Manual output test
Table 12. Manual output test sequence for
Step | Result | BOP1 | BOP2 | BOP3 | BOP4 | BOP5 | BOP6 | BOP7 | BOP8 | BOP9 | BO |
Number of times Test button is pressed |
| Fan high | 1)Fan medium 2)Exhaust fan | Fan low | Face and bypass damper, open to face | Face and bypass damper, close (bypass) | Outdoor air damper, open | Outdoor air damper, close | 1)Generic | ||
|
|
|
|
|
|
|
|
|
|
|
|
1 | Begins test | Off | Off | Off | Off | Off | Off | On/Close | Off | On/Close | Off |
| mode1 |
|
|
|
|
|
|
|
|
|
|
2 | Fan high2 | On/High | Off | Off | Off | On/Open | Off | Off | Off | Off | Off |
3 | Fan | Off | 1) On/Med | Off | Off | On/Open | Off | Off | Off | Off | Off |
| medium3 |
| 2) Off |
|
|
|
|
|
|
|
|
4 | Fan low4 | Off | Off | On/Low | Off | On/Open | Off | Off | Off | Off | Off |
5 | Main open, | On/High | Off | Off | On/Open | On/Open | Off | Off | Off | Off | Off |
| DX on |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
6 | Main close, | On/High | Off | Off | Off | On/Open | On/Open | Off | Off | Off | Off |
| DX off, aux |
|
|
|
|
|
|
|
|
|
|
| open |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
7 | Aux open, | On/High | 1) Off | Off | Off | On/Open | On/Open | Off | Off | Off | Off |
| EH1 on, |
| 2) On |
|
|
|
|
|
|
|
|
| exhaust |
|
|
|
|
|
|
|
|
|
|
| fan5 |
|
|
|
|
|
|
|
|
|
|
8 | Aux close, | On/High | Off | Off | Off | Off | Off | On/Close | On/Open | Off | Off |
| damper |
|
|
|
|
|
|
|
|
|
|
| open |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
9 | Outdoor air | On/High | Off | Off | Off | Off | Off | On/Close | Off | On/Close | Off |
| damper |
|
|
|
|
|
|
|
|
|
|
| close |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10 | Generic/ | On/High | Off | Off | Off | Off | Off | On/Close | Off | Off | On |
| baseboard |
|
|
|
|
|
|
|
|
|
|
| heat |
|
|
|
|
|
|
|
|
|
|
| energized6 |
|
|
|
|
|
|
|
|
|
|
11: Exit5 |
|
|
|
|
|
|
|
|
|
|
|
1The controller turns off all fan and electric heat outputs and drives all dampers and valves closed.
2The controller attempts to clear all diagnostics.
3If configured for a
4If configured for a
5If the unit is configured for a 1- or
6After step 10, the manual output test performs an exit, which initiates a reset to restore the controller to normal operation.
| 55 |