Baldor mn1854 manual Additional Information, Troubleshooting MN1854

Page 89

Additional Information Continued

Symptom

Possible Cause

Possible Remedies

No RS232 commu-

If the keypad works, the RS232 port

Refer to Section 5, “Configure Serial Communications”.

nication but keypad

is working. Something else is wrong

Verify PC COM port is set to 9600 baud, 8 data bits 1 stop bit,

works.

(wiring, configuration, address).

no parity.

RS232 communica-

The keypad is disabled.

Verify that you do not have an RS485 version.

tion and keypad do

 

Enable the keypad by the switch on back of keypad.

not work.

 

 

The serial port is not working.

Contact Baldor.

 

“Hit A Limit”

A limit switch has been activated.

Either the motion commanded was not correct, or the EOT

 

 

switch is incorrectly positioned on your system.

“Amplifier Fault”

Multiple drive faults have occurred.

The fault can be determined with the keypad or by using serial

 

 

status commands (SS, SA, SD).

 

 

 

“Over Temperature

Internal Fan is not operating or

Remove obstruction, or clean tunnel by removing unit, use

Fault”

Heatsink Tunnel is clogged or

screwdriver to prevent the fan from turning, and blow shop

 

restricted.

air through the tunnel. Return unit to installation.

 

Ambient air in cabinet is too hot.

If multiple units are installed within the enclosure, ventilation

 

 

must be adequately to remove heat.

 

The fan does not operate.

With power off, verify the internal fan connections. If properly

 

 

connected, the fan may have failed. Contact Baldor.

 

 

 

“Over Current Fault”

Motor is miswired or damaged. The

With power off verify all connections.

 

LinStep+ has short circuit protection,

Verify current setting is correct for the motor rating.

 

but you must correct the problem to

Verify the motor phases are not open or shorted (phase to

 

clear the fault.

phase and phase to ground). The resistance in each phase

 

 

should be about the same and only a few ohms. If the

 

 

phases are open or have a large resistance, the motor is

 

 

probably damaged and should be replaced.

“Over Voltage Fault”

Excessive bus voltage. Usually

Eliminate the regen event by reducing the load or make the

 

caused by a regen condition that

move less aggressively by reducing the commanded

 

overwhelms the internal power

acceleration or velocity.

 

dump circuit.

 

 

It can also be caused by high line

Verify AC line voltage is within the limits.

 

voltage, or voltage spikes.

 

“Interlock Fault”

Motor connector does not have an

Connect motor connector with Interlock.

 

interlock jumper, or motor has been

 

 

disconnected.

 

“Following Error”

Motor stalled.

Confirm proper motor configuration (current, AR, mH).

 

 

Make a less aggressive move.

 

Wrong encoder resolution set.

Verify the encoder settings are correct. Incorrect settings can

 

 

cause a following error.

“Encoder Wired

Encoder position is changing opposite

Verify motor and encoder wiring. Reverse phases of either

Backwards”

the commanded move.

motor or encoder. Contact Baldor for assistance.

“Encoder Fault”

Attempted closed loop motion and

Verify encoder wiring.

 

encoder position is unchanged.

 

“Error Finding Home”

Both EOT switches were activated

Verify home switch connections and configuration (NORM

 

without finding the home switch.

OPEN or NORM CLOSED).

“Invalid Program”

Attempted to “call” an empty program

Verify program number, or define program “called”.

 

(i.e. GT, GS).

 

“Program Too Large”

Program length exceeds 1024 bytes.

Divide program into smaller programs or reduce program size.

“Insufficient Memory”

All stored user programs exceed 60K.

Reduce program size, or delete programs.

“Invalid Program #”

Program number exceeds 400 or

Verify program name and number.

 

program name does not exist.

 

7-2 Troubleshooting

MN1854

Image 89
Contents LinStep+ Dual-Axis Microstepping Indexer/Driver Table of Contents Increment/Decrement Variables Other Programming Samples Ii Table of Contents MN1854Arithmetic Operands and Equations Troubleshooting Serial Communications Problems Iv Table of Contents MN1854 CE Compliance Limited WarrantySection General Information Could result in injury or death Product Notice Intended useCould result in damage to property On next 2General Information MN1854Connection before you first ensure that power has been Do not touch any circuit board, power device or electricalDo not apply AC power before you ensure that grounds are Voltages that are conducted to its power input terminals.Instead, we recommend using a four wire Wye Extend more than 0.2 5 into keypad assemblyPower is removed from the drive Driver should have specifications compatible to the driveMotors Section Product OverviewOverview Product Overview MN1854 Power Dissipation Section Receiving and InstallationMechanical Installation Receiving & InspectionGND 2Receiving & Installation MN1854System Grounding Ungrounded Distribution System Input Power Conditioning4Receiving & Installation MN1854 Wire Size and Protection DevicesPower Connections Power connections are shown in Figure Connection Locations 115VAC, 2 Axis MN1854 Receiving & InstallationTools Required 6Receiving & Installation MN1854RS-232 PC Connections 9 & 25 Pin RS-232 Cable Connections for UL InstallationsDaisy Chain Connections 8Receiving & Installation MN1854Rules for Daisy Chain Operation PC / Host DeviceOptional Opto I/O Connections Programmable I/O ConnectionsThese input connections are made at terminals 6-40 Figure Typical connection each inputEncoder Signal PVS100 Danaher 9-Pin D 10Receiving & Installation MN1854Encoder Color Code +5VDCLD9068A00 Leadwire Connection 9 pin to flying leads Motor ConnectorInterlock Intlk Ground GNDPower Off Checks Start-Up ProcedureSwitch and Potentiometer Settings Section General InformationAction Display Comments Power On ChecksMotor should now be producing torque HighReceiving & Installation MN1854 Overview Section Keypad OperationKeypad layout with the LCD display is shown in Figure F1, F2, F3Copies one program to another within the LinStep+ Alpha Decimal PointComma Thus eliminating the need for a PC terminal connection TestTrace Output Move Shutdn RS232 EncoderPressing the Edit key displays a set of sub-menus Edit MenuEdit an existing program Save the program6Keypad Operation MN1854 Save Program? YesNoExample of Naming a Program Naming a programPress ESC. You will be prompted as shown in Figure Mine AC.3 VE2 DI1 GO8Keypad Operation MN1854 Entering Characters with the Alpha Key In edit modeUse the =O keys for additional alpha characters Submenu Setup Parameter Description of Setup Parameter Edit, Setup SubmenuPress EDIT, ↓ , List to Press EDIT, POS F3 Press YES F1 or no F3Display the number Programs stored Press ↓ to display the totalPressing Help in Menus and Sub-Menus Pressing Help in the Main MenuPressing Help In the Program Edit function Sequentially Eeprom message disappearsEnter the program number. Or, if COPY, to PAD SubmenuYou wish, you can scroll the list Program namesProcedure Format Definition Section SetupAxis One Motor Type Steper Setup MN1854Axis One Drive Res Axis One Motor DirOpen Loop Axis One ENC ModeApplication Notes Axis One Encoder RES ↑5000 cnts/in ↓Value IN-RANGE Setup WindowIN-RANGE Window PM GainMech Setup Configure Your Application MechanicsDist Vmax Accel AmaxEdit Axis One Vel Units In/sAxis One MAX Vel 500.0 in/s ↓→Char Keypad Display Input Character Description Configure the I/OIuuuuuuu ←↑↓→ Service routine program Inputs will work. See the RG command for more detailsTo summarize, when INT98CTRL=1 Reset to 1. This allows for input debounce and controllingPower-up program, if defined, will start Warm BootJog Speed InputsOUT1 Programmable Pppppppp ←↑↓→ OPTO9 Input Configure the Output StatesIiiiiiii OFFConfigure JOG Parameters Configure End of Travel Switch PolarityEnable Accel LO-VEL HI-VELOffset DIR Configure Home ParametersMode Edge Switch Negative ↑SETUP↓ Configure Power-up ProgramPower Up Program PROGRAM0 Axis One Final Dir PositiveRS232C Setup Configure Serial Communications↑ Enabled ↓ Echo UNIT#Data Type Description of Display Data Type Configure Miscellaneous Setup ParametersPassword Setup General Password RulesOpratr Admin Clear Password Type Description Gives access to these menusSection Keypad Programming Keypad Program Command ListAcceleration Start Home Outputs On/Off Function Key Message to DisplayValue Units Range Keypad Programming MN1854Example AC2 DE.5 VE12 DA3 GO DA3 GO DA3 GODC Distance to Change DCn * DCn*1 * Vn*1 2* Vnt w Example Distance to ChangeExamples of DC move profiles, AC = seconds, VE=ips DC n + 10 +AC.1 VE60 DI2 GO DI1 GO DI-4 GO DE DecelerationIF2,1 EN EB DI2 GO Value Units Range N/ALP2 DI3 GO EB =26 =27 =28 =12 =13 =17 =18 =22 =23RUN Edit Copy DELExample 3-Screen Menu Program GH Start Home Set in Edit Setup Mech Accel VELValue N/A Units N/A Range N/A Go Immediate Syntax GI or GIiValue N/A Units N/A Range i=1-16 GO Go Start a Move Syntax GO or GOiAC.05 DE.05 VE50 DI5 GO VE2 AC.1 DA4,2 GP=1-400, name = any legal program name Gosub Syntax GSi and GSnameIF10 Gtpart a EB If input 1 is on and input 2 is off, jump to program Part aIFPARTS=25 GS20 EB Units RangeDilength IV12,LENGTHLppieces Value Units N/A Range N/A Syntax LPi LP LoopSyntax MC+ MC Move Continuous Move Continuous 27 7th character, 2nd row MS27,COUNTGthome Powerup ONL,GTON EOTMain VE5 DA20 GO=0 input high. X=1 input low grounded = starting output number=anything else ignore input changes OT4,1 Turn on Output OT2,0D1Syntax RGr RG Registration Value N/A Units N/A SQRESULT=0 SQ27.96,SQRESULTST1 AC1 DE1 VE25 DA6 GO VE50 DA0 GO EN Value N/A Units seconds= starting input number Syntax VEr VE VelocityWTexpression Programming Overview Summary of Expressions, Operators and FunctionsHelpful Hints Programming your application Variable Names Example of Hosted ModeProgram Variable Name Description of Built-in Variable Type Examples of how to use Built-in VariablesBuilt-in Variables Using Built-in Variable Arowrel Lpnumber Non-Volatile VariablesParts Arithmetic Operands and Equations AO15=VOLTAGE + ErrorExamples of incorrect use Instead, you should useIncrement/Decrement Variables Logical OperatorsExpressions Other Programming SamplesCreate a Menu menu display on keypad display for operator Setting an Output=On on-the-flyCreate a Message and Read an Input Variable Reading an Analog Input Value Read a 4 Digit BCD number, 2 Digits at a timeGET 4 Bcds Digit BCD=4 Digit BCD+2TW1Operation Indicators Section Troubleshooting2Axis 1 and 2 Indicators Additional Information GeneralAdditional Information Troubleshooting MN1854Serial Communications Problems Troubleshooting MN1854 MN1854 Specifications & Product Data Section Specifications & Product DataIdentification LinStep+ LX 2 P 1 aProtection & Indicators Description General SpecificationsVAC VDC94.7 230.1 DimensionsOptional Keypad 10.08 256.0 Axis Driver 148.3 Specifications & Product Data MN1854 Section CE Guidelines Wiring of Shielded Screened CablesCE Declaration of Conformity EMC Conformity and CE MarkingCE Guidelines MN1854 EMC Wiring TechniqueCit Grounding EarthCable Screens Grounding EMC Installation InstructionsSimulated Encoder Output Cable Grounding Input Signal Cable GroundingEncoder Cable Grounding To ControllerMN1854 Appendix A-1 Appendix aProgramming Template Appendix MN1854 MN1854 Appendix A-3 122.88 Remote Keypad Mounting Template838 111.25Baldor Electric Company MN1854 01 C&J Baldor Electric CompanyLinStep+ Dual-Axis Microstepping Indexer/Driver