Trane CNT-SVX07C-EN, Zone Controller, N512 manual Troubleshooting, Valves remain closed

Page 74

Chapter 7 Troubleshooting

Table 17. Fan does not energize (Continued)

Probable cause

Explanation

 

 

Cycling fan operation/

The controller operates the fan continuously when in the occupied, occupied standby, or

continuous

occupied bypass mode. When the controller is in the unoccupied mode, the fan is cycled

 

between high speed and off with capacity.

 

 

Unoccupied operation

Even if the controller is configured for continuous fan operation, the fan normally cycles

 

with capacity during unoccupied mode. While unoccupied, the fan cycles on or off with

 

heating/cooling to provide varying amounts of heating or cooling to the space.

 

 

Fan mode off

If a local fan mode switch determines the fan operation, the off position controls the fan

 

off.

 

 

Requested mode off

You can communicate a desired operating mode (such as off, heat, and cool) to the con-

 

troller. If off is communicated to the controller, the unit controls the fan off. There is no

 

heating or cooling.

 

 

Table 18. Valves remain closed

Probable cause

Explanation

 

 

Unit wiring

The wiring between the controller outputs and the valve(s) must be present and correct

 

for normal valve operation. Refer to applicable wiring diagram.

 

 

Failed end device

The valves must be checked to ensure proper operation.

 

 

No power to the con-

If the controller does not have power, the unit valve(s) will not operate. For the Tracer

troller

ZN521 controller to operate normally, you must apply an input voltage of 24 Vac. If the

 

green LED is off continuously, the controller does not have sufficient power or has failed.

 

 

Power-up control-wait

If power-up control-wait is enabled (non-zero time), the controller remains off until one of

 

two conditions occurs:

 

1) The controller exits power-up control-wait after it receives communicated information.

 

2) The controller exits power-up control-wait after the power-up control-wait time expires.

 

 

Diagnostic present

Several diagnostics affect valve operation. For information about these diagnostics, see

 

Table 16 on page 59.

 

 

Normal operation

The controller opens and closes the valves to meet the unit capacity requirements.

 

 

Unit configuration

The controller must be properly configured based on the actual installed end devices and

 

application. If the unit configuration does not match the actual end device, the valves

 

may not work correctly.

 

 

Manual output test

The controller includes a manual output test sequence you can use to verify output oper-

 

ation and associated output wiring. However, based on the current step in the test

 

sequence, the valves may not be open. Refer to the “Manual output test” on page 52.

 

 

Random start

After power-up, the controller always observes a random start from 5 to 30 seconds. The

observed

controller remains off until the random start time expires.

 

 

Requested mode off

You can communicate a desired operating mode (such as off, heat, and cool) to the con-

 

troller. If off is communicated to the controller, the unit controls the fan off. There is no

 

heating or cooling.

 

 

Entering water

The controller includes entering water temperature sampling logic, which is automati-

temperature

cally initiated during 2-pipe and 4-pipe changeover if the entering water temperature is

sampling logic

either too cool or too hot for the desired heating or cooling. (See “AI1: Entering water

 

temperature” on page 17.)

 

 

Valve configuration

Make sure the valves are correctly configured, using the Rover service tool, as normally

 

open or normally closed as dictated by the application.

 

 

64

CNT-SVX07C-EN

Image 74
Contents Installation and Operation Tracer ZN521 Zone Controller Page CNT-SVX07C-EN April CNT-SVX07C-EN Tracer ZN521 Zone Controller Installation and Operation CNT-SVX07C-EN Contents Sequence of operations Status indicators for operation and communication Troubleshooting Index Overview and specifications Product descriptionClearances DimensionsStorage environment Plastic-cover model dimensions and clearances Agency listing/compliance Additional componentsZone humidity sensor Tracer zone temperature sensor optionsDamper actuators CO2 sensorOverview and specifications Input/output terminal wiring AC-power wiringGeneral wiring information Communication-link wiring and addressing General wiring information Location recommendations Operating environment requirementsMounting recommendations Mounting the Tracer ZN521 zone controllerControlValve Economizing Typical applications for the Tracer ZN521 zone controllerApplication SpeedfanMultiple Dehumidification HeatElectricBI2 Condensate overflow BI1 Low-coil-temperature detectionBinary inputs Binary inputsBI3 Occupancy or generic binary input BI4 Fan statusGND Ground terminals ZN Zone temperatureAnalog inputs Analog inputsSET Local setpoint FAN Fan mode inputAI1 Entering water temperature AI2 Discharge air temperature AI3 Outdoor air temperature or generic temperatureAI4 Universal 4-20 mA AI4 configuration options and associated measurement rangesConfiguration Measurement range AI4 terminal wiring CO2 measurement Binary output functions Binary outputsGeneric binary output Binary output FunctionsRequired controller inputs for proper operation Wiring requirements and optionsOverriding binary outputs Function Input source For more information SeeTwo-pipe hydronic-cooling unit Two-pipe hydronic-heating unit Two-pipe hydronic heating/cooling unit with auto changeover Four-pipe hydronic heating/cooling unit Four-pipe heating/cooling unit with auto changeover Two-pipe heating unit with DX cooling Electric heat unit with DX cooling Electric heat unit Two-pipe heating unit with face-and-bypass damper Two-pipe heating/cooling unit with face-and-bypass damper Four-pipe heating/cooling unit with face-and-bypass damper Input/output functions and wiring for typical applications Power-up sequence Random startOccupied standby mode Occupied modeUnoccupied mode Occupancy modesOccupied bypass mode Timed override controlSimplified zone control Zone temperature controlCascade zone control Morning warm-up Heating or cooling modeDischarge air tempering Morning cool-downEntering water temperature sampling function Fan operationExhaust control Exhaust controlModulating valve calibration Valve operationModulating valve operation Valve control optionsIsolation-valve operation Modulating outdoor/return air dampersTwo-position valve operation Two-pipe operationModulating outdoor air damper position Economizing free cooling Ashrae Cycle 1 conformanceAshrae Cycle 2 conformance DX cooling operation Two-position control of a modulating outdoor air damperFace-and-bypass damper operation Face-and-bypass, isolation-valve operationDehumidification Electric heat operationBaseboard heat operation Peer-to-peer communication Unit protection strategiesFan off delay Smart resetLow-coil-temperature protection Condensate overflowFreeze avoidance Filter-maintenance timerFreeze protection discharge air temperature low limit Test button Tracer ZN521 zone controller circuit boardManual output test For non OutputClose damper, air Outdoor Open damper, air Outdoor Step Result BOP1 BOP2 BOP3 BOP4 BOP5 BOP6 BOP7 BOP8 BOP9Interpreting LEDs Service pin buttonRed LED Service indicator LED activity ExplanationGreen LED Status indicator Yellow LED Communications indicatorDiagnostics Types of diagnosticsDiagnostic Probable cause Consequences Type Table of diagnosticsDiagnostics Fan unaffectedValved unaffected PositionDamper unaffected Status indicators for operation and communication Fan does not energize Probable cause ExplanationTroubleshooting Valves remain closedValves remain open DX or electric heat does not energizeOutdoor air damper remains closed Outdoor air damper remains openOutdoor air damper remains open Troubleshooting Index NumericsIndex Index Index Page Trane