Trane CNT-SVX07C-EN, Zone Controller, N512 manual Agency listing/compliance, Additional components

Page 14

Chapter 1 Overview and specifications

Agency listing/compliance

CE—Immunity: EN 50082-1:1997; EN 50082-2:1995

CE—Emissions: EN 50081-1:1992 (CISPR 22) Class B

UL and C-UL 916 listed: Energy management system

UL 94-5V (UL flammability rating for plenum use)

FCC Part 15, Class A

ASHRAE Cycle 1 & Cycle 2 control sequences

Additional components

The Tracer ZN521 zone controller requires the use of additional compo- nents for monitoring and proper control of the associated equipment. The use of specific components depends on the application. These components are not included with the Tracer ZN521 zone controller.

Power transformer

Use a UL-listed Class 2 power transformer supplying a nominal 24 Vac (19–30 Vac) to power both the Tracer ZN521 zone controller (14 VA) and its associated output devices, including relays and actuators, to a maxi- mum of 12 VA per output utilized.

Water, duct, and outdoor-air temperature sensors

Temperature sensors must be Trane 10 kΩ (at 25°C) thermistors. Enter- ing water and discharge air inputs may use a sealed temperature sensor (part number 4190 1100).

Binary input switching devices

Occupancy, condensate overflow, low-coil-temperature, and fan status inputs accept switching devices that may have normally open or normally closed dry contacts.

Output devices

Output devices connected to the Tracer ZN521 binary outputs cannot exceed 12 VA (0.5 A) current draw at 24 Vac.

Zone temperature sensors

Table 1 shows the Trane zone temperature sensors that are supported by the Tracer ZN521 zone controller.

Valve actuators

Valve actuators cannot exceed 12 VA draw at 24 Vac. For two-position valves, use actuators with on/off action, and with a spring action that

4

CNT-SVX07C-EN

Image 14
Contents Installation and Operation Tracer ZN521 Zone Controller Page CNT-SVX07C-EN April CNT-SVX07C-EN Tracer ZN521 Zone Controller Installation and Operation CNT-SVX07C-EN Contents Sequence of operations Status indicators for operation and communication Troubleshooting Index Overview and specifications Product descriptionClearances DimensionsStorage environment Plastic-cover model dimensions and clearances Agency listing/compliance Additional componentsZone humidity sensor Tracer zone temperature sensor optionsDamper actuators CO2 sensorOverview and specifications Input/output terminal wiring AC-power wiringGeneral wiring information Communication-link wiring and addressing General wiring information Location recommendations Operating environment requirementsMounting recommendations Mounting the Tracer ZN521 zone controllerControlValve Economizing Typical applications for the Tracer ZN521 zone controllerApplication SpeedfanMultiple Dehumidification HeatElectricBI2 Condensate overflow BI1 Low-coil-temperature detectionBinary inputs Binary inputsBI3 Occupancy or generic binary input BI4 Fan statusGND Ground terminals ZN Zone temperatureAnalog inputs Analog inputsSET Local setpoint FAN Fan mode inputAI1 Entering water temperature AI2 Discharge air temperature AI3 Outdoor air temperature or generic temperatureAI4 Universal 4-20 mA AI4 configuration options and associated measurement rangesConfiguration Measurement range AI4 terminal wiring CO2 measurement Binary output functions Binary outputsGeneric binary output Binary output FunctionsRequired controller inputs for proper operation Wiring requirements and optionsOverriding binary outputs Function Input source For more information SeeTwo-pipe hydronic-cooling unit Two-pipe hydronic-heating unit Two-pipe hydronic heating/cooling unit with auto changeover Four-pipe hydronic heating/cooling unit Four-pipe heating/cooling unit with auto changeover Two-pipe heating unit with DX cooling Electric heat unit with DX cooling Electric heat unit Two-pipe heating unit with face-and-bypass damper Two-pipe heating/cooling unit with face-and-bypass damper Four-pipe heating/cooling unit with face-and-bypass damper Input/output functions and wiring for typical applications Power-up sequence Random startOccupied standby mode Occupied modeUnoccupied mode Occupancy modesOccupied bypass mode Timed override controlSimplified zone control Zone temperature controlCascade zone control Morning warm-up Heating or cooling modeDischarge air tempering Morning cool-downEntering water temperature sampling function Fan operationExhaust control Exhaust controlModulating valve calibration Valve operationModulating valve operation Valve control optionsIsolation-valve operation Modulating outdoor/return air dampersTwo-position valve operation Two-pipe operationModulating outdoor air damper position Economizing free cooling Ashrae Cycle 1 conformanceAshrae Cycle 2 conformance DX cooling operation Two-position control of a modulating outdoor air damperFace-and-bypass damper operation Face-and-bypass, isolation-valve operationDehumidification Electric heat operationBaseboard heat operation Peer-to-peer communication Unit protection strategiesFan off delay Smart resetLow-coil-temperature protection Condensate overflowFreeze avoidance Filter-maintenance timerFreeze protection discharge air temperature low limit Test button Tracer ZN521 zone controller circuit boardManual output test For non OutputClose damper, air Outdoor Open damper, air Outdoor Step Result BOP1 BOP2 BOP3 BOP4 BOP5 BOP6 BOP7 BOP8 BOP9Interpreting LEDs Service pin buttonRed LED Service indicator LED activity ExplanationGreen LED Status indicator Yellow LED Communications indicatorDiagnostics Types of diagnosticsDiagnostic Probable cause Consequences Type Table of diagnosticsDiagnostics Fan unaffectedValved unaffected PositionDamper unaffected Status indicators for operation and communication Fan does not energize Probable cause ExplanationTroubleshooting Valves remain closedValves remain open DX or electric heat does not energizeOutdoor air damper remains closed Outdoor air damper remains openOutdoor air damper remains open Troubleshooting Index NumericsIndex Index Index Page Trane