Trane N512, Zone Controller, CNT-SVX07C-EN Test button, Tracer ZN521 zone controller circuit board

Page 61

Red (service) LED

Service pin button

Chapter 6

Status indicators for operation and communication

This chapter describes the operation and communication status indica- tors on the Tracer ZN521 controller, including:

A description of the location and function of the Test button and Ser- vice pin button and the light-emitting diodes (LEDs) located on the controller

A complete list of the diagnostics that can occur, their effect on con- troller outputs, and an explanation of how diagnostics are cleared and the device restored to normal operation

Test button

The Test button is used to perform the manual output test (see “Manual output test” on page 52), which verifies that the controller output devices are operating properly. It is located on the Tracer ZN521 circuit board as shown in Figure 19. You must remove the cover to access the Test button.

Figure 19. Tracer ZN521 zone controller circuit board

Green (status)

LED

Test button

Neuron ID label

Yellow

(communication)

LED

CNT-SVX07C-EN

51

Image 61
Contents Installation and Operation Tracer ZN521 Zone Controller Page CNT-SVX07C-EN April CNT-SVX07C-EN Tracer ZN521 Zone Controller Installation and Operation CNT-SVX07C-EN Contents Sequence of operations Status indicators for operation and communication Troubleshooting Index Product description Overview and specificationsStorage environment DimensionsClearances Plastic-cover model dimensions and clearances Additional components Agency listing/complianceDamper actuators Tracer zone temperature sensor optionsZone humidity sensor CO2 sensorOverview and specifications AC-power wiring Input/output terminal wiringGeneral wiring information Communication-link wiring and addressing General wiring information Operating environment requirements Location recommendationsMounting the Tracer ZN521 zone controller Mounting recommendationsApplication SpeedfanMultiple Dehumidification Typical applications for the Tracer ZN521 zone controllerControlValve Economizing HeatElectricBinary inputs BI1 Low-coil-temperature detectionBI2 Condensate overflow Binary inputsBI4 Fan status BI3 Occupancy or generic binary inputAnalog inputs ZN Zone temperatureGND Ground terminals Analog inputsAI1 Entering water temperature FAN Fan mode inputSET Local setpoint AI3 Outdoor air temperature or generic temperature AI2 Discharge air temperatureConfiguration Measurement range AI4 configuration options and associated measurement rangesAI4 Universal 4-20 mA AI4 terminal wiring CO2 measurement Generic binary output Binary outputsBinary output functions Binary output FunctionsOverriding binary outputs Wiring requirements and optionsRequired controller inputs for proper operation Function Input source For more information SeeTwo-pipe hydronic-cooling unit Two-pipe hydronic-heating unit Two-pipe hydronic heating/cooling unit with auto changeover Four-pipe hydronic heating/cooling unit Four-pipe heating/cooling unit with auto changeover Two-pipe heating unit with DX cooling Electric heat unit with DX cooling Electric heat unit Two-pipe heating unit with face-and-bypass damper Two-pipe heating/cooling unit with face-and-bypass damper Four-pipe heating/cooling unit with face-and-bypass damper Input/output functions and wiring for typical applications Random start Power-up sequenceUnoccupied mode Occupied modeOccupied standby mode Occupancy modesTimed override control Occupied bypass modeCascade zone control Zone temperature controlSimplified zone control Discharge air tempering Heating or cooling modeMorning warm-up Morning cool-downFan operation Entering water temperature sampling functionExhaust control Exhaust controlModulating valve operation Valve operationModulating valve calibration Valve control optionsTwo-position valve operation Modulating outdoor/return air dampersIsolation-valve operation Two-pipe operationModulating outdoor air damper position Ashrae Cycle 2 conformance Ashrae Cycle 1 conformanceEconomizing free cooling Face-and-bypass damper operation Two-position control of a modulating outdoor air damperDX cooling operation Face-and-bypass, isolation-valve operationBaseboard heat operation Electric heat operationDehumidification Unit protection strategies Peer-to-peer communicationLow-coil-temperature protection Smart resetFan off delay Condensate overflowFreeze protection discharge air temperature low limit Filter-maintenance timerFreeze avoidance Tracer ZN521 zone controller circuit board Test buttonManual output test Output For nonClose damper, air Outdoor Open damper, air Outdoor BOP1 BOP2 BOP3 BOP4 BOP5 BOP6 BOP7 BOP8 BOP9 Step ResultRed LED Service indicator Service pin buttonInterpreting LEDs LED activity ExplanationYellow LED Communications indicator Green LED Status indicatorTypes of diagnostics DiagnosticsDiagnostics Table of diagnosticsDiagnostic Probable cause Consequences Type Fan unaffectedPosition Valved unaffectedDamper unaffected Status indicators for operation and communication Probable cause Explanation Fan does not energizeValves remain closed TroubleshootingDX or electric heat does not energize Valves remain openOutdoor air damper remains open Outdoor air damper remains closedOutdoor air damper remains open Troubleshooting Numerics IndexIndex Index Index Page Trane