower Connections Power connections are shown in Figure Wire Size and Protection Devices4Receiving & Installation MN1854 MN1854 Receiving & Installation Connection Locations 115VAC, 2 Axis6Receiving & Installation MN1854 Tools Required9 & 25 Pin RS-232 Cable Connections for UL Installations RS-232 PC Connections8Receiving & Installation MN1854 Daisy Chain ConnectionsRules for Daisy Chain Operation PC / Host DeviceProgrammable I/O Connections Optional Opto I/O ConnectionsThese input connections are made at terminals 6-40 Figure Typical connection each input10Receiving & Installation MN1854 Encoder Signal PVS100 Danaher 9-Pin DEncoder Color Code +5VDCMotor Connector LD9068A00 Leadwire Connection 9 pin to flying leadsInterlock Intlk Ground GNDStart-Up Procedure Power Off ChecksSwitch and Potentiometer Settings Section General InformationPower On Checks Action Display CommentsMotor should now be producing torque HighReceiving & Installation MN1854 Section Keypad Operation OverviewKeypad layout with the LCD display is shown in Figure F1, F2, F3Copies one program to another within the LinStep+ Comma Decimal PointAlpha Test Thus eliminating the need for a PC terminal connectionTrace Output Move Shutdn RS232 EncoderEdit Menu Pressing the Edit key displays a set of sub-menusSave the program Edit an existing program6Keypad Operation MN1854 Save Program? YesNoNaming a program Example of Naming a ProgramPress ESC. You will be prompted as shown in Figure Mine AC.3 VE2 DI1 GOUse the =O keys for additional alpha characters Entering Characters with the Alpha Key In edit mode8Keypad Operation MN1854 Edit, Setup Submenu Submenu Setup Parameter Description of Setup ParameterPress EDIT, POS F3 Press YES F1 or no F3 Press EDIT, ↓ , List toDisplay the number Programs stored Press ↓ to display the totalPressing Help in the Main Menu Pressing Help in Menus and Sub-MenusPressing Help In the Program Edit function Sequentially Eeprom message disappearsCOPY, to PAD Submenu Enter the program number. Or, ifYou wish, you can scroll the list Program namesSection Setup Procedure Format DefinitionSetup MN1854 Axis One Motor Type SteperAxis One Drive Res Axis One Motor DirAxis One ENC Mode Open LoopApplication Notes Axis One Encoder RES ↑5000 cnts/in ↓IN-RANGE Setup Window ValueIN-RANGE Window PM GainConfigure Your Application Mechanics Mech SetupDist Vmax Accel AmaxAxis One Vel Units In/s EditAxis One MAX Vel 500.0 in/s ↓→Iuuuuuuu ←↑↓→ Configure the I/OChar Keypad Display Input Character Description Inputs will work. See the RG command for more details Service routine programTo summarize, when INT98CTRL=1 Reset to 1. This allows for input debounce and controllingWarm Boot Power-up program, if defined, will startJog Speed InputsOUT1 Programmable Pppppppp ←↑↓→ Configure the Output States OPTO9 InputIiiiiiii OFFConfigure End of Travel Switch Polarity Configure JOG ParametersEnable Accel LO-VEL HI-VELMode Edge Switch Configure Home ParametersOffset DIR Negative Configure Power-up Program ↑SETUP↓Power Up Program PROGRAM0 Axis One Final Dir PositiveConfigure Serial Communications RS232C Setup↑ Enabled ↓ Echo UNIT#Configure Miscellaneous Setup Parameters Data Type Description of Display Data TypeGeneral Password Rules Password SetupOpratr Admin Clear Password Type Description Gives access to these menusKeypad Program Command List Section Keypad ProgrammingAcceleration Start Home Outputs On/Off Function Key Message to DisplayKeypad Programming MN1854 Value Units RangeExample AC2 DE.5 VE12 DA3 GO DA3 GO DA3 GODC Distance to Change Example Distance to Change DCn * DCn*1 * Vn*1 2* Vnt wExamples of DC move profiles, AC = seconds, VE=ips DC n + 10 +DE Deceleration AC.1 VE60 DI2 GO DI1 GO DI-4 GOLP2 DI3 GO EB Value Units Range N/AIF2,1 EN EB DI2 GO =12 =13 =17 =18 =22 =23 =26 =27 =28RUN Edit Copy DELExample 3-Screen Menu Program Set in Edit Setup Mech Accel VEL GH Start HomeGo Immediate Syntax GI or GIi Value N/A Units N/A Range N/AGO Go Start a Move Syntax GO or GOi Value N/A Units N/A Range i=1-16AC.05 DE.05 VE50 DI5 GO VE2 AC.1 DA4,2 GPGosub Syntax GSi and GSname =1-400, name = any legal program nameIF10 Gtpart a EB If input 1 is on and input 2 is off, jump to program Part aUnits Range IFPARTS=25 GS20 EBLppieces IV12,LENGTHDilength Syntax LPi LP Loop Value Units N/A Range N/ASyntax MC+ MC Move Continuous Move Continuous MS27,COUNT 27 7th character, 2nd rowPowerup ONL,GTON EOT GthomeMain VE5 DA20 GO= starting output number =0 input high. X=1 input low grounded=anything else ignore input changes OT4,1 Turn on Output OT2,0D1Syntax RGr RG Registration SQRESULT=0 SQ27.96,SQRESULT Value N/A Units N/AST1 AC1 DE1 VE25 DA6 GO VE50 DA0 GO EN Value N/A Units secondsWTexpression Syntax VEr VE Velocity= starting input number Helpful Hints Programming your application Summary of Expressions, Operators and FunctionsProgramming Overview Program Example of Hosted ModeVariable Names Built-in Variables Examples of how to use Built-in VariablesVariable Name Description of Built-in Variable Type Using Built-in Variable Arowrel Parts Non-Volatile VariablesLpnumber AO15=VOLTAGE + Error Arithmetic Operands and EquationsExamples of incorrect use Instead, you should useLogical Operators Increment/Decrement VariablesExpressions Other Programming SamplesCreate a Message and Read an Input Variable Setting an Output=On on-the-flyCreate a Menu menu display on keypad display for operator Read a 4 Digit BCD number, 2 Digits at a time Reading an Analog Input ValueGET 4 Bcds Digit BCD=4 Digit BCD+2TWSection Troubleshooting 1Operation Indicators2Axis 1 and 2 Indicators Additional Information GeneralTroubleshooting MN1854 Additional InformationSerial Communications Problems Troubleshooting MN1854 Section Specifications & Product Data MN1854 Specifications & Product DataIdentification LinStep+ LX 2 P 1 aGeneral Specifications Protection & Indicators DescriptionVAC VDCOptional Keypad 10.08 256.0 Axis Driver 148.3 Dimensions94.7 230.1 Specifications & Product Data MN1854 Wiring of Shielded Screened Cables Section CE GuidelinesCE Declaration of Conformity EMC Conformity and CE MarkingEMC Wiring Technique CE Guidelines MN1854Cit Grounding EarthEMC Installation Instructions Cable Screens GroundingInput Signal Cable Grounding Simulated Encoder Output Cable GroundingEncoder Cable Grounding To ControllerProgramming Template Appendix aMN1854 Appendix A-1 Appendix MN1854 MN1854 Appendix A-3 Remote Keypad Mounting Template 122.88838 111.25Baldor Electric Company Baldor Electric Company MN1854 01 C&JLinStep+ Dual-Axis Microstepping Indexer/Driver