Trane Zone Controller, N512, CNT-SVX07C-EN manual Damper actuators, Zone humidity sensor, CO2 sensor

Page 15

 

 

 

 

 

 

 

 

 

Additional components

Table 1. Tracer zone temperature sensor options

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Timed

 

 

 

 

 

Fan

 

 

 

Zone

 

override

 

BAS

 

 

 

 

 

 

 

 

 

buttons

Comm

 

 

 

 

 

 

 

 

 

 

 

order

Use

 

 

 

 

 

 

 

 

 

 

number

 

 

 

 

 

 

Setpoint

 

 

 

 

jack

 

 

 

 

 

 

Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

Med

Low

Auto

Off

thumb-

On

 

Cancel

 

 

 

sensor

 

 

 

 

 

 

 

 

 

wheel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4190 1087

Any

 

 

 

 

 

 

x

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4190 1088

Any

 

 

 

 

 

 

x

x

 

x

x

 

 

 

 

 

 

 

 

 

 

 

 

 

4190 1090

Any

 

 

 

 

 

x

x

x

 

x

x

 

 

 

 

 

 

 

 

 

 

 

 

 

4190 1094

Any

 

 

 

 

 

x

x

 

 

 

x

 

 

 

 

 

 

 

 

 

 

 

 

 

4190 1095

Unit

x

 

x

 

x

x

x

x

 

x

x

 

ventilator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4190 1115

Fan coil

x

x

x

x

x

x

x

x

 

x

x

 

 

 

 

 

 

 

 

 

 

 

 

 

4190 1116

Unit

x

 

x

x

x

x

x

x

 

x

x

 

ventilator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4190 1117

Any

 

 

 

x

x

x

x

x

 

x

x

 

 

 

 

 

 

 

 

 

 

 

 

 

returns the valve to normally open or closed (dependent on the desired default position). For modulating valve control, use tri-state modulating actuators with or without a spring return, as required by the application.

Damper actuators

Damper actuators cannot exceed 12 VA draw at 24 Vac. For control of out- door/return air dampers, use tri-state modulating actuators that incorpo- rate a spring return.

Zone humidity sensor

For measurement of relative humidity (RH), the Tracer ZN521 requires a zone humidity sensor with a 4–20 mA output, where 4 mA is 0% RH and 20 mA is 100% RH. The controller provides 20 Vdc to power the zone humidity sensor.

CO2 sensor

For CO2 measurement, the Tracer ZN521 requires a CO2 sensor with a 4– 20 mA output, where 4 mA = 0 ppm and 20 mA = 2000 ppm.

CNT-SVX07C-EN

5

Image 15
Contents Installation and Operation Tracer ZN521 Zone Controller Page CNT-SVX07C-EN April CNT-SVX07C-EN Tracer ZN521 Zone Controller Installation and Operation CNT-SVX07C-EN Contents Sequence of operations Status indicators for operation and communication Troubleshooting Index Product description Overview and specificationsDimensions Storage environmentClearances Plastic-cover model dimensions and clearances Additional components Agency listing/complianceCO2 sensor Tracer zone temperature sensor optionsDamper actuators Zone humidity sensorOverview and specifications AC-power wiring Input/output terminal wiringGeneral wiring information Communication-link wiring and addressing General wiring information Operating environment requirements Location recommendationsMounting the Tracer ZN521 zone controller Mounting recommendationsHeatElectric Typical applications for the Tracer ZN521 zone controllerApplication SpeedfanMultiple Dehumidification ControlValve EconomizingBinary inputs BI1 Low-coil-temperature detectionBinary inputs BI2 Condensate overflowBI4 Fan status BI3 Occupancy or generic binary inputAnalog inputs ZN Zone temperatureAnalog inputs GND Ground terminalsFAN Fan mode input AI1 Entering water temperatureSET Local setpoint AI3 Outdoor air temperature or generic temperature AI2 Discharge air temperatureAI4 configuration options and associated measurement ranges Configuration Measurement rangeAI4 Universal 4-20 mA AI4 terminal wiring CO2 measurement Binary output Functions Binary outputsGeneric binary output Binary output functionsFunction Input source For more information See Wiring requirements and optionsOverriding binary outputs Required controller inputs for proper operationTwo-pipe hydronic-cooling unit Two-pipe hydronic-heating unit Two-pipe hydronic heating/cooling unit with auto changeover Four-pipe hydronic heating/cooling unit Four-pipe heating/cooling unit with auto changeover Two-pipe heating unit with DX cooling Electric heat unit with DX cooling Electric heat unit Two-pipe heating unit with face-and-bypass damper Two-pipe heating/cooling unit with face-and-bypass damper Four-pipe heating/cooling unit with face-and-bypass damper Input/output functions and wiring for typical applications Random start Power-up sequenceOccupancy modes Occupied modeUnoccupied mode Occupied standby modeTimed override control Occupied bypass modeZone temperature control Cascade zone controlSimplified zone control Morning cool-down Heating or cooling modeDischarge air tempering Morning warm-upFan operation Entering water temperature sampling functionExhaust control Exhaust controlValve control options Valve operationModulating valve operation Modulating valve calibrationTwo-pipe operation Modulating outdoor/return air dampersTwo-position valve operation Isolation-valve operationModulating outdoor air damper position Ashrae Cycle 1 conformance Ashrae Cycle 2 conformanceEconomizing free cooling Face-and-bypass, isolation-valve operation Two-position control of a modulating outdoor air damperFace-and-bypass damper operation DX cooling operationElectric heat operation Baseboard heat operationDehumidification Unit protection strategies Peer-to-peer communicationCondensate overflow Smart resetLow-coil-temperature protection Fan off delayFilter-maintenance timer Freeze protection discharge air temperature low limitFreeze avoidance Tracer ZN521 zone controller circuit board Test buttonManual output test Output For nonClose damper, air Outdoor Open damper, air Outdoor BOP1 BOP2 BOP3 BOP4 BOP5 BOP6 BOP7 BOP8 BOP9 Step ResultLED activity Explanation Service pin buttonRed LED Service indicator Interpreting LEDsYellow LED Communications indicator Green LED Status indicatorTypes of diagnostics DiagnosticsFan unaffected Table of diagnosticsDiagnostics Diagnostic Probable cause Consequences TypePosition Valved unaffectedDamper unaffected Status indicators for operation and communication Probable cause Explanation Fan does not energizeValves remain closed TroubleshootingDX or electric heat does not energize Valves remain openOutdoor air damper remains open Outdoor air damper remains closedOutdoor air damper remains open Troubleshooting Numerics IndexIndex Index Index Page Trane