Chapter 5 Sequence of operations

low-speed fan operation. A controller can also receive a BAS-communi- cated outdoor air damper minimum position.

A BAS-communicated minimum position setpoint has priority over all locally configured setpoints. When a communicated minimum position setpoint is not present, the controller uses the configured minimum posi- tion for low fan speed whenever the fan is running at low speed, regard- less of the occupancy state. See Table 9 and Table 10 for more information about how the controller determines the position of the modulating out- door air damper.

Table 9. Modulating outdoor air damper position setpoint determination

Occupancy

BAS-communicated

Fan speed

Active minimum setpoint

setpoint

 

 

 

 

 

 

 

Unoccupied

Any value

Any value

0% (closed)

 

 

 

 

Occupied

Valid

Any value

BAS-communicated

Occupied bypass

 

 

 

Occupied standby

 

 

 

 

 

 

 

Occupied

Invalid

Low

Occupied low fan minimum

Occupied bypass

 

 

 

Occupied standby

 

 

 

 

 

 

 

Occupied

Invalid

Medium/high

Occupied minimum

Occupied bypass

 

 

 

 

 

 

 

Occupied standby

Invalid

Medium/high

Occupied standby minimum

 

 

 

 

Table 10. Relationship between outdoor temperature sensors and damper position

 

Modulating outdoor air damper position

Outdoor air temperature

Occupied or occupied

 

Occupied standby

 

Unoccupied

 

 

 

 

 

 

bypass

 

 

 

 

 

 

 

 

 

 

 

 

 

No or invalid outdoor air

Open to occupied

 

Open to occupied standby

 

Closed

temperature

minimum position

 

minimum position

 

 

 

 

 

 

 

 

Failed outdoor air sensor

Open to occupied

 

Open to occupied standby

 

Closed

 

minimum position

 

minimum position

 

 

 

 

 

 

 

 

Outdoor air temperature

Economizing; damper

 

Economizing; damper

 

Open and economizing

present and economizing

controlled between

 

controlled between

 

during unit operation; oth-

possible1

occupied minimum

 

occupied standby

 

erwise closed

 

position and 100%

 

minimum position and

 

 

 

 

 

100%

 

 

 

 

 

 

 

 

Outdoor air temperature

Open to occupied mini-

 

Open to occupied standby

 

Closed

present and economizing

mum position

 

minimum position

 

 

not possible1

 

 

 

 

 

1For an explanation of the economizing feature, see “Economizing (free cooling)” on page 45.

44

CNT-SVX07C-EN

Image 54
Contents Installation and Operation Tracer ZN521 Zone Controller Page CNT-SVX07C-EN April CNT-SVX07C-EN Tracer ZN521 Zone Controller Installation and Operation CNT-SVX07C-EN Contents Sequence of operations Status indicators for operation and communication Troubleshooting Index Overview and specifications Product descriptionDimensions Storage environmentClearances Plastic-cover model dimensions and clearances Agency listing/compliance Additional componentsZone humidity sensor Tracer zone temperature sensor optionsDamper actuators CO2 sensorOverview and specifications Input/output terminal wiring AC-power wiringGeneral wiring information Communication-link wiring and addressing General wiring information Location recommendations Operating environment requirementsMounting recommendations Mounting the Tracer ZN521 zone controllerControlValve Economizing Typical applications for the Tracer ZN521 zone controllerApplication SpeedfanMultiple Dehumidification HeatElectricBI2 Condensate overflow BI1 Low-coil-temperature detectionBinary inputs Binary inputsBI3 Occupancy or generic binary input BI4 Fan statusGND Ground terminals ZN Zone temperatureAnalog inputs Analog inputsFAN Fan mode input AI1 Entering water temperatureSET Local setpoint AI2 Discharge air temperature AI3 Outdoor air temperature or generic temperatureAI4 configuration options and associated measurement ranges Configuration Measurement rangeAI4 Universal 4-20 mA AI4 terminal wiring CO2 measurement Binary output functions Binary outputsGeneric binary output Binary output FunctionsRequired controller inputs for proper operation Wiring requirements and optionsOverriding binary outputs Function Input source For more information SeeTwo-pipe hydronic-cooling unit Two-pipe hydronic-heating unit Two-pipe hydronic heating/cooling unit with auto changeover Four-pipe hydronic heating/cooling unit Four-pipe heating/cooling unit with auto changeover Two-pipe heating unit with DX cooling Electric heat unit with DX cooling Electric heat unit Two-pipe heating unit with face-and-bypass damper Two-pipe heating/cooling unit with face-and-bypass damper Four-pipe heating/cooling unit with face-and-bypass damper Input/output functions and wiring for typical applications Power-up sequence Random startOccupied standby mode Occupied modeUnoccupied mode Occupancy modesOccupied bypass mode Timed override controlZone temperature control Cascade zone controlSimplified zone control Morning warm-up Heating or cooling modeDischarge air tempering Morning cool-downEntering water temperature sampling function Fan operationExhaust control Exhaust controlModulating valve calibration Valve operationModulating valve operation Valve control optionsIsolation-valve operation Modulating outdoor/return air dampersTwo-position valve operation Two-pipe operationModulating outdoor air damper position Ashrae Cycle 1 conformance Ashrae Cycle 2 conformanceEconomizing free cooling DX cooling operation Two-position control of a modulating outdoor air damperFace-and-bypass damper operation Face-and-bypass, isolation-valve operationElectric heat operation Baseboard heat operationDehumidification Peer-to-peer communication Unit protection strategiesFan off delay Smart resetLow-coil-temperature protection Condensate overflowFilter-maintenance timer Freeze protection discharge air temperature low limitFreeze avoidance Test button Tracer ZN521 zone controller circuit boardManual output test For non OutputClose damper, air Outdoor Open damper, air Outdoor Step Result BOP1 BOP2 BOP3 BOP4 BOP5 BOP6 BOP7 BOP8 BOP9Interpreting LEDs Service pin buttonRed LED Service indicator LED activity ExplanationGreen LED Status indicator Yellow LED Communications indicatorDiagnostics Types of diagnosticsDiagnostic Probable cause Consequences Type Table of diagnosticsDiagnostics Fan unaffectedValved unaffected PositionDamper unaffected Status indicators for operation and communication Fan does not energize Probable cause ExplanationTroubleshooting Valves remain closedValves remain open DX or electric heat does not energizeOutdoor air damper remains closed Outdoor air damper remains openOutdoor air damper remains open Troubleshooting Index NumericsIndex Index Index Page Trane