Trane N512, Zone Controller Outdoor air damper remains closed, Outdoor air damper remains open

Page 76

Chapter 7 Troubleshooting

Table 20. DX or electric heat does not energize (Continued)

Probable cause

Explanation

 

 

Requested mode off

You can communicate a desired operating mode (such as off, heat, and cool) to the con-

 

troller. If off is communicated to the controller, the unit shuts off the compressor or elec-

 

tric heat.

 

 

Freeze avoidance

When the fan is off with no demand for capacity (0%) and the outdoor air temperature is

 

below the freeze avoidance setpoint, the controller disables compressors and electric

 

heat outputs (100%) to prevent coil freezing. This includes unoccupied mode when there

 

is no call for capacity or any other time the fan is off.

 

 

Table 21. Outdoor air damper remains closed

Probable cause

Explanation

 

 

Unit wiring

The wiring between the controller outputs and the outdoor air damper must be present

 

and correct for normal outdoor air damper operation. Refer to applicable wiring diagram.

 

 

Failed end device

Check damper actuator to ensure proper operation.

 

 

No power to the

If the controller does not have power, the outdoor air damper does not operate. For the

controller

Tracer ZN521 controller to operate normally, you must apply an input voltage of 24 Vac. If

 

the green LED is off continuously, the controller does not have sufficient power or has

 

failed.

 

 

Diagnostic present

Several diagnostics affect outdoor air damper operation. For information about these

 

diagnostics, see Table 16 on page 59.

 

 

Normal

The controller opens and closes the outdoor air damper based on the controller’s occu-

operation

pancy mode and fan status. Normally, the outdoor air damper is open during occupied

 

mode when the fan is running and closed during unoccupied mode.

 

 

Unit configuration

The controller must be properly configured based on the actual installed end devices and

 

application. If the unit configuration does not match the actual end device, the outdoor air

 

damper may not work correctly.

 

 

Manual output test

The controller includes a manual output test sequence you can use to verify output oper-

 

ation and associated output wiring. However, based on the current step in the test

 

sequence, the outdoor air damper may not be open. Refer to the “Manual output test” on

 

page 52.

 

 

Warm-up and cool-

The controller includes both a morning warm-up and cool-down sequence to keep the

down sequence

outdoor air damper closed during the transition from unoccupied to occupied. This is an

 

attempt to bring the space under control as quickly as possible.

 

 

Requested mode off

You can communicate a desired operating mode (such as off, heat, or cool) to the control-

 

ler. If off is communicated to the controller, the unit closes the outdoor air damper.

 

 

Table 22. Outdoor air damper remains open

Probable cause

Explanation

 

 

Unit wiring

The wiring between the controller outputs and the outdoor air damper must be present

 

and correct for normal outdoor air damper operation. Refer to applicable wiring diagram.

 

 

Failed end device

Check damper actuator to ensure proper operation.

 

 

66

CNT-SVX07C-EN

Image 76
Contents Installation and Operation Tracer ZN521 Zone Controller Page CNT-SVX07C-EN April CNT-SVX07C-EN Tracer ZN521 Zone Controller Installation and Operation CNT-SVX07C-EN Contents Sequence of operations Status indicators for operation and communication Troubleshooting Index Overview and specifications Product descriptionStorage environment DimensionsClearances Plastic-cover model dimensions and clearances Agency listing/compliance Additional componentsTracer zone temperature sensor options Damper actuatorsZone humidity sensor CO2 sensorOverview and specifications Input/output terminal wiring AC-power wiringGeneral wiring information Communication-link wiring and addressing General wiring information Location recommendations Operating environment requirementsMounting recommendations Mounting the Tracer ZN521 zone controllerTypical applications for the Tracer ZN521 zone controller Application SpeedfanMultiple DehumidificationControlValve Economizing HeatElectricBI1 Low-coil-temperature detection Binary inputsBI2 Condensate overflow Binary inputsBI3 Occupancy or generic binary input BI4 Fan statusZN Zone temperature Analog inputsGND Ground terminals Analog inputsAI1 Entering water temperature FAN Fan mode inputSET Local setpoint AI2 Discharge air temperature AI3 Outdoor air temperature or generic temperatureConfiguration Measurement range AI4 configuration options and associated measurement rangesAI4 Universal 4-20 mA AI4 terminal wiring CO2 measurement Binary outputs Generic binary outputBinary output functions Binary output FunctionsWiring requirements and options Overriding binary outputsRequired controller inputs for proper operation Function Input source For more information SeeTwo-pipe hydronic-cooling unit Two-pipe hydronic-heating unit Two-pipe hydronic heating/cooling unit with auto changeover Four-pipe hydronic heating/cooling unit Four-pipe heating/cooling unit with auto changeover Two-pipe heating unit with DX cooling Electric heat unit with DX cooling Electric heat unit Two-pipe heating unit with face-and-bypass damper Two-pipe heating/cooling unit with face-and-bypass damper Four-pipe heating/cooling unit with face-and-bypass damper Input/output functions and wiring for typical applications Power-up sequence Random startOccupied mode Unoccupied modeOccupied standby mode Occupancy modesOccupied bypass mode Timed override controlCascade zone control Zone temperature controlSimplified zone control Heating or cooling mode Discharge air temperingMorning warm-up Morning cool-downEntering water temperature sampling function Fan operationExhaust control Exhaust controlValve operation Modulating valve operationModulating valve calibration Valve control optionsModulating outdoor/return air dampers Two-position valve operationIsolation-valve operation Two-pipe operationModulating outdoor air damper position Ashrae Cycle 2 conformance Ashrae Cycle 1 conformanceEconomizing free cooling Two-position control of a modulating outdoor air damper Face-and-bypass damper operationDX cooling operation Face-and-bypass, isolation-valve operationBaseboard heat operation Electric heat operationDehumidification Peer-to-peer communication Unit protection strategiesSmart reset Low-coil-temperature protectionFan off delay Condensate overflowFreeze protection discharge air temperature low limit Filter-maintenance timerFreeze avoidance Test button Tracer ZN521 zone controller circuit boardManual output test For non OutputClose damper, air Outdoor Open damper, air Outdoor Step Result BOP1 BOP2 BOP3 BOP4 BOP5 BOP6 BOP7 BOP8 BOP9Service pin button Red LED Service indicatorInterpreting LEDs LED activity ExplanationGreen LED Status indicator Yellow LED Communications indicatorDiagnostics Types of diagnosticsTable of diagnostics DiagnosticsDiagnostic Probable cause Consequences Type Fan unaffectedValved unaffected PositionDamper unaffected Status indicators for operation and communication Fan does not energize Probable cause ExplanationTroubleshooting Valves remain closedValves remain open DX or electric heat does not energizeOutdoor air damper remains closed Outdoor air damper remains openOutdoor air damper remains open Troubleshooting Index NumericsIndex Index Index Page Trane