Diagnostics
Smart reset diagnostics
After the controller detects the first smart reset diagnostic, the unit waits 30 minutes before initiating the smart reset function. If another diagnos- tic of this type occurs again within 24 hours after an automatic clearing, you must clear the diagnostic manually by using any of the ways shown for “Manual (latching) diagnostics.”
Informational diagnostics
Informational diagnostics provide information about the status of the controller. They do not affect machine operation. They can be cleared from the controller using any of the ways shown for “Manual (latching) diag- nostics.”
Table of diagnostics
Table 16 The tables present each diagnostic that can be generated by the
Tracer ZN521, its effect on outputs (consequences), and its type.
Note:
The generic binary output is unaffected by diagnostics.
Table 16. Diagnostics
Diagnostic | Probable cause | Consequences | Diagnostic | |
type | ||||
|
|
| ||
|
|
|
| |
Maintenance Required | Fan run hours exceed the | Fan unaffected | Informational | |
| time set to indicate filter | Valves unaffected |
| |
| change | Electric heat unaffected |
| |
|
| Face and bypass damper unaffected |
| |
|
|
|
| |
Condensate Overflow | The drain pan is full of | Fan off | Manual | |
| water | Valves closed |
| |
|
| Outdoor air damper closed |
| |
|
| Face and bypass damper bypass |
| |
|
| DX/electric heat off |
| |
|
| Baseboard heat off |
| |
|
|
|
| |
Low Coil Temp Detection | The leaving fluid temper- | Fan off | Smart reset/ | |
| ature may be close to | Valves open | Manual | |
| freezing | Outdoor air damper closed |
| |
|
| Face and bypass damper bypass |
| |
|
| DX/electric heat off |
| |
|
| Baseboard heat off |
| |
|
|
|
| |
Low | The fan drive belt, con- | Fan off | Manual | |
| tactor, or motor has | Valves closed |
| |
| failed. | Outdoor air damper closed |
| |
|
| Face and bypass damper bypass |
| |
|
| DX/electric heat off |
| |
|
| Baseboard heat off |
| |
|
|
|
|
| 59 |