Chapter 4 Input/output functions and wiring for typical applications
Overriding binary outputs
The Tracer ZN521 controller includes a manual output test and a water valve override feature. Use the manual output test to manually control the outputs in a defined sequence. For information, see “Manual output test” on page 52.
The water valve override feature is a procedure used for water balancing.
Using the Rover service tool or a BAS, a user can specify that a Tracer
ZN521 override the state of water valves to:
•Open all valves
•Close all valves
The controller resets itself to normal operation after two hours.
Wiring requirements and options
Table 7 shows required controller inputs for minimal proper operation of all applications.
Table 7. Required controller inputs for proper operation
Function | Input source | For more information, | |
see: | |||
|
| ||
|
|
| |
24 Vac power | Terminals: GND, 24 V | ||
|
| page 7 | |
|
|
| |
Zone temperature | Terminals: ZN, GND | “ZN: Zone tempera- | |
| or communicated | ture” on page 16 | |
|
|
| |
Discharge air temperature | Terminals: AI2 | “AI2: Discharge air tem- | |
|
| perature” on page 18 | |
|
|
| |
Entering water tempera- | Terminal: AI1 | “AI1: Entering water | |
or communicated | temperature” on | ||
units with auto |
| page 17 | |
changeover |
|
| |
|
|
| |
Outdoor air temperature— | Terminals: AI3 or | “AI3: Outdoor air tem- | |
required only for econo- | communicated | perature or generic | |
mizing |
| temperature” on | |
|
| page 18 | |
|
|
| |
Relative humidity— | Terminals: AI4 | “AI4: Universal 4– | |
required only for dehu- |
| 20 mA” on page 19 | |
midification |
|
| |
|
|
|
Figure 7 on page 23 through Figure 17 on page 33 show typical applica- tions that include all required and all optional components.
22 |
|