Trane CNT-SVX07C-EN, Zone Controller, N512 manual Two-pipe heating unit with DX cooling

Page 38

Chapter 4 Input/output functions and wiring for typical applications

Figure 12. Two-pipe heating unit with DX cooling

Fan status (closed=on)*

Occupancy (open=occupied)*

Condensate overflow (closed=normal)*

Low-coil-temperature detection (closed=normal)*

24 Vac H N

24 V

Fan, high speed

24 V

Exhaust (or fan, medium speed)

24 V

Fan, low speed

24 V

DX cooling

 

24 V

 

 

Heating valve

 

 

24 V

 

 

Outdoor air damper actuator

Open Close

Open Close

24 V

Generic/baseboard heat

 

 

GND 24V 24V 24V BI1

BI2

BI3

BI4

1 2 3 4 5 6 7 8 9 10 STATUS

 

 

 

 

LED

AC POWER

BINARY INPUTS

 

BINARY OUTPUTS

ZONE SENSOR

ANALOG INPUTS

COMM5

 

SERVICE

 

 

 

COMM5

PIN LED ZN GND SET FAN GND AI1

AI2

AI3 +20 AI4 GND A

B A B

LED

On

Cancel

1

 

2

 

3

 

4

 

5 LonTalk

Entering water

6

temperature

Discharge air temperature

}

LonTalk

AI4 input: See

in

Figures 5 and 6

 

on page 20 for

 

wiring options

out

 

Outdoor air or generic temperature

* All binary inputs are configurable.

Connect 24 V to an AC POWER (24V) terminal.

28

CNT-SVX07C-EN

Image 38
Contents Installation and Operation Tracer ZN521 Zone Controller Page CNT-SVX07C-EN April CNT-SVX07C-EN Tracer ZN521 Zone Controller Installation and Operation CNT-SVX07C-EN Contents Sequence of operations Status indicators for operation and communication Troubleshooting Index Overview and specifications Product descriptionClearances DimensionsStorage environment Plastic-cover model dimensions and clearances Agency listing/compliance Additional componentsZone humidity sensor Tracer zone temperature sensor optionsDamper actuators CO2 sensorOverview and specifications Input/output terminal wiring AC-power wiringGeneral wiring information Communication-link wiring and addressing General wiring information Location recommendations Operating environment requirementsMounting recommendations Mounting the Tracer ZN521 zone controllerControlValve Economizing Typical applications for the Tracer ZN521 zone controllerApplication SpeedfanMultiple Dehumidification HeatElectricBI2 Condensate overflow BI1 Low-coil-temperature detectionBinary inputs Binary inputsBI3 Occupancy or generic binary input BI4 Fan statusGND Ground terminals ZN Zone temperatureAnalog inputs Analog inputsSET Local setpoint FAN Fan mode inputAI1 Entering water temperature AI2 Discharge air temperature AI3 Outdoor air temperature or generic temperatureAI4 Universal 4-20 mA AI4 configuration options and associated measurement rangesConfiguration Measurement range AI4 terminal wiring CO2 measurement Binary output functions Binary outputsGeneric binary output Binary output FunctionsRequired controller inputs for proper operation Wiring requirements and optionsOverriding binary outputs Function Input source For more information SeeTwo-pipe hydronic-cooling unit Two-pipe hydronic-heating unit Two-pipe hydronic heating/cooling unit with auto changeover Four-pipe hydronic heating/cooling unit Four-pipe heating/cooling unit with auto changeover Two-pipe heating unit with DX cooling Electric heat unit with DX cooling Electric heat unit Two-pipe heating unit with face-and-bypass damper Two-pipe heating/cooling unit with face-and-bypass damper Four-pipe heating/cooling unit with face-and-bypass damper Input/output functions and wiring for typical applications Power-up sequence Random startOccupied standby mode Occupied modeUnoccupied mode Occupancy modesOccupied bypass mode Timed override controlSimplified zone control Zone temperature controlCascade zone control Morning warm-up Heating or cooling modeDischarge air tempering Morning cool-downEntering water temperature sampling function Fan operationExhaust control Exhaust controlModulating valve calibration Valve operationModulating valve operation Valve control optionsIsolation-valve operation Modulating outdoor/return air dampersTwo-position valve operation Two-pipe operationModulating outdoor air damper position Economizing free cooling Ashrae Cycle 1 conformanceAshrae Cycle 2 conformance DX cooling operation Two-position control of a modulating outdoor air damperFace-and-bypass damper operation Face-and-bypass, isolation-valve operationDehumidification Electric heat operationBaseboard heat operation Peer-to-peer communication Unit protection strategiesFan off delay Smart resetLow-coil-temperature protection Condensate overflowFreeze avoidance Filter-maintenance timerFreeze protection discharge air temperature low limit Test button Tracer ZN521 zone controller circuit boardManual output test For non OutputClose damper, air Outdoor Open damper, air Outdoor Step Result BOP1 BOP2 BOP3 BOP4 BOP5 BOP6 BOP7 BOP8 BOP9Interpreting LEDs Service pin buttonRed LED Service indicator LED activity ExplanationGreen LED Status indicator Yellow LED Communications indicatorDiagnostics Types of diagnosticsDiagnostic Probable cause Consequences Type Table of diagnosticsDiagnostics Fan unaffectedValved unaffected PositionDamper unaffected Status indicators for operation and communication Fan does not energize Probable cause ExplanationTroubleshooting Valves remain closedValves remain open DX or electric heat does not energizeOutdoor air damper remains closed Outdoor air damper remains openOutdoor air damper remains open Troubleshooting Index NumericsIndex Index Index Page Trane