| Troubleshooting | |
Table 19. Valves remain open | ||
|
|
|
Probable cause | Explanation | |
|
|
|
Unit wiring | The wiring between the controller outputs and the valve(s) must be present and correct | |
| for normal valve operation. Refer to applicable wiring diagram. | |
|
|
|
Failed end device | The valves must be checked to ensure proper operations. | |
|
|
|
Normal operation | The controller opens and closes the valves to meet the unit capacity requirements. | |
|
|
|
Manual output test | The controller includes a manual output test sequence you can use to verify output oper- | |
| ation and associated output wiring. However, based on the current step in the test | |
| sequence, the values may not be open. refer to the “Manual output test” on page 52. | |
|
|
|
Diagnostic present | Several diagnostics affect valve operation. For information about these diagnostics, see | |
| Table 16 on page 59. | |
|
|
|
Unit configuration | The controller must be properly configured based on the actual installed end devices and | |
| application. If the unit configuration does not match the actual end device, the valves may | |
| not work correctly. | |
|
|
|
Entering water | The controller includes entering water temperature sampling logic, which is automatically | |
temperature | initiated during | |
sampling logic | too cool or too hot for the desired heating or cooling. (See “AI1: Entering water tempera- | |
| ture” on page 17.) | |
|
|
|
Valve configuration | Make sure the valves are correctly configured, using the Rover service tool, as normally | |
| open or normally closed as dictated by the application. | |
|
|
|
Freeze avoidance | When the fan is off with no demand for capacity (0%) and the outdoor air temperature is | |
| below the freeze avoidance setpoint, the controller opens the water valves (100%) to pre- | |
| vent coil freezing. This includes unoccupied mode when there is no call for capacity or | |
| any other time the fan is off. | |
|
|
|
Table 20. DX or electric heat does not energize | ||
|
|
|
Probable cause | Explanation |
|
|
|
|
Unit wiring | The wiring between the controller outputs and the end devices must be present and cor- |
|
| rect for normal operation. Refer to applicable wiring diagram. |
|
|
|
|
Failed end device | Check the control contactors or the electric heat element, including any auxiliary safety |
|
| interlocks, to ensure proper operation. |
|
|
|
|
No power to the | If the controller does not have power, heat outputs do not operate. For the Tracer ZN521 |
|
controller | controller to operate normally, you must apply an input voltage of 24 Vac. If the green |
|
| LED is off continuously, the controller does not have sufficient power or has failed. |
|
|
|
|
Diagnostic present | Several diagnostics affect DX and electric heat operation. For information about these |
|
| diagnostics, see Table 16 on page 59. |
|
|
|
|
Normal operation | The controller controls compressor or electric heat outputs as needed to meet the unit |
|
| capacity requirements. |
|
|
|
|
Unit | The controller must be properly configured based on the actual installed end devices and |
|
configuration | application. If the unit configuration does not match the actual end device, DX or electric |
|
| heat may not operate correctly. |
|
|
|
|
Manual output test | The controller includes a manual output test sequence you can use to verify output oper- |
|
| ation and associated output wiring. However, based on the current step in the test |
|
| sequence, the DX or electric heat outputs may be off. Refer to the “Manual output test” |
|
| on page 52. |
|
|
|
|
| 65 |