Trane N512, Zone Controller, CNT-SVX07C-EN manual Index

Page 82

Index

Switching devices Condensate overflow, 4, 14 Current sensing, 4

Fan status, 4

Freeze protection, 4, 14 Low-coil-temperature, 4 Occupancy, 4, 15

T

Temperature sensors

Table of options, 5

Water and duct, 4

Zone, 4

Termination resistors, 9

Test button, 51–52

Timeclock, 15

Timed override control, 37

Transformers, 4, 7, 8

Troubleshooting DX cooling, 65 Electric heat failure, 65 Fans, 63

Outdoor air damper, 66 Valves, 64

Two-pipe operation, 43

Two-position damper control, 46

Two-position valve operation, 43

Types of diagnostics, 58

U

UL, see Agency listing/compliance

Unit protection strategies Condensate overflow, 49 Discharge air temperature low

limit, 50

Fan off delay, 49 Fan status, 49

Filter-maintenance timer, 50 Freeze avoidance, 50 Freeze protection, 50 Low-coil-temperature

protection, 49 Smart reset, 49

Unit ventilators, 1, 21

Universal 4–20 mA, 19

V

Valves Actuators, 4

Calibration of modulating, 42 Four-pipe operation, 43 General operation, 42 Isolation-valve operation, 43 Operation of modulating, 42 Operation of two-position, 43 Supported applications, 1, 21,

42

Tri-state modulating, 1, 21, 42 Troubleshooting, 64 Two-pipe operation, 43 Two-position, 1, 21

W

Water and duct temperature sensors, 4

Wiring

BAS communication, 9 Compliance with National

Electrical Code, 7, 8, 9 General, 7–9 Input/output terminals, 7 LonTalk communication, 9 Minimum requirements, 22 Requirements and options,

22–34

Wiring diagrams, 22–34 Electric heat unit, 30 Electric heat unit with DX

cooling, 29

Four-pipe heating/cooling unit with auto changeover, 27 Four-pipe heating/cooling unit

with face-and-bypass damper, 33

Four-pipe hydronic heating/ cooling unit, 26

Two-pipe heating unit with DX cooling, 28

Two-pipe heating/cooling unit with face-and-bypass damper, 32

Two-pipe hydronic heating/ cooling unit with auto changeover, 25

Two-pipehydronic-cooling unit, 23

Two-pipehydronic-heating unit, 24

Z

Zone humidity

Sensor, 5

Zone temperature

Input, 16

Sensors, 4

Zone temperature control, 38

Zone temperature failure diagnostic, 59

42

CNT-SVX07C-EN

Image 82
Contents Installation and Operation Tracer ZN521 Zone Controller Page CNT-SVX07C-EN April CNT-SVX07C-EN Tracer ZN521 Zone Controller Installation and Operation CNT-SVX07C-EN Contents Sequence of operations Status indicators for operation and communication Troubleshooting Index Overview and specifications Product descriptionStorage environment DimensionsClearances Plastic-cover model dimensions and clearances Agency listing/compliance Additional componentsZone humidity sensor Tracer zone temperature sensor optionsDamper actuators CO2 sensorOverview and specifications Input/output terminal wiring AC-power wiringGeneral wiring information Communication-link wiring and addressing General wiring information Location recommendations Operating environment requirementsMounting recommendations Mounting the Tracer ZN521 zone controllerControlValve Economizing Typical applications for the Tracer ZN521 zone controllerApplication SpeedfanMultiple Dehumidification HeatElectricBI2 Condensate overflow BI1 Low-coil-temperature detectionBinary inputs Binary inputsBI3 Occupancy or generic binary input BI4 Fan statusGND Ground terminals ZN Zone temperatureAnalog inputs Analog inputsAI1 Entering water temperature FAN Fan mode inputSET Local setpoint AI2 Discharge air temperature AI3 Outdoor air temperature or generic temperatureConfiguration Measurement range AI4 configuration options and associated measurement rangesAI4 Universal 4-20 mA AI4 terminal wiring CO2 measurement Binary output functions Binary outputsGeneric binary output Binary output FunctionsRequired controller inputs for proper operation Wiring requirements and optionsOverriding binary outputs Function Input source For more information SeeTwo-pipe hydronic-cooling unit Two-pipe hydronic-heating unit Two-pipe hydronic heating/cooling unit with auto changeover Four-pipe hydronic heating/cooling unit Four-pipe heating/cooling unit with auto changeover Two-pipe heating unit with DX cooling Electric heat unit with DX cooling Electric heat unit Two-pipe heating unit with face-and-bypass damper Two-pipe heating/cooling unit with face-and-bypass damper Four-pipe heating/cooling unit with face-and-bypass damper Input/output functions and wiring for typical applications Power-up sequence Random startOccupied standby mode Occupied modeUnoccupied mode Occupancy modesOccupied bypass mode Timed override controlCascade zone control Zone temperature controlSimplified zone control Morning warm-up Heating or cooling modeDischarge air tempering Morning cool-downEntering water temperature sampling function Fan operationExhaust control Exhaust controlModulating valve calibration Valve operationModulating valve operation Valve control optionsIsolation-valve operation Modulating outdoor/return air dampersTwo-position valve operation Two-pipe operationModulating outdoor air damper position Ashrae Cycle 2 conformance Ashrae Cycle 1 conformanceEconomizing free cooling DX cooling operation Two-position control of a modulating outdoor air damperFace-and-bypass damper operation Face-and-bypass, isolation-valve operationBaseboard heat operation Electric heat operationDehumidification Peer-to-peer communication Unit protection strategiesFan off delay Smart resetLow-coil-temperature protection Condensate overflowFreeze protection discharge air temperature low limit Filter-maintenance timerFreeze avoidance Test button Tracer ZN521 zone controller circuit boardManual output test For non OutputClose damper, air Outdoor Open damper, air Outdoor Step Result BOP1 BOP2 BOP3 BOP4 BOP5 BOP6 BOP7 BOP8 BOP9Interpreting LEDs Service pin buttonRed LED Service indicator LED activity ExplanationGreen LED Status indicator Yellow LED Communications indicatorDiagnostics Types of diagnosticsDiagnostic Probable cause Consequences Type Table of diagnosticsDiagnostics Fan unaffectedValved unaffected PositionDamper unaffected Status indicators for operation and communication Fan does not energize Probable cause ExplanationTroubleshooting Valves remain closedValves remain open DX or electric heat does not energizeOutdoor air damper remains closed Outdoor air damper remains openOutdoor air damper remains open Troubleshooting Index NumericsIndex Index Index Page Trane