Trane Zone Controller, N512, CNT-SVX07C-EN manual Power-up sequence, Random start

Page 45

Chapter 5

Sequence of operations

The Tracer ZN521 zone controller will operate to maintain the zone tem- perature setpoint. This chapter discusses many of the operational sequences used by the controller to accomplish this goal.

Power-up sequence

When 24 Vac power is initially applied to the Tracer ZN521 zone control- ler, the following sequence occurs:

1.The green status indicator LED turns on (see “Interpreting LEDs” on page 56).

2.All outputs are controlled off. All modulating valves and dampers close, and the face-and-bypass damper calibrates to bypass (when present).

3.The controller reads all input local values to determine initial values.

4.The random-start timer begins (see “Random start” on page 35).

5.If a hard-wired zone-temperature value is not detected, the controller begins to wait for a communicated value. (This can take several min- utes [15-minute default] and occurs concurrently with the remainder of the power-up sequence.)

6.The random-start timer expires.

7.The power-up control wait function begins automatically if the config- ured power-up control wait time is greater than 0 seconds. When this function is enabled, the controller waits for the configured amount of time (from 0 to 120 seconds) to allow a communicated occupancy request to arrive. If a communicated occupancy request arrives, nor- mal operation can begin. If a communicated occupancy request does not arrive, the controller assumes stand-alone operation.

8.Normal operation begins assuming no diagnostics have been generated.

Random start

Random start is intended to prevent all units in a building from energiz- ing at the same time. The random-start timer delays the fan and any heating or cooling start-up from 5 to 30 seconds. If neither heating nor cooling is initiated, or if fan operation is not required during the delay, the random-start timer will time-out.

CNT-SVX07C-EN

35

Image 45
Contents Installation and Operation Tracer ZN521 Zone Controller Page CNT-SVX07C-EN April CNT-SVX07C-EN Tracer ZN521 Zone Controller Installation and Operation CNT-SVX07C-EN Contents Sequence of operations Status indicators for operation and communication Troubleshooting Index Product description Overview and specificationsDimensions Storage environmentClearances Plastic-cover model dimensions and clearances Additional components Agency listing/complianceDamper actuators Tracer zone temperature sensor optionsZone humidity sensor CO2 sensorOverview and specifications AC-power wiring Input/output terminal wiringGeneral wiring information Communication-link wiring and addressing General wiring information Operating environment requirements Location recommendationsMounting the Tracer ZN521 zone controller Mounting recommendationsApplication SpeedfanMultiple Dehumidification Typical applications for the Tracer ZN521 zone controllerControlValve Economizing HeatElectricBinary inputs BI1 Low-coil-temperature detectionBI2 Condensate overflow Binary inputsBI4 Fan status BI3 Occupancy or generic binary inputAnalog inputs ZN Zone temperatureGND Ground terminals Analog inputsFAN Fan mode input AI1 Entering water temperatureSET Local setpoint AI3 Outdoor air temperature or generic temperature AI2 Discharge air temperatureAI4 configuration options and associated measurement ranges Configuration Measurement rangeAI4 Universal 4-20 mA AI4 terminal wiring CO2 measurement Generic binary output Binary outputsBinary output functions Binary output FunctionsOverriding binary outputs Wiring requirements and optionsRequired controller inputs for proper operation Function Input source For more information SeeTwo-pipe hydronic-cooling unit Two-pipe hydronic-heating unit Two-pipe hydronic heating/cooling unit with auto changeover Four-pipe hydronic heating/cooling unit Four-pipe heating/cooling unit with auto changeover Two-pipe heating unit with DX cooling Electric heat unit with DX cooling Electric heat unit Two-pipe heating unit with face-and-bypass damper Two-pipe heating/cooling unit with face-and-bypass damper Four-pipe heating/cooling unit with face-and-bypass damper Input/output functions and wiring for typical applications Random start Power-up sequenceUnoccupied mode Occupied modeOccupied standby mode Occupancy modesTimed override control Occupied bypass modeZone temperature control Cascade zone controlSimplified zone control Discharge air tempering Heating or cooling modeMorning warm-up Morning cool-downFan operation Entering water temperature sampling functionExhaust control Exhaust controlModulating valve operation Valve operationModulating valve calibration Valve control optionsTwo-position valve operation Modulating outdoor/return air dampersIsolation-valve operation Two-pipe operationModulating outdoor air damper position Ashrae Cycle 1 conformance Ashrae Cycle 2 conformanceEconomizing free cooling Face-and-bypass damper operation Two-position control of a modulating outdoor air damperDX cooling operation Face-and-bypass, isolation-valve operationElectric heat operation Baseboard heat operationDehumidification Unit protection strategies Peer-to-peer communicationLow-coil-temperature protection Smart resetFan off delay Condensate overflowFilter-maintenance timer Freeze protection discharge air temperature low limitFreeze avoidance Tracer ZN521 zone controller circuit board Test buttonManual output test Output For nonClose damper, air Outdoor Open damper, air Outdoor BOP1 BOP2 BOP3 BOP4 BOP5 BOP6 BOP7 BOP8 BOP9 Step ResultRed LED Service indicator Service pin buttonInterpreting LEDs LED activity ExplanationYellow LED Communications indicator Green LED Status indicatorTypes of diagnostics DiagnosticsDiagnostics Table of diagnosticsDiagnostic Probable cause Consequences Type Fan unaffectedPosition Valved unaffectedDamper unaffected Status indicators for operation and communication Probable cause Explanation Fan does not energizeValves remain closed TroubleshootingDX or electric heat does not energize Valves remain openOutdoor air damper remains open Outdoor air damper remains closedOutdoor air damper remains open Troubleshooting Numerics IndexIndex Index Index Page Trane